Plan Review Details - Permit 16041179
Plan Review Stops For Permit 16041179
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-20 Cont ID  
Sent By vperez Date 2016-06-20 Time 11:28 Rev Time 0.00
Received By cthroop Date 2016-06-20 Time 10:29 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-14 Cont ID  
Sent By cpuell Date 2016-06-15 Time 09:43 Rev Time 0.00
Received By cthroop Date 2016-06-14 Time 08:14 Sent To M
Notes
2016-06-14 08:22:06BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 DATE: 6/14/16
 ACTION: FAIL
  
 1. NEW STAIR CONSTRUCTION DETAIL ON PG. A-2 SHOWS 10"
 OPENING AT GUARDS. PLEASE COMPLY WITH FBC R312.1.3.
  
 R312.1.3 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS FROM THE
 WALKING SURFACE TO THE REQUIRED GUARD HEIGHT WHICH
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102 MM) IN
 DIAMETER.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-11 Cont ID  
Sent By cthroop Date 2016-05-11 Time 11:45 Rev Time 0.00
Received By cthroop Date 2016-05-11 Time 10:49 Sent To  
Notes
2016-05-11 11:56:531ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-7918
 [email protected]
  
 1. NEW STAIR CONSTRUCTION DETAIL ON PLAN SHEET A-2
 INDICATES A 10 INCH GAP AT BALASTRADES AND 81/4", 71/2"
 & 51/4" RISER HEIGHTS. STAIR CONSTRUCTION MUST COMPLY
 WITH THE FBC R311.7, SPECIFICALLY SECTIONS 311.7.5.1
 (RISERS) AND R312.1.3 (GUARDS).
 2. PROVIDE FASTENER SCHEDULE FOR DRYWALL PER CHPT. 1,
 SECTION 110.3.A.2.2.
  
 R311.7.5.1 RISERS.
 THE MAXIMUM RISER HEIGHT SHALL BE 73/4 INCHES (196 MM).
 THE RISER SHALL BE MEASURED VERTICALLY BETWEEN LEADING
 EDGES OF THE ADJACENT TREADS. THE GREATEST RISER HEIGHT
 WITHIN ANY FLIGHT OF STAIRS SHALL NOT EXCEED THE
 SMALLEST BY MORE THAN 3/8 INCH (9.5 MM). RISERS SHALL
 BE VERTICAL OR SLOPED FROM THE UNDERSIDE OF THE NOSING
 OF THE TREAD ABOVE AT AN ANGLE NOT MORE THAN 30 DEGREES
 (0.51 RAD) FROM THE VERTICAL. OPEN RISERS ARE PERMITTED
 PROVIDED THAT THE OPENING BETWEEN TREADS DOES NOT
 PERMIT THE PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE
 R312.1.3 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS FROM THE
 WALKING SURFACE TO THE REQUIRED GUARD HEIGHT WHICH
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102 MM) IN
 DIAMETER.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-20 Cont ID  
Sent By vperez Date 2016-06-20 Time 08:53 Rev Time 0.00
Received By vperez Date 2016-06-20 Time 11:28 Sent To B
Notes
2016-06-20 08:53:59INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:PROVISO
 1. PLEASE SHOW REQUIRED SWITCH AND LIGHTING OUTLETS FOR
 NEW STAIRS SHOWN PER FBC RES E3903.3
 2. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERN.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-12 Cont ID  
Sent By vperez Date 2016-05-12 Time 14:26 Rev Time 0.00
Received By vperez Date 2016-05-12 Time 13:49 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-20 Cont ID  
Sent By cpuell Date 2016-06-20 Time 12:58 Rev Time 0.00
Received By cpuell Date 2016-06-17 Time 14:57 Sent To  
Notes
2016-06-17 14:57:23RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-15 Cont ID  
Sent By cpuell Date 2016-06-15 Time 09:43 Rev Time 0.00
Received By cpuell Date 2016-06-08 Time 10:20 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-06 Cont ID  
Sent By hmoser Date 2016-06-06 Time 09:44 Rev Time 0.00
Received By hmoser Date 2016-04-27 Time 13:24 Sent To  
Notes
2016-04-27 13:24:34R06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-06-14 Cont ID  
Sent By jvalido Date 2016-06-14 Time 14:56 Rev Time 0.00
Received By jvalido Date 2016-06-14 Time 14:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By hmoser Date 2016-06-06 Time 09:44 Rev Time 0.00
Received By hmoser Date 2016-06-06 Time 09:23 Sent To  
Notes
2016-06-06 09:44:29PLAN DENIED
 NO AIR CONDITIONING PLAN SUBMITTED.
  
 HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-20 Cont ID  
Sent By gjohnson Date 2016-06-20 Time 12:37 Rev Time 0.00
Received By gjohnson Date 2016-06-20 Time 11:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By gearl Date 2016-05-05 Time 12:45 Rev Time 0.00
Received By gearl Date 2016-05-05 Time 12:45 Sent To  
Notes
***NONE***