Plan Review Details - Permit 16041276
Plan Review Stops For Permit 16041276
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-16 Cont ID  
Sent By jwitmer Date 2016-08-16 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2016-08-16 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-19 Cont ID  
Sent By jwitmer Date 2016-07-19 Time 15:58 Rev Time 0.00
Received By jwitmer Date 2016-07-19 Time 15:28 Sent To  
Notes
2016-07-19 15:58:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041276
 ADD: 2900 N. AUSTRALIAN AVE.
 CONT: DC CONSTRUCTION
 TEL: 561-988-8505
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY 19/2016
 ACTION: DENIED
  
 1) REMOVE VOIDED SHEETS FROM THE PLANS!!!!!! COMMENT #
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
  
 2-3) COMPLIED.
  
 4) 2ND REQUEST . THE PLANS SHOW A RATED CORRIDOR BUT
 THERE IS A CLOSET WITHIN THE FIRE RATED CORRIDOR THAT
 IS NOT A 1 HOUR RATING NOR OPENING PROTECTIVE ON THE
 DOORS OR THE DOOR TO THE RESTROOM. FBC-B 466.8
 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE CONSTRUCTED
 OF WALLS HAVING NOT LESS THAN A 1-HOUR FIRE-RESISTANCE
 RATING. WHERE THE CORRIDOR CEILING IS AN ASSEMBLY
 HAVING 1-HOUR FIRE-RESISTANCE RATING WHERE TESTED AS A
 WALL, THE CORRIDOR WALLS SHALL BE PERMITTED TO
 TERMINATE AT THE CORRIDOR CEILING.
  
 5) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-19 Cont ID  
Sent By jwitmer Date 2016-05-19 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2016-05-19 Time 15:26 Sent To  
Notes
2016-05-19 16:45:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041276
 ADD: 2900 N. AUSTRALIAN AVE.
 CONT: DC CONSTRUCTION
 TEL: 561-988-8505
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 19/2016
 ACTION: DENIED
  
 1) SHEET A2.0
 1A) THE PLANS INDICATE THERE IS TO BE AN ADULT DAY CARE
 CENTER. NONE OF THE ROOMS INDICATED ON THIS SHEET
 INDICATE WHICH ROOM IS GOING TO BE USED FOR THE
 DAYCARE. PLEASE NOTE THE MAIN ACTIVITY AREA INDICATES
 2077 SQ. FT. WHEN THIS ROOM IS USED AS A MULT-PURPOSE
 ROOM AND 15 SQ. FT./ OCCUPANT THE 139.
 DOORS D107 & D111 BOTH SWING AGAINST THE MEANS OF
 EGRESS. 2014 FBC-B 1008.1.2. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 1B) 2014 FBC-B 463.1. ADULT DAY CARE FACILITIES SHALL
 COMPLY WITH THE FOLLOWING DESIGN AND CONSTRUCTION
 STANDARDS. AGENCY FOR HEALTH CARE ADMINISTRATION (AHCA)
 RULE 58A-6, FLORIDA ADMINISTRATIVE CODE, AND CHAPTER
 400, PART V, FLORIDA STATUTES. PLEASE PROVIDE PLANS
 STAMPED BY THE STATE AGENCY FOR APPROVAL.
  
 1B) AREAS THAT ARE IN QUESTION IF THEY ARE GOING TO BE
 PART OF THE ADULT DAY CARE CENTER ARE THE FIRST AID
 STATION AND THE YOUTH ACTIVITY ROOM. FBC-B 463.5.4 A
 PRIVATE AREA SHALL BE AVAILABLE FOR THE PROVISION OF
 FIRST AID, SPECIAL CARE AND COUNSELING SERVICES WHEN
 PROVIDED, OR AS NECESSARY FOR OTHER SERVICES REQUIRED
 BY PARTICIPANTS. THIS AREA SHALL BE APPROPRIATELY
 FURNISHED AND EQUIPPED.
 466.7 DETECTION AND ALARM SYSTEMS. DAY CARE OCCUPANCIES
 SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM IN
 ACCORDANCE WITH SECTION 907 AND THIS SECTION.
  
