Plan Review Details - Permit 16050066
Plan Review Stops For Permit 16050066
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-13 Cont ID  
Sent By cthroop Date 2016-05-13 Time 08:48 Rev Time 0.00
Received By cthroop Date 2016-05-13 Time 08:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By aclange Date 2016-05-06 Time 09:33 Rev Time 0.00
Received By cthroop Date 2016-05-06 Time 09:33 Sent To  
Notes
2016-05-06 09:38:401ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-7918
 [email protected]
  
 1. PROVIDE SHORING PLAN.
 2. RE-USE OF FLOOR SHEATHING PER INSPECTOR APPROVAL.
 FBC 104.9.1
 3. SPECIFY VERTICAL REINFORCEMENT AT NEW STEM WALLS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 [A] 104.9.1 USED MATERIALS AND EQUIPMENT.
 THE USE OF USED MATERIALS WHICH MEET THE REQUIREMENTS
 OF THIS CODE FOR NEW MATERIALS IS PERMITTED. USED
 EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS
 APPROVED BY THE BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-12 Cont ID  
Sent By mvaldes Date 2016-05-12 Time 10:29 Rev Time 0.00
Received By mvaldes Date 2016-05-12 Time 10:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By mvaldes Date 2016-05-04 Time 17:34 Rev Time 0.00
Received By mvaldes Date 2016-05-04 Time 16:51 Sent To B
Notes
2016-05-04 17:35:12REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
 SMOKE ALARMS REQUIRED PER RESIDENTIAL SECTIONS 314 &
 315.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-13 Cont ID  
Sent By cthroop Date 2016-05-13 Time 08:48 Rev Time 0.00
Received By cthroop Date 2016-05-11 Time 13:43 Sent To  
Notes
2016-05-11 13:43:55RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-06 Cont ID  
Sent By cthroop Date 2016-05-06 Time 09:38 Rev Time 0.00
Received By cthroop Date 2016-05-03 Time 15:20 Sent To  
Notes
2016-05-03 15:22:39ELEC