Plan Review Details - Permit 16050068
Plan Review Stops For Permit 16050068
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-25 Cont ID  
Sent By mvaldes Date 2016-05-25 Time 13:15 Rev Time 0.00
Received By mvaldes Date 2016-05-25 Time 12:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2016-05-09 Cont ID  
Sent By mvaldes Date 2016-05-09 Time 11:10 Rev Time 0.00
Received By mvaldes Date 2016-05-09 Time 11:08 Sent To  
Notes
2016-05-09 11:10:12REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - FOLLOWING UP ON FIRE COMMENTS , MATCH ALL DEVICE
 COUNT ON FLOOR PLANS TO THE RISER DIAGRAM. ( SEE FIRE
 REVIEW FOR DETAILS. )

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-24 Cont ID  
Sent By pleduc Date 2016-05-24 Time   Rev Time 0.00
Received By pleduc Date 2016-05-24 Time 14:31 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By mvaldes Date 2016-05-09 Time 11:10 Rev Time 0.00
Received By pleduc Date 2016-05-04 Time 16:28 Sent To E
Notes
2016-05-04 16:35:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET T11 F01 - THERE APPEARS TO DISCREPANCIES IN
 THE DEVICE COUNTS AND CALCULATIONS.
  
 2) SHEET T11 F01 - THERE ARE 11 SMOKE DETECTORS
 INDICATED IN THE DIAGRAM; HOWEVER, 12 ARE INDICATED ON
 THE FLOOR PLAN.
  
 3) SHEET T11 F01 - THERE ARE 9 STROBES INDICATED ON THE
 DIAGRAM AND FLOOR PLANS; HOWEVER, 10 ARE INDICATED IN
 THE CALCULATIONS.
  
 4) SHEET T11 F01 - THE DEVICE TABLES INDICATES 4 WALL
 HORN STROBES; HOWEVER, CEILING MOUNTED HORN STROBES ARE
 INDICATED ON THE FLOOR PLAN.
  
 5) SHEET T11 F01 - 4 HORN STROBES ARE INDICATED ON THE
 FLOOR PLAN AND DEVICE TABLE; HOWEVER, 3 HORN STROBES
 ARE INDICATED IN THE VOLTAGE DROP CALCULATIONS.
  
 PLEASE REVIEW AND PROVIDE ADJUSTMENTS OR CLARIFICATIONS
 WHERE APPLICANLE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-25 Cont ID  
Sent By mvaldes Date 2016-05-25 Time 13:15 Rev Time 0.00
Received By mvaldes Date 2016-05-20 Time 13:27 Sent To  
Notes
2016-05-23 13:27:15RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-09 Cont ID  
Sent By mvaldes Date 2016-05-09 Time 11:10 Rev Time 0.00
Received By mvaldes Date 2016-05-03 Time 12:54 Sent To FIRE
Notes
***NONE***