Plan Review Details - Permit 16050068
| Plan Review Stops For Permit 16050068 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-05-25 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-25 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-05-25 |
Time |
12:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2016-05-09 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-09 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-05-09 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2016-05-09 11:10:12 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - FOLLOWING UP ON FIRE COMMENTS , MATCH ALL DEVICE | | | COUNT ON FLOOR PLANS TO THE RISER DIAGRAM. ( SEE FIRE | | | REVIEW FOR DETAILS. ) |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-05-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-05-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-05-24 |
Time |
14:31 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-05-04 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-09 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-05-04 |
Time |
16:28 |
Sent To |
E |
|
| Notes |
| 2016-05-04 16:35:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET T11 F01 - THERE APPEARS TO DISCREPANCIES IN | | | THE DEVICE COUNTS AND CALCULATIONS. | | | | | | 2) SHEET T11 F01 - THERE ARE 11 SMOKE DETECTORS | | | INDICATED IN THE DIAGRAM; HOWEVER, 12 ARE INDICATED ON | | | THE FLOOR PLAN. | | | | | | 3) SHEET T11 F01 - THERE ARE 9 STROBES INDICATED ON THE | | | DIAGRAM AND FLOOR PLANS; HOWEVER, 10 ARE INDICATED IN | | | THE CALCULATIONS. | | | | | | 4) SHEET T11 F01 - THE DEVICE TABLES INDICATES 4 WALL | | | HORN STROBES; HOWEVER, CEILING MOUNTED HORN STROBES ARE | | | INDICATED ON THE FLOOR PLAN. | | | | | | 5) SHEET T11 F01 - 4 HORN STROBES ARE INDICATED ON THE | | | FLOOR PLAN AND DEVICE TABLE; HOWEVER, 3 HORN STROBES | | | ARE INDICATED IN THE VOLTAGE DROP CALCULATIONS. | | | | | | PLEASE REVIEW AND PROVIDE ADJUSTMENTS OR CLARIFICATIONS | | | WHERE APPLICANLE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-05-25 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-25 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-05-20 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2016-05-23 13:27:15 | RESUB ROUTED TO FIRE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-05-09 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-09 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-05-03 |
Time |
12:54 |
Sent To |
FIRE |
|
| Notes |
|
|
|