Plan Review Details - Permit 16041214
Plan Review Stops For Permit 16041214
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-02 Cont ID  
Sent By mvaldes Date 2016-05-02 Time 18:54 Rev Time 0.00
Received By mvaldes Date 2016-05-02 Time 18:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-05-02 Cont ID  
Sent By pleduc Date 2016-05-02 Time   Rev Time 0.00
Received By pleduc Date 2016-05-02 Time 10:20 Sent To E
Notes
2016-05-02 11:17:44THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THE NATURE OF FIRE ALARM WORK MAY REQUIRE A FIRE
 WATCH WHEN APPLICABLE'
  
 PER NFPA 72, CHAPTER 10, CIRCUITS AND PATHWAYS
  
 10.19* IMPAIRMENTS.
  
 10.19.3* WHERE REQUIRED, MITIGATING MEASURES ACCEPTABLE
 TO THE AUTHORITY HAVING JURISDICTION SHALL BE
 IMPLEMENTED FOR THE PERIOD THAT THE SYSTEM IS IMPAIRED.
  
 NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
  
 9.6.1.6* WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF
 SERVICE FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE
 AUTHORITY HAVING JURISDICTION SHALL BE NOTIFIED, AND
 THE BUILDING SHALL BE EVACUATED, OR AN APPROVED FIRE
 WATCH SHALL BE PROVIDED FOR ALL PARTIES LEFT
 UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE ALARM SYSTEM
 HAS BEEN RETURNED TO SERVICE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-02 Cont ID  
Sent By mvaldes Date 2016-05-02 Time 18:54 Rev Time 0.00
Received By mvaldes Date 2016-04-27 Time 13:31 Sent To  
Notes
2016-04-28 13:32:00ROUTED TO FIRE