| Plan Review Stops For Permit 16041211 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2016-08-25 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-08-25 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-08-25 |
Time |
13:37 |
Sent To |
I |
|
| Notes |
| 2016-08-25 15:40:04 | WITH THE EXCEPTION OF THE UL CERTIFICATE FOR THE | | | MONITORING STATION, ALL PREVIOUSLY MENTIONED | | | DEFICIENCIES HAVE BEEN SATISFACTORILY ADDRESSED. | | | CONTRACTOR WAS TOLD TO HAVE THE REQUIRED CERTIFICATE | | | READY FOR THE INSPECTOR FOR FINAL INSPECTION AND FOR | | | THE LOG BOOK. A COPY OF THE CERTIFICATE MUST BE | | | SUBMITTED TO US FOR THE RECORD. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2016-07-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-07-21 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-07-21 |
Time |
10:29 |
Sent To |
I |
|
| Notes |
| 2016-07-21 09:40:26 | ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & | | | NFPA 70 2011 (NEC) | | | | | | JOB NAME: 215 5TH STREET | | | JOB ADDRESS: 215 5TH STREET | | | DESCRIPTION: FACP & COMMUNICATOR REPLACEMENT | | | MAST. PERMIT: 16041211 | | | REVISION/SUB-PERMIT: | | | | | | 1. NFPA 10.5.5.2 CIRCUIT IDENTIFICATION & | | | ACCESSIBILITY: THE LOCATION OF THE BRANCH CIRCUIT | | | DISCONNECTING MEANS SHALL BE LEGIBLY IDENTIFIED. BE | | | PROPERLY MARKED AND SECURED OR BE ACCESSIBLE ONLY TO | | | QUALIFIED PERSONS. | | | 2. FBC-B907.1.2 HAS SPECIFIC REQUIREMENTS FOR THE | | | CONTENTS OF THE SUBMITTED SHOP DRAWINGS WHICH HAVE NOT | | | BEEN COMPLIED WITH. CORRECT THE DRAWINGS TO INCLUDE THE | | | LOCATION OF THE POWER SOURCE, BATTERY CALCULATIONS, | | | CONDUCTOR TYPE AND SIZING, VOLTAGE DROP CALCULATIONS, | | | MANUFACTURERS SPEC SHEETS FOR ALL APPARATUS AND MOST | | | IMPORTANTLY NOTE THE CEILING HEIGHT FOR THE | | | RETAIL/DISPLAY AREAS. NOTE THAT W/O THE ACTUAL LAYOUT | | | PROPER NOTIFICATION DEVICE PLACEMENT CAN?T BE SECURED. | | | THIS WILL BE SUBJECT TO FIELD INSPECTOR?S APPROVAL. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-06-25 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-06-25 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-06-25 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2016-06-25 08:38:02 | 2ND REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE PER FIRE COMMENTS; FOR A COMPLETE | | | REVIEW | | | 2. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE | | | FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-05-06 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-05-06 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-05-06 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2016-05-06 09:59:29 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE PER FIRE COMMENTS; FOR A COMPLETE | | | REVIEW | | | 2. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE | | | FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2016-08-24 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-08-24 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-08-24 |
Time |
12:50 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2016-07-20 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-07-20 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-07-20 |
Time |
12:49 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2016-06-23 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-06-23 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-06-23 |
Time |
11:03 |
Sent To |
E |
|
| Notes |
| 2016-06-23 11:17:04 | 215 5TH STREET | | | PERMIT #16041211 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS INDICATE "NTS." SUBMIT SCALABLE PLANS. | | | | | | OFFICE AREAS WILL REQUIRE APPROXIMATELY 55DB SOUND | | | LEVELS IN ALL SPACES PER NFPA 72. PROVIDING | | | NOTIFICATION APPLIANCES IN OPEN SPACES AND CORRIDORS | | | ONLY WILL PROVIDE A CHALLENGE IN OBTAINING ADEQUATE | | | SOUND LEVELS IN ALL ROOMS WITH DOORS. INSPECTOR WILL | | | FIELD VERIFY WITH DB METER. | | | | | | FIRST FLOOR: INADEQUATE HORN-STROBE COVERAGE FOR NORTH | | | FLOOR AREA. | | | | | | SECOND FLOOR: INADEQUATE APPLIANCE COVERAGE IN NORTH | | | WORKROOM. NO APPLIANCE PROVIDED IN BREAKROOM. WHAT IS | | | THE SOUTH UNNAMED ROOM ADJACENT TO THE STORAGE ROOM? | | | | | | THIRD FLOOR: LARGE WORK AREA HAS INADEQUATE COVERAGE IN | | | THE SOUTHWEST CORNER. NO APPLIANCE PROVIDED IN THE | | | CONFERENCE ROOM. | | | | | | PENTHOUSE: NO AUDIBLE COVERAGE PROVIDED FOR ALL | | | PENTHOUSE SPACES. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-04-28 |
|
|
Cont ID |
|
| Sent By |
J.Walker |
Date |
2016-04-28 |
Time |
|
Rev Time |
0.30 |
| Received By |
|
Date |
2016-04-28 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-04-28 16:15:11 | FACP CHANGE OUT REQUIRES THAT BUILDING / SYSTEM DEVICES | | | BE BROUGHT UP TO NFPA 72 2010 STANDARDS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-08-25 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-08-25 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-08-22 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2016-08-25 15:49:12 | 8/25/16 PLANS APPROVED FOR PERMITTING. CONTRACTOR | | | NOTIFIED VIA EMAIL. FILE SENT TO SMALL READY BIN "A". | | | MA | | 2016-08-22 12:55:51 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-07-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-07-21 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-07-19 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2016-07-21 11:31:56 | 7/21/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | | NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED DRAWER | | | "A". MA | | 2016-07-19 14:33:11 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-06-25 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-06-25 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-06-25 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2016-06-22 11:33:49 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-05-06 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-05-06 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-05-06 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2016-04-27 15:09:14 | ROUTED TO FIRE |
|
|