Plan Review Details - Permit 16041150
Plan Review Stops For Permit 16041150
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-10-12 Cont ID  
Sent By jwitmer Date 2016-10-12 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2016-10-12 Time 11:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-04 Cont ID  
Sent By jwitmer Date 2016-08-04 Time 17:26 Rev Time 0.00
Received By jwitmer Date 2016-08-04 Time 16:01 Sent To  
Notes
2016-08-04 16:42:21 
 BUILDING PROVISO:
 NOTE THIS POOL DECK AND POOL ARE COVERED UNDER THE FAIR
 HOUSING ACT, TO DATE THE GUIDELINES ONLY REQUIRES
 ACCESS MUST BE PROVIDED TO THE POOL DECK AREA, NOT AN
 ACCESSIBLE ROUTE (RAMP OR LIFT) DOWN INTO THE WATER
 INTO THE POOL. ON THE OTHER HAND IF THE ASSOCIATION
 ELECTS TO ALLOW THE COMMUNITY ROOM, POOL, AND OR POOL
 DECK TO BE RENTED OUT FOR PARTIES THAT THE PUBLIC COULD
 USE, THEN THIS AREA WOULD BE REQUIRED TO MEET FLORIDA
 ACCESSIBILITY SECTION 1009 OF THE ACCESSIBILITY CODE
 POOL LIFTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-08 Cont ID  
Sent By jwitmer Date 2016-06-08 Time   Rev Time  
Received By jwitmer Date 2016-06-08 Time   Sent To E
Notes
2016-06-08 14:42:48BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041150
 ADD: 333 FERN ST/ POOL 7TH FLOOR LEVEL
 CONT: A & G CONCRETE POOLS
 TEL: 772-878-7752
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 08/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IT IS UNDERSTOOD THE PRIME BUILDING
 PERMIT: 15031312 IS FOR A R-2 APARTMENT COMPLEX/ FAIR
 HOUSING DOES NOT REQUIRE AN ACCESSIBLE ENTRANCE INTO
 THE SWIMMING POOL.
  
 1) THE SHEET 4 POOL EQUIPMENT ROOM LAYOUT SHOWS A
 HEATER BUT THERE ARE NO MANUFACTURERS SPEC ON THE
 HEATER. RESPONSE COMMENTS FROM ACE AQUATIC CONSULTING
 COMMENT # 11 INDICATES THERE ARE MANUFACTURERS SPEC
 SHEET ATTACHED TO THIS LETTER. NOT FOUND. THERE ARE
 MANUFACTURER'S SPEC ON THE MAIN DRAIN GRATES. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED. SHOW COMPLIANCE WITH
 2014 FBC-ENERGY CODE
  
 2) SHEET 4 SHOWING A HEATER WILL NEED TO SHOW
 COMPLIANCE WITH: 2014 FBC-ENERGY CODE C404.7.1 POOL
 HEATERS.
 ALL POOL HEATERS SHALL MEET THE MINIMUM EFFICIENCY
 LISTED FOR THAT TYPE OF POOL HEATER IN TABLE C404.2 AND
 BE EQUIPPED WITH A READILY ACCESSIBLE ON-OFF SWITCH
 THAT IS MOUNTED OUTSIDE OF THE HEATER TO ALLOW SHUTTING
 OFF THE HEATER WITHOUT ADJUSTING THE THERMOSTAT
 SETTING. GAS-FIRED HEATERS SHALL NOT BE EQUIPPED WITH
 CONSTANT BURNING PILOT LIGHTS.
  
 3) WITH THE SWIMMING POOL HAVING A HEATER PLEASE SHOW
 COMPLIANCE WITH ENERGY CODE SECTION C404.7.3 COVERS.
 HEATED SWIMMING POOLS AND INGROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-21 Cont ID  
Sent By jwitmer Date 2016-10-12 Time 12:16 Rev Time 0.00
Received By mvaldes Date 2016-09-21 Time 14:17 Sent To P
Notes
2016-09-21 15:26:53ROUTED TO TKL PLUMBING

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-27 Cont ID  
Sent By mvaldes Date 2016-07-27 Time 10:20 Rev Time 0.00
Received By mvaldes Date 2016-07-27 Time 09:05 Sent To  
Notes
2016-07-27 10:34:10REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
  
 1) OUTLETS SUPPLYING POOL PUMP MOTORS CONNECTED TO
 SINGLE-PHASE, 120 VOLT THROUGH 240 VOLT BRANCH
 CIRCUITS, RATED 15 OR 20 AMPERES, WHETHER BY RECEPTACLE
 OR BY DIRECT CONNECTION, SHALL BE PROVIDED WITH
 GROUND-FAULT CIRCUITINTERRUPTER PROTECTION FOR
 PERSONNEL.
 - SHOW GFCI PROTECTION ON THE ELECTRICAL DIAGRAM.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-20 Cont ID  
Sent By mvaldes Date 2016-06-20 Time 08:51 Rev Time 0.00
Received By mvaldes Date 2016-06-20 Time 08:51 Sent To  
Notes
2016-06-20 08:56:06REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PROVIDE SPECS ON POOL EQUIPMENT POOL HEATERS AND POOL
 PUMPS. FBC 107 INSUFFICIENT DOCUMENTS.
  
 - SPECIFY WHETHER LIGHT NICHE REQUIRES # 8 AWG BONDING
 CONDUCTOR OR NOT ? NEC 680.22(B)(2)/680.24, IF NOT HOW
 WILL POOL WATER BE BONDED ? NEC 680.26(C)
  
 - GENERAL COMMENT GFC PROTECTION REQUIRED FOR POOL
 PUMPS , LIGHTS , RECEPTACLES. NEC 680.21, 680.22.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-05-20 Cont ID  
Sent By tklarge Date 2016-05-20 Time 06:37 Rev Time 0.00
Received By tklarge Date 2016-05-20 Time 06:33 Sent To  
Notes
2016-05-20 06:36:57GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-12 Cont ID  
Sent By jwitmer Date 2016-10-12 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2016-09-19 Time 15:34 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-04 Cont ID  
Sent By jwitmer Date 2016-08-04 Time 17:30 Rev Time 0.00
Received By jwitmer Date 2016-07-25 Time 10:28 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-20 Cont ID  
Sent By mvaldes Date 2016-06-20 Time 09:37 Rev Time 0.00
Received By mvaldes Date 2016-04-26 Time 15:21 Sent To  
Notes
2016-05-18 09:43:55ROUTED TO ELECTRIC.
2016-04-26 15:21:59ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-09-24 Cont ID  
Sent By tklarge Date 2016-09-24 Time 04:30 Rev Time 0.00
Received By tklarge Date 2016-09-24 Time 03:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-07-26 Cont ID  
Sent By jwitmer Date 2016-08-04 Time 17:20 Rev Time 0.00
Received By tklarge Date 2016-07-26 Time 06:13 Sent To  
Notes
2016-07-26 11:19:51SUBMIT MSDS ( MATERIAL SAFETY DATA SHEETS ) SHEETS FOR
 THE POOL CHEMICALS THAT WILL BE USED IN TREATING THE
 POOL WATER.WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-20 Cont ID  
Sent By tklarge Date 2016-05-20 Time 06:33 Rev Time 0.00
Received By tklarge Date 2016-05-19 Time 06:21 Sent To  
Notes
2016-05-20 06:33:251) THE PLANS SHOW THE POOL WATER WASTE DISCHARGE TO THE
 SANITARY SEWER.POOL WATER CANNOT DISCHARGE TO THE
 SANITARY OR STORM SYSTEM PER WPB CITY ORD. SECS. 90-126
 (5), 90-203 (A), 90-204, AND 90-205 (1). THE RESPONSE
 FROM THE ENGINEER OF RECORD STATES THAT THIS ISSUE HAS
 BEEN RESOLVED AND THE WASTE WATER WILL GO TO THE
 SANITARY. I DO NOT HAVE ANY DOCUMENTATION THAT THIS
 WILL BE ALLOWED.
 2) THE HYDRAULIC CALCULATIONS THAT WERE DONE ON SHT. 4
 TO REDUCE THE CAPACITY OF THE COLLECTOR TANKS WERE
 BASED ON A FLOW RATE OF 185 GPM BUT THE FLOW RATE ON
 SHT.1 IN THE POOL DATA TABLE SHOWS A FLOW RATE OF 155
 GPM. CLARIFY.
 3) THERE WAS NO MSDS DOCUMENTATION ATTACHED TO THE
 RESPONSE LETTER FROM THE ENGINEER AS NOTED IN HIS
 RESPONSE TO COMMENT # 8. CLARIFY.
 4) THERE WERE NO SPECIFICATIONS SUBMITTED FOR THE POOL
 HEATER. THIS INFORMATION CAN BE SUBMITTED WHEN THE GAS
 PERMIT IS SUBMITTED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-18 Cont ID  
Sent By aaponte Date 2016-05-18 Time 09:43 Rev Time 0.00
Received By aaponte Date 2016-05-18 Time 09:42 Sent To  
Notes
2016-05-18 09:43:25PROVISO: ROW ENCROACHMENT SHALL BE APPROVED BEFORE
 FINAL CO.