Plan Review Details - Permit 16041163
Plan Review Stops For Permit 16041163
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-11 Cont ID  
Sent By cthroop Date 2016-05-11 Time 09:18 Rev Time 0.00
Received By cthroop Date 2016-05-11 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By cthroop Date 2016-05-05 Time 09:37 Rev Time 0.00
Received By cthroop Date 2016-05-05 Time 08:50 Sent To M
Notes
2016-05-05 09:43:541ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-7918
 [email protected]
  
 1. PROVIDE FRAMING DETAIL FOR NEW ENCLOSURE AT EXISTING
 CONCRETE PAD.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-16 Cont ID  
Sent By mvaldes Date 2016-05-16 Time 13:27 Rev Time 0.00
Received By mvaldes Date 2016-05-16 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By mvaldes Date 2016-04-28 Time 17:45 Rev Time 0.00
Received By mvaldes Date 2016-04-28 Time 16:50 Sent To  
Notes
2016-04-28 17:54:59REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 -NEC 2108 B GFCI PROTECTION REQUIRED FOR GARAGE DOOR
 MOTOR RECEPTACLE OUTLET.
 -FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. REFLECT NEW LOADS OF DRYER , WASHER , AND
 A/C MINI SPLIT.
 -NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-17 Cont ID  
Sent By lmarchan Date 2016-05-17 Time 09:57 Rev Time 0.00
Received By lmarchan Date 2016-05-06 Time 11:12 Sent To  
Notes
2016-05-09 11:12:35R13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-06 Cont ID  
Sent By cpuell Date 2016-05-06 Time 09:44 Rev Time 0.00
Received By cpuell Date 2016-04-26 Time 08:24 Sent To  
Notes
2016-04-27 08:24:42R13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-16 Cont ID  
Sent By mvaldes Date 2016-05-16 Time 13:39 Rev Time 0.00
Received By jvalido Date 2016-05-16 Time 13:38 Sent To  
Notes
2016-05-16 13:28:50ACCIDENTLY CHECKED IN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By jvalido Date 2016-05-06 Time 08:27 Rev Time 0.00
Received By jvalido Date 2016-05-05 Time 16:36 Sent To  
Notes
2016-05-06 08:27:02FLORIDA BUILDING CODE 5TH EDITION (2014) ENERGY
 CONSERVATION
  
 R101.4.5 CHANGE IN SPACE CONDITIONING.
 ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THIS CODE.
  
 PROVIDE ENERGY CALCULATIONS FOR THE GARAGE.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-11 Cont ID  
Sent By gjohnson Date 2016-05-11 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2016-05-11 Time 16:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By gearl Date 2016-05-04 Time 16:44 Rev Time 0.00
Received By gearl Date 2016-05-04 Time 16:44 Sent To  
Notes
2016-05-04 16:47:57 
  
  
 1. NEED TO INSTALL NEW W/M TRAP AND STAND PIPE FBC 2014
 PLUMBING SECTION 406.1 AND 406.2
  
  
 GEORGE EARL PLUMBING PLANS REVIEWER 0013 B