 1C) THE PLANS DO NOT INDICATE IF THE BUILDING IS FIRE
 SPRINKLERED OR NOT?
  
 2) FBC-B 466.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE
 SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 3) FBC-B 466.6 PROTECTION FROM HAZARDS. ROOMS OR SPACES
 FOR THE STORAGE, PROCESSING OR USE OF MATERIALS
 SPECIFIED BELOW SHALL BE PROTECTED IN ACCORDANCE WITH
 THE FOLLOWING.
  
 466.6.1
 THE FOLLOWING ROOMS OR SPACES SHALL BE SEPARATED FROM
 THE REMAINDER OF THE BUILDING BY FIRE BARRIERS HAVING A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR OR SHALL
 BE PROTECTED BY AN APPROVED AUTOMATIC EXTINGUISHING
 SYSTEM.
  
 ROOMS OR SPACES USED FOR THE STORAGE OF COMBUSTIBLE
 SUPPLIES IN QUANTITIES DEEMED HAZARDOUS BY THE BUILDING
 OFFICIAL.
  
 JANITOR CLOSETS. EXCEPTION: DOORS TO JANITOR CLOSETS
 SHALL BE PERMITTED TO HAVE VENTILATING LOUVERS WHERE
 THE SPACE IS PROTECTED BY AUTOMATIC SPRINKLERS.
  
 4) FBC-B 466.8 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL
 BE CONSTRUCTED OF WALLS HAVING NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING.
  
 EXCEPTIONS:
  
 1. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTIONS 901.6 AND 903.3.1.1, CORRIDOR WALLS SHALL
 NOT BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS
 FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 710.
  
 2. WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING
 1-HOUR FIRE-RESISTANCE RATING WHERE TESTED AS A WALL,
 THE CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE CORRIDOR CEILING.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO WHOM IT MAY CONCERN:
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-08-10 Cont ID  
Sent By vperez Date 2016-08-10 Time 08:29 Rev Time 0.00
Received By vperez Date 2016-08-10 Time 08:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-06-30 Cont ID  
Sent By vperez Date 2016-06-30 Time 11:49 Rev Time 0.00
Received By vperez Date 2016-06-30 Time 11:49 Sent To  
Notes
2016-06-30 13:12:292ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADDRESS PENDING BUILDING AND MECHANICAL
 REVIEWER COMMENTS FOR AN ELECTRICAL APPROVAL.
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-10 Cont ID  
Sent By vperez Date 2016-05-10 Time 09:09 Rev Time 0.00
Received By vperez Date 2016-05-09 Time 11:06 Sent To  
Notes
2016-05-10 09:12:18APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY THE CONTACTOR SHOWN ON ONE-LINE RISER
 DIAGRAM FOR PORTABLE GENERATOR SHOWN. PER NEC 702.5, A
 LISTED TRANSFER SWITCH IS TO USED IN THIS APPLICATION.
 2. PROVIDE A NOTE TO PROVIDE TAMPER RESISTANT
 RECEPTACLES FOR THE CLASSROOM AREA AS SHOWN ON FLOOR
 PLAN. NEC 406.14
 3. SHOW THAT THERE IS A WP/GFCI RECEPTACLE WITHIN 25FT
 OF THE ROOFTOP UNITS, SHOW LOADS ON PANEL SCHEDULE. NEC
 210.63
 4. PROVIDE A NOTE TO INDICATE REQUIRED LOW VOLTAGE
 SYSTEMS (ACCESS, DATA ETC.) SEPARATE PERMITS. A NOTE
 WILL SUFFICE.
 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-08-05 Cont ID  
Sent By pleduc Date 2016-08-05 Time   Rev Time 0.00
Received By pleduc Date 2016-08-05 Time 10:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-24 Cont ID  
Sent By pleduc Date 2016-06-24 Time   Rev Time 0.00
Received By pleduc Date 2016-06-24 Time 14:45 Sent To  
Notes
2016-06-24 14:59:24THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) ONLY ONE (1) SHEET OF PLANS SHEETS IS PROPERLY
 COLALATED.
  
