| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | - FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER OWNED |
| | SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM OF 2% |
| | VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR A |
| | MAXIMUM OF 3% VOLTAGE DROP. PLEASE REFERENCE THIS CODE |
| | OR PROVIDE WIRE SIZE IN ACCORDANCE WITH LOAD DEMANDS TO |
| | VERIFY IF VOLTAGE DROP WAS TAKEN INTO CONSIDERATION. |
| | - FBC-E C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING |
| | NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND |
| | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR |
| | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF |
| | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.. |
| | - PROVIDE A DEMAND CALCULATION SUMMARY OF LOAD BEING |
| | ADDED AND A PANEL SCHEDULE SHOWING WIRE / CONDUCTOR / |
| | BREAKER SIZES WITH CIRCUITS BEING IDENTIFIED ON SITE |
| | FLOOR PLAN. WPBA 107 |
| | - MUST COMPLY WITH WIND LOAD RATING MINIMUM |
| | REQUIREMENTS FOR POLE LIGHTS. ( BUILDING PLAN EXAMINER |
| | TO VERIFY ) FBC CHAPTER 16 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |