Plan Review Details - Permit 16041117
Plan Review Stops For Permit 16041117
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2017-02-07 Cont ID  
Sent By jwitmer Date 2017-02-07 Time 09:53 Rev Time 0.00
Received By jwitmer Date 2017-02-07 Time 09:35 Sent To  
Notes
2017-02-07 09:40:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041117
 ADD: 6611 S. DIXIE HWY.
 CONT: T. B. D./ TO BE DETERMINED
 TEL: 856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 6TH REVIEW
 DATE: TUES. FEB. 07/ 2017
 ACTION: BUILDING PROVISO
  
 1) SHEET 2 OF 3 INDICATES A NEW ROOF TOP A/C UNIT,
 PLEASE PROVIDE PRODUCT INFORMATION FOR THE NEW ROOF TOP
 UNIT AND THE CONNECTION (ATTACHMENT) OF THE ROOF TOP
 UNIT TO CURB.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2017-01-04 Cont ID  
Sent By jwitmer Date 2017-01-04 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2017-01-04 Time 06:32 Sent To  
Notes
2017-01-04 07:02:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041117
 ADD: 6611 S. DIXIE HWY.
 CONT: T. B. D./ TO BE DETERMINED
 TEL: 856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: WED. JAN. 04/2017
 ACTION: DENIED
  
 1) THE COVERSHEET UNDER THE HEADING SCOPE OF WORK
 STATEMENT # 8 AIR CONDITIONING EXISTING NO CHANGES.
 THERE IS A DISCREPANCY IN PLANS, SHEET 2 OF 3 THE ROOF
 PLAN INDICATES TO INSTALL A SECOND 5 TON ROOF TOP UNIT,
 MAINTAIN 36 INCHES APART. 2014 FLORIDA BUILDING CODE W
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED, A DISCREPANCY IN PLANS.
  
 2) SHEET 2 OF 3 INDICATING A NEW 5 TON ROOF TOP UNIT,
 PLEASE PROVIDE THE TYPE OF ROOF SHEATHING/ DECK
 MATERIAL TO BE PENETRATED, PLEASE PROVIDE THE TYPE OF
 ROOF FRAMING, IF HEADERS ARE REQUIRED, IF A SECONDARY
 ROOF JOIST IS REQUIRED( DOUBLER) AND OR IF BAR JOIST
 SYSTEM AND TYPE & SIZE OF ANGLE IRON TO BE USED FOR
 FRAMING, IF JOIST STIFFNER IS REQUIRED?
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) SHEET 2 OF 3 INDICATES A NEW ROOF TOP A/C UNIT,
 PLEASE PROVIDE PRODUCT INFORMATION FOR THE NEW ROOF TOP
 CURB, ANCHORAGE OF CURB TO ROOF DECK, AND THE
 CONNECTION OF THE
 ROOF TOP UNIT TO CURB. FOR ALL ROOF TOP EQUIPMENT,
 CURBS OR A/C STANDS, DETAILED ATTACHMENT TO THE ROOF
 FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF STAND
 TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 4) SHEET 2 OF 3 INDICATES A NEW ROOF TOP A/C UNIT, THE
 PLANS DO NOT INDICATE THE ELEVATION OF THE ROOF ABOVE
 GRADE NOR IF THERE IS A PARAPET REQUIREDTO TRANSVERSE
 BEFORE GAINING ACCESS TO THE ROOF TOP UNIT. 2014 FBC-B
 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT
 A HEIGHT EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL
 BE PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS,
 THE EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL
 TO THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) HIGH OR
 WALKING ON ROOFS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-12-06 Cont ID  
Sent By jwitmer Date 2016-12-06 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2016-12-06 Time 13:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-09 Cont ID  
Sent By ccole Date 2016-11-09 Time 16:16 Rev Time 0.00
Received By jwitmer Date 2016-11-09 Time 15:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-04 Cont ID  
Sent By jwitmer Date 2016-08-04 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2016-08-04 Time 06:30 Sent To Z
Notes
2016-08-04 06:56:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041117
 ADD: 6611 S. DIXIE HWY.
 CONT: T. B. D./ TO BE DETERMINED
 TEL: 856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. AUGUST 04/ 2016
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) COMPLIED.
 1B) 2ND REQUEST. THE DESIGNER OF RECORD HAS INDICATED
 THIS IS A LEVEL 1 ALTERATION. PLEASE REVIEW 2014
 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 1ST ROUND COMMENT. THE DESIGNER OF RECORD HAS NOT
 INDICATED COMPLIANCE WITH 2014 FBC-EXISTING BUILDING
 CODE 301.1 GENERAL. THE REPAIR, ALTERATION, CHANGE OF
 OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED
 IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE
 APPLICANT. APPLICATION OF A METHOD SHALL BE THE SOLE
 BASIS FOR ASSESSING THE COMPLIANCE OF WORK PERFORMED
 UNDER A SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE
 CODE OFFICIAL. SECTIONS 301.1.1 THROUGH 301.1.3 SHALL
 NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
  
