Plan Review Details - Permit 16041211
Plan Review Stops For Permit 16041211
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-08-25 Cont ID  
Sent By albarran Date 2016-08-25 Time 15:37 Rev Time 0.00
Received By albarran Date 2016-08-25 Time 13:37 Sent To I
Notes
2016-08-25 15:40:04WITH THE EXCEPTION OF THE UL CERTIFICATE FOR THE
 MONITORING STATION, ALL PREVIOUSLY MENTIONED
 DEFICIENCIES HAVE BEEN SATISFACTORILY ADDRESSED.
 CONTRACTOR WAS TOLD TO HAVE THE REQUIRED CERTIFICATE
 READY FOR THE INSPECTOR FOR FINAL INSPECTION AND FOR
 THE LOG BOOK. A COPY OF THE CERTIFICATE MUST BE
 SUBMITTED TO US FOR THE RECORD.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-07-21 Cont ID  
Sent By albarran Date 2016-07-21 Time 09:39 Rev Time 0.00
Received By albarran Date 2016-07-21 Time 10:29 Sent To I
Notes
2016-07-21 09:40:26ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 JOB NAME: 215 5TH STREET
 JOB ADDRESS: 215 5TH STREET
 DESCRIPTION: FACP & COMMUNICATOR REPLACEMENT
 MAST. PERMIT: 16041211
 REVISION/SUB-PERMIT:
  
 1. NFPA 10.5.5.2 CIRCUIT IDENTIFICATION &
 ACCESSIBILITY: THE LOCATION OF THE BRANCH CIRCUIT
 DISCONNECTING MEANS SHALL BE LEGIBLY IDENTIFIED. BE
 PROPERLY MARKED AND SECURED OR BE ACCESSIBLE ONLY TO
 QUALIFIED PERSONS.
 2. FBC-B907.1.2 HAS SPECIFIC REQUIREMENTS FOR THE
 CONTENTS OF THE SUBMITTED SHOP DRAWINGS WHICH HAVE NOT
 BEEN COMPLIED WITH. CORRECT THE DRAWINGS TO INCLUDE THE
 LOCATION OF THE POWER SOURCE, BATTERY CALCULATIONS,
 CONDUCTOR TYPE AND SIZING, VOLTAGE DROP CALCULATIONS,
 MANUFACTURERS SPEC SHEETS FOR ALL APPARATUS AND MOST
 IMPORTANTLY NOTE THE CEILING HEIGHT FOR THE
 RETAIL/DISPLAY AREAS. NOTE THAT W/O THE ACTUAL LAYOUT
 PROPER NOTIFICATION DEVICE PLACEMENT CAN?T BE SECURED.
 THIS WILL BE SUBJECT TO FIELD INSPECTOR?S APPROVAL.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-06-25 Cont ID  
Sent By vperez Date 2016-06-25 Time 08:37 Rev Time 0.00
Received By vperez Date 2016-06-25 Time 08:37 Sent To  
Notes
2016-06-25 08:38:022ND REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE PER FIRE COMMENTS; FOR A COMPLETE
 REVIEW
 2. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By vperez Date 2016-05-06 Time 09:57 Rev Time 0.00
Received By vperez Date 2016-05-06 Time 09:57 Sent To  
Notes
2016-05-06 09:59:29APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE PER FIRE COMMENTS; FOR A COMPLETE
 REVIEW
 2. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-08-24 Cont ID  
Sent By wjolin Date 2016-08-24 Time 12:50 Rev Time 0.00
Received By wjolin Date 2016-08-24 Time 12:50 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-07-20 Cont ID  
Sent By wjolin Date 2016-07-20 Time 12:55 Rev Time 0.00
Received By wjolin Date 2016-07-20 Time 12:49 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-06-23 Cont ID  
Sent By wjolin Date 2016-06-23 Time 11:17 Rev Time 0.00
Received By wjolin Date 2016-06-23 Time 11:03 Sent To E
Notes
2016-06-23 11:17:04215 5TH STREET
 PERMIT #16041211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS INDICATE "NTS." SUBMIT SCALABLE PLANS.
  
 OFFICE AREAS WILL REQUIRE APPROXIMATELY 55DB SOUND
 LEVELS IN ALL SPACES PER NFPA 72. PROVIDING
 NOTIFICATION APPLIANCES IN OPEN SPACES AND CORRIDORS
 ONLY WILL PROVIDE A CHALLENGE IN OBTAINING ADEQUATE
 SOUND LEVELS IN ALL ROOMS WITH DOORS. INSPECTOR WILL
 FIELD VERIFY WITH DB METER.
  
 FIRST FLOOR: INADEQUATE HORN-STROBE COVERAGE FOR NORTH
 FLOOR AREA.
  
 SECOND FLOOR: INADEQUATE APPLIANCE COVERAGE IN NORTH
 WORKROOM. NO APPLIANCE PROVIDED IN BREAKROOM. WHAT IS
 THE SOUTH UNNAMED ROOM ADJACENT TO THE STORAGE ROOM?
  
 THIRD FLOOR: LARGE WORK AREA HAS INADEQUATE COVERAGE IN
 THE SOUTHWEST CORNER. NO APPLIANCE PROVIDED IN THE
 CONFERENCE ROOM.
  
 PENTHOUSE: NO AUDIBLE COVERAGE PROVIDED FOR ALL
 PENTHOUSE SPACES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By J.Walker Date 2016-04-28 Time   Rev Time 0.30
Received By   Date 2016-04-28 Time   Sent To  
Notes
2016-04-28 16:15:11FACP CHANGE OUT REQUIRES THAT BUILDING / SYSTEM DEVICES
 BE BROUGHT UP TO NFPA 72 2010 STANDARDS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-25 Cont ID  
Sent By albarran Date 2016-08-25 Time 15:47 Rev Time 0.00
Received By albarran Date 2016-08-22 Time 12:55 Sent To  
Notes
2016-08-25 15:49:128/25/16 PLANS APPROVED FOR PERMITTING. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL READY BIN "A".
 MA
2016-08-22 12:55:51RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-21 Cont ID  
Sent By albarran Date 2016-07-21 Time 11:30 Rev Time 0.00
Received By albarran Date 2016-07-19 Time 14:32 Sent To  
Notes
2016-07-21 11:31:567/21/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED DRAWER
 "A". MA
2016-07-19 14:33:11RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-25 Cont ID  
Sent By vperez Date 2016-06-25 Time 08:38 Rev Time 0.00
Received By vperez Date 2016-06-25 Time 08:38 Sent To  
Notes
2016-06-22 11:33:49RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-06 Cont ID  
Sent By vperez Date 2016-05-06 Time 09:59 Rev Time 0.00
Received By vperez Date 2016-05-06 Time 09:59 Sent To  
Notes
2016-04-27 15:09:14ROUTED TO FIRE