Plan Review Details - Permit 16041291
| Plan Review Stops For Permit 16041291 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-06-06 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-06-06 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-06-06 |
Time |
13:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-05-02 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-02 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-05-02 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2016-05-02 14:06:25 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - PROVIDE GROUNDING DETAIL SHOWING GROUNDING ELECTRODE | | | SYSTEM IN ACCORDANCE WITH NEC 250.50 AND 250.94 | | | INTERSYSTEM BONDING. | | | SHOW EXISTING RISER WIRE SIZE AND PROVIDE LOAD CALCS TO | | | VERIFY LOAD DEMANDS, A MORE ACCURATE PANEL SCHEDULE | | | SHOWING EXISTING CIRCUITS. WPBA 107 | | | | | | - NEC 225.37 IDENTIFICATION. WHERE A BUILDING OR | | | STRUCTURE HAS ANY | | | COMBINATION OF FEEDERS, BRANCH CIRCUITS, OR SERVICES | | | PASSING | | | THROUGH IT OR SUPPLYING IT, A PERMANENT PLAQUE OR | | | DIRECTORY | | | SHALL BE INSTALLED AT EACH FEEDER AND BRANCH-CIRCUIT | | | DISCONNECT | | | LOCATION DENOTING ALL OTHER SERVICES, FEEDERS, OR | | | BRANCH CIRCUITS | | | SUPPLYING THAT BUILDING OR STRUCTURE OR PASSING THROUGH | | | THAT | | | BUILDING OR STRUCTURE AND THE AREA SERVED BY EACH. | | | | | | - NEC 408.4(B) PANEL BOARDS SHALL HAVE A LABEL MARKING | | | WERE THE LOCATION OF THE SOURCE OF POWER SUPPLY. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-05-02 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-02 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-04-29 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2016-04-29 14:32:51 | ELEC -$5000 |
|
|
|