 PLEASE COLLATE THE 2ND SET
  
 FIRE HAS STAMPED AND DATE THE CURRENT FACE SHEET A
 1.00.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-03 Cont ID  
Sent By pleduc Date 2016-05-03 Time   Rev Time 0.00
Received By pleduc Date 2016-05-03 Time 11:14 Sent To  
Notes
2016-05-03 13:03:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 2.20 - THE MAIN ACTIVITY ROOM OCCUPACNY LOAD
 CLACULATION INDICATES 46.1; HOWEVER, 6 TABLES WITH 8
 CHAIRS, 6 SITTING CHAIRS AND 3 BAR CHAIRS ARE SHOWN
 INDICATING 57 SITTING PLACES; EXCEEDING THE OCCUPATION
 LOAD.
  
 PLEASE CORRECT OR CLARIFY.
  
 2) SHEET A 2.20 - DOORS D107 & D 111 INDICATING
 IN-SWINGING AGAINST THE FLOW OF EGRESS.
  
 PER SECTION NFPA 101, DOOR SWING DIRECTION, 7.2.1.4.2,
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
 THECOMBINED OCCUPANCY LOAD EXCEEDS 50.
  
 PLEASE CORRECT.
  
 3) SHEET A 2.20 - THERE ARE STORAGE ROOMS AND A LAUNDRY
 ROOM INDICATED. PER NFPA CAHPTER 16
  
 16.3.2 PROTECTION FROM HAZARDS.
 16.3.2.1 ROOMS OR SPACES FOR THE STORAGE, PROCESSING,
 OR USE OF MATERIALS SPECIFIED IN 16.3.2.1(1) THROUGH
 (3) SHALL BE PROTECTED IN ACCORDANCE WITH THE
 FOLLOWING:
 (1) SEPARATION FROM THE REMAINDER OF THE BUILDING BY
 FIRE BARRIERS HAVING A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING, OR PROTECTION OF SUCH ROOMS BY AUTOMATIC
 EXTINGUISHING SYSTEMS AS SPECIFIED IN SECTION 8.7, IN
 THE FOLLOWING AREAS:
 (A) BOILER AND FURNACE ROOMS, UNLESS SUCH ROOMS ENCLOSE
 ONLY AIR-HANDLING EQUIPMENT
 (B) ROOMS OR SPACES USED FOR THE STORAGE OF COMBUSTIBLE
 SUPPLIES IN QUANTITIES DEEMED HAZARDOUS BY THE
 AUTHORITY HAVING JURISDICTION
 (C) ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS
 MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS
 INQUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS
 (D) JANITOR CLOSETS
  
 (2) SEPARATION FROM THE REMAINDER OF THE BUILDING BY
 FIRE BARRIERS HAVING A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING AND PROTECTION OF SUCH ROOMS BY AUTOMATIC
 EXTINGUISHING SYSTEMS AS SPECIFIED IN SECTION 8.7 IN
 THE FOLLOWING AREAS:
 (A)* LAUNDRIES
 (B) MAINTENANCE SHOPS, INCLUDING WOODWORKING AND
 PAINTING AREAS
 (C) ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE AUTHORITY
 HAVING JURISDICTION
 (D) ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS
 IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
  
 PLEASE PROVIDE FOR PROPER PROTECTION FROM THESE AREAS.
  
 4) SHEET A 2.00 - NOTE E INDICATES A 30" BUILT-IN OVEN.
 PER NFPA CHAPTER 16
  
 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH 9.2.3, UNLESS OTHERWISE PERMITTED BY
 16.3.2.4 OR 16.3.2.5.
 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED
 BETWEEN FOOD PREPARATION AREAS AND DINING AREAS.
 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR
 FOOD WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED
 TO BE PROTECTED.
  
 PLEASE PROVIDE DETAILS AND ENFORCEMENT POLICIES TO
 COMPLY WITH THE ABOVE OF 9.2.3 SHALL APPLY.
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FORVENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
  
 5) SHEET A 2.20 - THERE ARE ROOMS THAT INDICATE MEETING
 SPACE FOR CLEINTS. PER NFPA 101, CHAPOTER 16
  
 16.2.11.1 WINDOWS FOR RESCUE.
 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT
 LESS THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH ALL OF THE FOLLOWING, UNLESS OTHERWISE
 PERMITTED BY 16.2.11.1.2:
  
 PLEASE PROVIDE.
  
 ADDITIONAL COMMENTS MAY BE ADDED BASED ON THE
 RESUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-19 Cont ID  
Sent By tklarge Date 2016-08-19 Time 09:10 Rev Time 0.00
Received By tklarge Date 2016-08-19 Time 09:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-17 Cont ID  
Sent By tklarge Date 2016-08-17 Time 11:45 Rev Time 0.00
Received By tklarge Date 2016-07-27 Time 13:08 Sent To  
Notes
2016-07-28 13:08:37C19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-19 Cont ID  
Sent By jwitmer Date 2016-07-19 Time 15:59 Rev Time 0.00
Received By jwitmer Date 2016-06-22 Time 15:34 Sent To  
Notes
2016-06-22 15:34:27C19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-19 Cont ID  
Sent By C13 Date 2016-05-19 Time 16:58 Rev Time 0.00
Received By cpuell Date 2016-04-28 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-08-04 Cont ID  
Sent By ccole Date 2016-08-04 Time 06:52 Rev Time 0.00
Received By ccole Date 2016-08-04 Time 06:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-19 Cont ID  
Sent By ccole Date 2016-06-27 Time 16:23 Rev Time 0.00
Received By ccole Date 2016-06-27 Time 12:41 Sent To  
Notes
2016-06-27 12:46:522ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041276
 6/27/16
  
 1) THE VOIDED PLAN SHEETS MUST BE REMOVED FROM THE
 RESUBMITTED PLAN SETS- SECTION 107.2.1.4 WPB AMENDMENTS
 TO THE FBC:
  
 QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 2) THE STRUCTURAL PLANS EXAMINER HAS DETERMINED THE
 OCCUPANT LOADS FOR THE MULTI-USE AREAS TO BE GREATER
 THAN THE LOADS USED IN THE VENTILATION CALULATION ON
 SHEET M1.1. IF THE ENGINEER IS CHOOSING TO USE THE
 EXCEPTION UNDER SECTION 403.3, AS HE IS STATING IN THE
 RESPONSE NARRATIVE, THEN SUFFICIENT DOCUMENTATION MUST
 BE SUBMITTED TO JUSTIFY THE REDUCED OCCUPANT LOAD AND
 O/A REQUIERMENT- SEE SECTION 403.3 EXCEPTION.
  
 3) REFER TO SECTION 504.5 AND PROVIDE A MEANS OF MAKEUP
 AIR FOR THE DRYER IN THE CLOSET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-10 Cont ID  
Sent By ccole Date 2016-05-10 Time 14:21 Rev Time 0.00
Received By ccole Date 2016-05-10 Time 14:21 Sent To  
Notes
2016-05-10 15:17:171ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041276
 5/10/16
  
