Plan Review Details - Permit 16050027
Plan Review Stops For Permit 16050027
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-06 Cont ID  
Sent By rmcdouga Date 2016-09-06 Time 18:26 Rev Time 0.00
Received By rmcdouga Date 2016-09-06 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-29 Cont ID  
Sent By rmcdouga Date 2016-06-29 Time 10:19 Rev Time 0.00
Received By rmcdouga Date 2016-06-28 Time 18:12 Sent To  
Notes
2016-06-29 09:30:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A COMPLETE DESCRIPTION OF WORK ON THE PLANS.
 INDICATE WHICH WINDOWS AND DOORS ARE TO BE REPLACED.
 FBC 107.2.1
  
 2) THIS APPEARS TO BE A LEVEL 3 ALTERATION. PROVIDE A
 FLOOR PLAN OF THE EXISTING BUILDING. FBC EXISTING
 BUILDING 505 AND FBC 107.2.1
  
 3) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION SECTION
 R101.4.3 BY SUBMITTING THE REQUIRED CONSTRUCTION
 DOCUMENTS. FBC ENERGY CONSERVATION R101.5.1
  
 4) PROVIDE ADDITIONAL DETAILS ON THE STEEL COLUMN CAP
 INCLUDING THE WELDS. FBC 107.2.1
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 IMPACT PROTECTION DEVICES AND EXTERIOR DOOR TYPES.
  
 6) ON SHEETS 3 AND 8, THE CONSTRUCTION TYPE SHOULD BE
 V-B AND THE OCCUPANCY IS R-3 SINGLE FAMILY DWELLING. ON
 SHEET 3 THE 2010 FBC EDITION OF THE CODE IS CITED AND
 IT SHOULD BE THE 2014 FBC.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-23 Cont ID  
Sent By vperez Date 2016-09-23 Time 14:54 Rev Time 0.00
Received By vperez Date 2016-09-23 Time 14:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-12 Cont ID  
Sent By vperez Date 2016-08-12 Time 08:07 Rev Time 0.00
Received By vperez Date 2016-08-12 Time 08:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-13 Cont ID  
Sent By vperez Date 2016-05-13 Time 11:56 Rev Time 0.00
Received By vperez Date 2016-05-13 Time 11:56 Sent To  
Notes
2016-05-13 12:00:59INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. A PANEL BOARD MUST BE AT THE NEW DETACHED STRUCTURE
 AND A GROUNDING ELECTRODE CONDUCTOR MUST BE SHOWN PER
 E3607.3. SHOW PANEL LOCATION ON FLOOR PLAN OF DETACHED.
 2. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT
 GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC
 107.3.5
 3. SHOW ONE LINE REFLECTING SERVICE AND DETACHED BEING
 FED PER COMMENT ABOVE. FBC 107.3.5
 4. PROVIDE GENERAL NOTES TO INDICATE REQUIREMENTS FOR
 AFCI PROTECTION, TAMPER RESISTANT RECEPTACLES. FBC RES
 E3902 E4002.14
 5. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2016-09-23 Cont ID  
Sent By gjohnson Date 2016-08-26 Time 10:04 Rev Time 0.00
Received By gjohnson Date 2016-08-26 Time 10:04 Sent To  
Notes
2016-08-26 10:05:44GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-06-30 Cont ID  
Sent By tklarge Date 2016-06-30 Time 08:15 Rev Time 0.00
Received By tklarge Date 2016-06-30 Time 08:15 Sent To  
Notes
2016-06-30 08:16:29GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By destabro Date 2016-09-13 Time 13:23 Rev Time 0.00
Received By destabro Date 2016-09-13 Time 13:23 Sent To B
Notes
2016-09-13 13:23:409/13/16 - SCOPE OF WORK UNCHANGED SINCE HPB APPROVAL
 CASE NO.16-18 (APRIL 2016). DLE

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-05-17 Cont ID  
Sent By destabro Date 2016-05-17 Time 12:25 Rev Time 0.00
Received By destabro Date 2016-05-17 Time 12:25 Sent To  
Notes
2016-05-17 12:32:535/17/16 - APPROVED BY HPB AT APRIL 26 (2016) MEETING,
 CONDITIONS MET IN DESIGN SUBMISSION. ALUMINUM
 REPLACEMENT WINDOWS SHALL BE CLEAR GLASS OR LOW-E
 GLASS, BUT NOT TINTED GLASS; FRAMING ELEMENTS,
 INCLUDING MUNTINS AND SASHES, WILL BE WHITE IN COLOR.-
 DLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 13:09 Rev Time 0.00
Received By gjohnson Date 2016-09-16 Time 12:32 Sent To  
Notes
2016-09-16 12:32:22ROUTED TO JORGE VALIDO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 13:09 Rev Time 0.00
Received By gjohnson Date 2016-08-05 Time 12:55 Sent To  
Notes
2016-08-08 12:55:24R22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-29 Cont ID  
Sent By rmcdouga Date 2016-06-29 Time 10:19 Rev Time 0.00
Received By rmcdouga Date 2016-05-02 Time 09:24 Sent To  
Notes
2016-05-03 09:24:57R07 - TRAVELING WITH 16050022

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-16 Cont ID  
Sent By jvalido Date 2016-09-16 Time 17:06 Rev Time 0.00
Received By jvalido Date 2016-09-16 Time 17:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-07 Cont ID  
Sent By jvalido Date 2016-06-07 Time 19:00 Rev Time 0.00
Received By jvalido Date 2016-06-07 Time 18:31 Sent To  
Notes
2016-06-07 19:00:22FLORIDA ENERGY CODE - FBC 2014
  
 (1) HEAT LOAD CALCULATIONS SUBMITTED DO NOT MATCH UNITS
 CAPACITY ON PLANS. CHECK CALCULATIONS AND MAKE
 CORRECTIONS.
 (2) PROVIDE AHRI
 (3) PROVIDE CONDENSER TIE DOWN DETAIL

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-09-23 Cont ID  
Sent By gjohnson Date 2016-09-23 Time 13:07 Rev Time 0.00
Received By gjohnson Date 2016-09-23 Time 13:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-08-26 Cont ID  
Sent By gjohnson Date 2016-08-26 Time 10:10 Rev Time 0.00
Received By gjohnson Date 2016-08-25 Time 13:55 Sent To  
Notes
2016-08-26 10:23:481ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. WATER CLOSETS ARE NOT VENTED. FBC RES. P3101..2.1
  
 2. SHOWER SHALL CONNECT TO HORIZONTAL DRAIN SHOULD NOT
 CONNECT TO VERTICAL STACK ABOVE LAVATORY. PER WPB
 AMEND. TO FBC 107.2.1
  
 3. THE WASHING MACHINE TRAP SHALL BE 2IN. PER FBC RES.
 TABLE P3201.7
  
 4. SHT. 3OF8 SHOWS TANKLESS HEATER NEAR NW CORNER OF
 HOUSE SHT. 8OF8 SHOWS IT NEAR SE CORNER PLEASE CLARIFY.
 PER WPB AMEND. TO FBC 107.2.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By gearl Date 2016-05-05 Time 12:20 Rev Time 0.00
Received By gearl Date 2016-05-05 Time 12:19 Sent To  
Notes
2016-05-05 12:21:17 
  
  
  
 1. WILL NEED GAS PERMIT FOR NEW TANKLESS W/H AND STOVE
 HOOK-UP