Plan Review Details - Permit 16041132
Plan Review Stops For Permit 16041132
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-27 Cont ID  
Sent By lmarchan Date 2016-05-27 Time 10:12 Rev Time 0.00
Received By lmarchan Date 2016-05-26 Time 14:18 Sent To  
Notes
2016-05-26 14:18:37RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-26 Cont ID  
Sent By lmarchan Date 2016-04-27 Time 14:17 Rev Time 0.00
Received By lmarchan Date 2016-04-26 Time 13:16 Sent To  
Notes
2016-04-26 13:16:43MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jvalido Date 2016-06-16 Time 16:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-05-26 Cont ID  
Sent By jvalido Date 2016-05-26 Time 17:59 Rev Time 0.00
Received By jvalido Date 2016-05-26 Time 17:48 Sent To  
Notes
2016-05-26 17:59:49CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1
 (1) PROVIDE OWNER/AGENT SIGNATURE AND DATE ON ALL
 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION FORM.
  
 PROVIDE AHRI WHICH MEETS THE DESIGN ENERGY
 REQUIREMENTS.
  
 A/C CHANGE OUT COMPLIANCE FORM SHOWS 13 SEER.
  
 109.3 BUILDING PERMIT VALUATIONS
 VALUE ON PERMIT APPLICATION IS TO LOW. RECALCULATE JOB
 OR PROVIDE COPY OF PROPOSAL. ADD MIMI SPLIT SYSTEMS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-27 Cont ID  
Sent By jvalido Date 2016-04-27 Time 17:14 Rev Time 0.00
Received By jvalido Date 2016-04-27 Time 16:06 Sent To  
Notes
2016-04-27 17:14:19WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1
 (1) PROVIDE OWNER/AGENT SIGNATURE AND DATE ON ALL
 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION FORM.
 (2) PROVIDE ACCURATE WORK DESCRIPTION OF WORK TO BE
 DONE ON PERMIT APPLICATION. EXAMPLE INSTALLATION OF TWO
 A/C SYSTEMS WITH DUCTWORK. INSTALLATION OF TWO
 MINI-SPLIT SYSTEMS.
 (3) PROVIDE FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION FORM FOR UNIT 414.
 (4) ARE THE MINI-SPLIT SYSTEMS NEW?
 (5) PROVIDE LOCATION OF CONDENSERS FOR MINI-SPLIT.
 (6) MODEL NUMBERS ON THE EQUIPMENT SCHEDULE ARE BOTH
 CONDENSING UNITS. PROVIDE AHU WHICH MATCHES AS PER AHRI
 ON EQUIPMENT SCHEDULE.
  
 109.3 BUILDING PERMIT VALUATIONS
 VALUE ON PERMIT APPLICATION IS TO LOW. RECALCULATE JOB
 OR PROVIDE COPY OF PROPOSAL.
  