 1) M1.1: THE VENTILATION CALCULATIONS DO NOT INCLUDE
 BREAKDOWNS FOR THE CLASSROOMS AND THE ACTIVITY ROOM.
 2) M1.1: THE VENTILATION CALCULATIONS APPEAR TO BE
 INCORRECT FOR THE MULTI-USE ASSEMBLY WHICH MUST BE
 BASED ON AN OCCUPANT DENSITY OF 100 PERSONS PER 1000 SF
 PER TABLE 403.3.
 3) REFER TO SECTION 507.2.2 FBC-14 MECHANICAL AND
 PROVIDE SPECIFACATIONS FOR THE OVEN AND MICROWAVE IN
 THE KITCHENETTE. IF A HEAT HOOD IS NOT TO BE INSTALLED
 PROVIDE AN EXHAUST VENTILATION CALCULATION,
 4) REFER TO SECTION C403.2.5.1 FBC-14 ENERGY
 CONSERVATION: DEMAND CONTROLLED VENTILATION IS REQUIRED
 FOR THE MULTI-USE ASSEMBLY ROOM, ACTIVITY ROOM, AND
 CLASSROOMS. INDICATE A MEANS OF COMPLIANCE ON THE PLANS
 AND PROVIDE SPECIFICATIONS.
 5) PROVIDE A MECHANICAL ROOF PLAN WITH CLEARANCE
 DISTANCE MEASUREMENTS FOR THE O/A INTAKES TO EXHAUST
 OUTLETS AND VENTS, AND THE DISTANCES FROM EQUIPEMENT TO
 ROOF EDGES- SEE SECTIONS 401.4 AND 304.11.
 6) PROVIDE WIND LOAD TIE-DOWN ENGINEERING FOR
 INSTALLATION OF THE RTU'S AND RTU CURBS- SECTION
 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-08-19 Cont ID  
Sent By tklarge Date 2016-08-19 Time 09:10 Rev Time 0.00
Received By tklarge Date 2016-08-19 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-08-17 Cont ID  
Sent By tklarge Date 2016-08-17 Time 11:45 Rev Time 0.00
Received By tklarge Date 2016-08-17 Time 10:46 Sent To  
Notes
2016-08-17 11:57:041) TOILET PAPER DISPENSERS SHALL BE LOCATED 7-9 INCHES
 FROM THE FRONT OF THE WATER CLOSET TO THE CENTER LINE
 OF THE DISPENSERS. FAC SEC. 604.9.6.
 2) THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED FROM
 FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE, NOT TO
 THE CENTERLINE AS SHOWN ON THE PLANS. FAC SEC. 609.4.
 3) THE SHOWER SEAT SHALL BE LOCATED A MAXIMUM OF 19
 INCHES ABOVE THE FINISH FLOOR, NOT TWENTY INCHES AS
 SHOWN. FAC SEC.610.3.
 5) THE BREAKROOM SINK SHALL BE LOCATED A MAXIMUM OF 34
 INCHES ABOVE FINISH FLOOR.FAC SEC. 606.3.
 6) THE HEIGHT OF THE FEMININE PRODUCT DISPENSER SHALL
 COMPLY WITH FAC SEC. 308. MAXIMUM OF 48 INCHES ABOVE
 FINISH FLOOR.
 7) THE LOCATION OF THE SHOWER CCONTROLS IN THE
 HANDICAPPED ACCESSIBLE SHOWER SHALL COMPLY WITH FAC
 SEC. 608.5.3.
 8) PLEASE CORRECT THE ADA NOTES ON SHT. A4.10 TO COMPLY
 WITH FAC. SEE NOTE #5, 7, &10.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-23 Cont ID  
Sent By gearl Date 2016-06-23 Time   Rev Time 0.00
Received By gearl Date 2016-06-23 Time 14:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By gearl Date 2016-05-05 Time 10:54 Rev Time 0.00
Received By gearl Date 2016-05-05 Time 10:54 Sent To  
Notes
2016-05-05 11:01:25 
  
  
 1. BREAK ROOM SINK SK-2 NEEDS TO RUN THRU GREASE TRAP
  
 2. .ELECTRIC ROOM FLOOR DRAIN NEEDS A TRAP PRIMER
 INASTALLED
  
 3 . TRIPLE SINK NEEDS TO BE VENTED
  
 4. W/M NEED TO SHOW VTR SIZE
  
 5. PLEASE SUBMIT 2 COPIES OF CODE COMPLIANT SANITARY
 RISER DIAGRAMS
  
 6. SHOW VENTING OF FIXTURES ACCORDANCE TO FBC- PLUMBING
 SECTION 901.2.1
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-07 Cont ID  
Sent By ajones Date 2016-07-07 Time 12:05 Rev Time 0.00
Received By ajones Date 2016-07-07 Time 12:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-06 Cont ID  
Sent By ajones Date 2016-05-06 Time 10:47 Rev Time 0.00
Received By ajones Date 2016-05-06 Time 10:47 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved