Plan Review Details - Permit 16050022
Plan Review Stops For Permit 16050022
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-05-17 Cont ID  
Sent By rmcdouga Date 2017-05-17 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2017-05-17 Time 14:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-05-15 Cont ID  
Sent By rmcdouga Date 2017-05-15 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2017-05-11 Time 19:12 Sent To  
Notes
2017-05-15 14:30:08THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE ENERGY
 FORM R405.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-04-26 Cont ID  
Sent By rmcdouga Date 2017-04-26 Time 11:49 Rev Time 0.00
Received By rmcdouga Date 2017-04-26 Time 06:56 Sent To  
Notes
2017-04-26 11:49:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. THE PRODUCT APPROVALS ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.
  
 2) ON THE ENERGY FORM R405-2014, THE NUMBERS FOR THE
 COOLING BTUS AND THE SEER ARE SWITCHED. THE SEER SHOULD
 BE 16 AND THE BTUS SHOULD BE 18,000. FBC 107.2.1
  
 3) THE AHRI CERTIFICATION LETTER DOES NOT MATCH THE
 MODELS SPECIFIED ON THE PLANS. FBC 107.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-09-07 Cont ID  
Sent By rmcdouga Date 2016-09-07 Time 10:08 Rev Time 0.00
Received By rmcdouga Date 2016-09-06 Time 18:27 Sent To  
Notes
2016-09-06 18:58:28PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS THAT
 HAVE THE SIGNATURES OF THE PREPARER AND THE
 OWNER/AGENT. FBC ENERGY CONSERVATION R103 - COMPLETED
 FORMS R402 OR R405 ARE ACCEPTABLE.
  
 2) PROVIDE SIGNED AND SEALED CALCULATIONS TO VERIFY
 THAT THE (2) 2 X 12 BEAM SPANNING 15 FEET CAN SUPPORT
 THE 40 PSF LIVE LOAD AND DEAD LOAD OF THE BALCONY. FBC
 107.2.1.3
  
 3) THE PLANS DO NOT SPECIFY ANY CROSS BRACING OF THE
 DECK OR THE 4 X 4 POSTS THAT ARE SUPPORTING THE DECK.
 PROVIDE SIGNED AND SEALED CALCULATIONS TO SHOW THAT THE
 4" X 4" X 8' WOOD POSTS ARE CAPABLE OF RESISTING THE
 LATERAL LOADS, WIND LOADS, ETC.
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE RIDGE
 OR ROOF VENT, THE SIDING (IF IT IS ALUMINUM OR VINYL)
 AND THE ALUMINUM SOFFIT MATERIAL.
  
 5) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 SINGLE OUTSWING DOOR HAS A MAXIMUM NEGATIVE DESIGN
 PRESSURE FOR THE DOOR OF (-50 PSF) IS NOT ADEQUATE FOR
 THE DOOR LOCATED ON THE FIRST FLOOR IN THE END ZONE,
 WHICH REQUIRES -54.8 PSF. SUBMIT CORRECT PRODUCT
 APPROVALS. FBC-R301.2.1
  
 6) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 SECTIONAL GARAGE DOOR HAS MAXIMUM DESIGN PRESSURES OF
 +36, -42.5 PSF WHICH ARE NOT ADEQUATE. THE PLANS
 SPECIFY THAT THE REQUIRED PRESSURES ARE +37.5, -42.5
 PSF. SUBMIT CORRECT PRODUCT APPROVALS. FBC-R301.2.1
  
 7) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORTS
 WITH INSTALLATION REQUIREMENTS FOR THE OPEN CELL SPRAY
 FOAM INSULATION THAT IS SPECIFIED ON THE PLANS. FBC
 R316
  
 8) THE SECOND FLOOR OF THIS STRUCTURE IS CONDITIONED
 SPACE. THE FLOOR/CEILING ASSEMBLY ABOVE THE GARAGE IS
 REQUIRED TO HAVE THERMAL INSULATION. FBC ENERGY
 CONSERVATION R402.1
  
 9) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-28 Cont ID  
Sent By rmcdouga Date 2016-06-28 Time 16:37 Rev Time 0.00
Received By rmcdouga Date 2016-06-24 Time 18:56 Sent To  
Notes
2016-06-28 13:56:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS THAT
 HAVE THE SIGNATURES OF THE PREPARER AND THE
 OWNER/AGENT. FBC ENERGY CONSERVATION R103
  
 2) THERE ARE SEVERAL ERRORS ON SHEET 2 OF THE PLANS.
 THERE IS A WALL SECTION MARKER (1 ON 5) SHOWN IN THE
 OPEN AREA IN THE GARAGE. THE TYPE OF CONSTRUCTION IS
 V-B AND THE OCCUPANCY TYPE IS R-3, SINGLE FAMILY
 DWELLING. FBC 310.5
  
 3) SHOW COMPLIANCE WITH FBC-R311.7.8 FOR REQUIRED
 HANDRAILS AND FBC-R311.7.8.1 FOR HANDRAIL HEIGHT.
  
 4) SPECIFY THE REQUIRED LIVE LOADS FOR THE DWELLING AND
 BALCONY FLOORS AND THE STAIRS ON THE PLANS. FBC R301.5
  
 5) NONE OF THE WINDOWS ON THE SECOND FLOOR MEET THE
 EMERGENCY ESCAPE AND RESCUE REQUIREMENTS OF FBC-R310
 FOR SLEEPING ROOMS. THE STORAGE AREA CAN NOT BE USED
 FOR SLEEPING UNLESS THERE IS A WINDOW THAT COMPLIES
 WITH FBC-R310.
  
 6) PROVIDE CALCULATIONS TO VERIFY THAT THE (2) 2 X 12
 BEAM SPANNING 15 FEET CAN SUPPORT THE 40 PSF LIVE LOAD
 AND DEAD LOAD OF THE BALCONY. FBC 107.2.1.3
  
 7) THE SECOND FLOOR OF THIS STRUCTURE IS CONDITIONED
 SPACE. THE FLOOR/CEILING ASSEMBLY ABOVE THE GARAGE IS
 REQUIRED TO HAVE THERMAL INSULATION. FBC ENERGY
 CONSERVATION R402.1
  
 8) THE SECOND FLOOR DWELLING AREA IS REQUIRED TO BE
 SEPARATED FROM THE GARAGE BY 5/8" TYPE X DRYWALL OR
 EQUIVALENT PER FBC-R302.6 AND TABLE 302.6.
  
 9) FBC-R302.5 REQUIRES OPENINGS IN THE GARAGE CEILING
 TO BE PROTECTED IN ACCORDANCE WITH FBC-R302.11(4).
  
 10) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 DIFFERENT RIDGE OR ROOF VENT, THE SIDING AND THE
 ALUMINUM SOFFIT MATERIAL.
  
 11) THE PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR A
 DOUBLE OUTSWING DOOR AND THE PLANS SPECIFY A SINGLE
 OUTSWING DOOR. THE MAXIMUM NEGATIVE DESIGN PRESSURE FOR
 THE DOOR (-50 PSF) IS NOT ADEQUATE FOR THE DOOR LOCATED
 ON THE FIRST FLOOR IN EDGE ZONE 5, WHICH REQUIRES -54.8
 PSF. SUBMIT CORRECT PRODUCT APPROVALS. FBC-R301.2.1
  
 12) SUBMIT TWO SETS OF SURFACE WATER DRAINAGE PLANS
 THAT SHOW COMPLIANCE WITH FBC-R401.3.
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-03-28 Cont ID  
Sent By vperez Date 2017-03-28 Time 12:46 Rev Time 0.00
Received By vperez Date 2017-03-28 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-12 Cont ID  
Sent By vperez Date 2016-08-12 Time 08:06 Rev Time 0.00
Received By vperez Date 2016-08-12 Time 08:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-13 Cont ID  
Sent By vperez Date 2016-05-13 Time 11:31 Rev Time 0.00
Received By vperez Date 2016-05-13 Time 11:01 Sent To  
Notes
2016-05-13 11:55:56INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. SHOW A SMOKE DETECTOR AT THE LANDING AREA OF STAIRS
 AND THROUGHOUT PER FBC RES 314 & 315.
 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS.
 3. PANEL BOARD MUST BE AT THE NEW DETACHED STRUCTURE
 AND A GROUNDING ELECTRODE CONDUCTOR MUST BE SHOWN PER
 E3607.3. SHOW PANEL LOCATION ON FLOOR PLAN OF DETACHED.
 4. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT
 GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC
 107.3.5
 5. PROVIDE PANEL SCHEDULE ON SHEET 6 OF THIS STRUCTURE.
 FBC 107.3.5
 6. PROVIDE GENERAL NOTES TO INDICATE REQUIREMENTS FOR
 AFCI PROTECTION, TAMPER RESISTANT RECEPTACLES. FBC RES
 E3902 E4002.14
 7. GARAGE DOOR OPENER TO BE LABELED GFCI PROTECTED PER
 FBC RES E3902.2
 8. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 12:53 Rev Time 0.00
Received By gjohnson Date 2016-08-26 Time 10:00 Sent To  
Notes
2016-08-26 10:02:44GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-05-11 Cont ID  
Sent By rmcdouga Date 2017-05-15 Time 14:28 Rev Time 0.00
Received By destabro Date 2017-05-11 Time 09:09 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-04-05 Cont ID  
Sent By destabro Date 2017-04-05 Time 09:32 Rev Time 0.00
Received By destabro Date 2017-04-05 Time 09:32 Sent To B
Notes
2017-04-05 09:33:184/5/2017 - REVISIONS STILL MEET HPB APPROVED PLANS. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-09-13 Cont ID  
Sent By destabro Date 2016-09-13 Time 13:21 Rev Time 0.00
Received By destabro Date 2016-09-13 Time 13:21 Sent To B
Notes
2016-09-13 13:22:479/13/16 - SCOPE OF WORK UNCHANGED SINCE HPB APPROVAL
 CASE NO.16-18 (APRIL 2016). DLE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-05-15 Cont ID  
Sent By rmcdouga Date 2017-05-15 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2017-05-05 Time 16:26 Sent To HIST
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-04-26 Cont ID  
Sent By rmcdouga Date 2017-04-26 Time 11:49 Rev Time 0.00
Received By rmcdouga Date 2017-03-24 Time 15:51 Sent To  
Notes
2017-03-27 15:52:05R28

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 12:53 Rev Time 0.00
Received By gjohnson Date 2016-09-16 Time 12:31 Sent To  
Notes
2016-09-16 12:31:47ROUTED TO JORGE VALIDO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 12:53 Rev Time 0.00
Received By gjohnson Date 2016-08-05 Time 12:54 Sent To  
Notes
2016-09-16 17:32:15ROUTED TO GEORGE JOHNSON 9/16/2016 JDV
2016-08-08 12:54:14R22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-08 Cont ID  
Sent By rmcdouga Date 2016-06-28 Time 16:37 Rev Time 0.00
Received By lmarchan Date 2016-06-28 Time 16:37 Sent To  
Notes
2016-05-03 09:22:45R07 - TRAVELING WITH 16050027

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2017-05-17 Cont ID  
Sent By rmcdouga Date 2017-05-17 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2017-05-17 Time 14:38 Sent To  
Notes
2017-05-17 14:38:53MU 2017-13640

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-05-11 Cont ID  
Sent By rmcdouga Date 2017-05-11 Time 19:12 Rev Time 0.00
Received By rmcdouga Date 2017-05-11 Time 19:12 Sent To  
Notes
2017-05-11 19:13:46BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-09-06 Cont ID  
Sent By rmcdouga Date 2016-09-06 Time 18:27 Rev Time 0.00
Received By rmcdouga Date 2016-09-06 Time 18:27 Sent To  
Notes
2016-09-06 18:28:08BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By rmcdouga Date 2016-06-24 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2016-06-24 Time 18:57 Sent To  
Notes
2016-06-24 18:57:47BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-04-21 Cont ID  
Sent By hmoser Date 2017-04-21 Time 10:51 Rev Time 0.00
Received By hmoser Date 2017-04-20 Time 16:13 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-16 Cont ID  
Sent By jvalido Date 2016-09-16 Time 17:31 Rev Time 0.00
Received By jvalido Date 2016-09-16 Time 17:24 Sent To  
Notes
2016-09-16 17:31:22CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENT
  
 (1) PROVIDE LOCATION OF CONDENSER ON PLANS.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (2) FORM R405 - 2014 ENERGY CALCULATIONS REQUIRED
 (3) HEATLOAD CALCULATIONS REQUIRED.
 (4) AHRI IS REQUIRED FOR EQUIPMENT SPECIFIED ON PLANS.
  
 (3) PROVIDE AHRI FOR EQUIPMENT SPECIFIED ON PLANS.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-07 Cont ID  
Sent By jvalido Date 2016-06-07 Time 19:07 Rev Time 0.00
Received By jvalido Date 2016-06-07 Time 19:03 Sent To  
Notes
2016-06-07 19:07:28CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL - 107.2 CONSTRUCTION DOCUMENTS - 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 PROVIDE MECHANICAL PLANS FOR LOFT.
  
 FLORIDA ENERGY CODE - FBC 2014
  
 (2) PROVIDE ENERGY CALCULATIONS
 (3) PROVIDE HEAT LOAD CALCULATIONS
 (4) PROVIDE AHRI
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-04-14 Cont ID  
Sent By gjohnson Date 2017-04-14 Time 11:45 Rev Time 0.00
Received By gjohnson Date 2017-04-14 Time 11:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-26 Cont ID  
Sent By gjohnson Date 2016-08-26 Time 10:00 Rev Time 0.00
Received By gjohnson Date 2016-08-25 Time 13:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-06-30 Cont ID  
Sent By gearl Date 2016-06-30 Time 06:33 Rev Time 0.00
Received By tklarge Date 2016-06-30 Time 06:30 Sent To  
Notes
2016-05-05 12:16:23 
  
  
  
 PLANS SHOW FUTURE BATHROOM
  
 GEORGE EARL PLUMBING PLANS REVIEWER 0013 B

Review Stop Z ZONING
Rev No 3 Status P Date 2017-04-19 Cont ID  
Sent By destabro Date 2017-04-19 Time 15:22 Rev Time 0.00
Received By destabro Date 2017-04-19 Time 15:22 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By destabro Date 2016-09-13 Time 13:22 Rev Time 0.00
Received By destabro Date 2016-09-13 Time 13:22 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-17 Cont ID  
Sent By destabro Date 2016-05-17 Time 13:11 Rev Time 0.00
Received By destabro Date 2016-05-17 Time 13:11 Sent To  
Notes
2016-05-17 13:12:195/17/16 - HPD APPROVED PLANS AT APRIL 26 MEETING;
 PROPOSED PLANS MATCH APPROVED CONDITIONS, AND DESIGN
 MEETS LDR STANDARDS. DLE