 2) 2ND REQUEST. SHEET 2 OF 3 SHOWS NEW WALLS WITHIN THE
 ACCESSIBLE REST ROOM. 2014 EXISTING BUILDING CODE LEVEL
 II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 2014 FBC-ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 3) 2ND REQUEST. SHEET 2 OF 3 SHOWS THE BACK AND SIDE
 GRAB BARS SHOW 33-36 INCHES CENTER LINE OF THE GRAB
 BAR. PLEASE SHOW COMPLIANCE WITH
 ACCESS. CODE 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 (840 MM) MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE,
  
 4)2ND REQUEST. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART,? DO NOT RECITE CODE SECTIONS!!!
 SHEET 2 OF 3 ON THE FLOOR PLAN INDICATES A NEW PASS
 THROUGH WINDOW BUT NO ELEVATIONS. PLEASE PROVIDE
 COMPLIANCE WITH: 2014 FBC-ACCESS. CODE :
 904.5 FOOD SERVICE LINES. COUNTERS IN FOOD SERVICE
 LINES SHALL COMPLY WITH 904.5. 904.5.1 SELF-SERVICE
 SHELVES AND DISPENSING DEVICES. SELF-SERVICE SHELVES
 AND DISPENSING DEVICES FOR TABLEWARE, DISHWARE,
 CONDIMENTS, FOOD AND BEVERAGES SHALL COMPLY WITH 308.
  
 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) 2ND REQUEST. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART,? DO NOT RECITE CODE SECTIONS!!!
 SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014
 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) 2ND REQUEST. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART,? DO NOT RECITE CODE SECTIONS!!!
 SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014
 FBC-ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES. PLEASE NOTE IF THE
 DINING COUNTER AT THE FRONT WINDOW IS A HIGH-TOP OR
 NOT. IF HIGH TOP ACCESSIBLE SEATING MUST BE THERE AS
 WELL.
  
 7) NOTATION ONLY!!! ADDITIONAL PERMITS ARE REQUIRED,
 FOR GAS APPLIANCES, AND THE HOOD, ANSEL SYSTEMS AND
 EXHAUST SYSTEMS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By jwitmer Date 2016-05-05 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2016-05-05 Time 07:28 Sent To  
Notes
2016-05-05 07:57:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041117
 ADD: 6611 S. DIXIE HWY.
 CONT: T. B. D./ TO BE DETERMINED
 TEL: 856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 05/ 2016
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) THE DESIGNER OF RECORD HAS NOT INDICATED TO WHAT
 CODE THESE PLANS WERE DESIGNED? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1B) THE DESIGNER OF RECORD HAS NOT INDICATED COMPLIANCE
 WITH 2014 FBC-EXISITNG BUILDING CODE 301.1 GENERAL. THE
 REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR
 RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH
 ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE APPLICANT. APPLICATION OF A
 METHOD SHALL BE THE SOLE BASIS FOR ASSESSING THE
 COMPLIANCE OF WORK PERFORMED UNDER A SINGLE PERMIT
 UNLESS OTHERWISE APPROVED BY THE CODE OFFICIAL.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER.
  
 2) SHEET 2 OF 3 SHOWS NEW WALLS WITHIN THE ACCESSIBLE
 REST ROOM. 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 2014 FBC-ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 3) SHEET 2 OF 3 SHOWS THE BACK AND SIDE GRAB BARS SHOW
 33-36 INCHES CENTER LINE OF THE GRAB BAR. PLEASE SHOW
 COMPLIANCE WITH
 ACCESS. CODE 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 (840 MM) MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE,
  
 4) SHEET 2 OF 3 ON THE FLOOR PLAN INDICATES A NEW PASS
 THROUGH WINDOW BUT NO ELEVATIONS. PLEASE PROVIDE
 COMPLIANCE WITH: 2014 FBC-ACCESS. CODE :
 904.5 FOOD SERVICE LINES.
 COUNTERS IN FOOD SERVICE LINES SHALL COMPLY WITH 904.5.
  
 904.5.1 SELF-SERVICE SHELVES AND DISPENSING DEVICES.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL COMPLY WITH 308.
  
 904.5.2 TRAY SLIDES.
 THE TOPS OF TRAY SLIDES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 5) SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014
 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014
 FBC-ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES. PLEASE NOTE IF THE
 DINING COUNTER AT THE FRONT WINDOW IS A HIGH-TOP OR
 NOT. IF HIGH TOP ACCESSIBLE SEATING MUST BE THERE AS
 WELL.
  
 7) NOTATION ONLY!!! ADDITIONAL PERMITS ARE REQUIRED,
 FOR GAS APPLIANCES, AND THE HOOD AND EXHAUST SYSTEMS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2017-02-08 Cont ID  
Sent By vperez Date 2017-02-08 Time 11:07 Rev Time 0.00
Received By vperez Date 2017-02-08 Time 11:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2017-01-18 Cont ID  
Sent By mvaldes Date 2017-01-18 Time 13:47 Rev Time 0.00
Received By mvaldes Date 2017-01-18 Time 11:56 Sent To  
Notes
2017-01-18 13:47:51REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] COMPLY WITH OTHER TRADES.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-12-12 Cont ID  
Sent By mvaldes Date 2016-12-12 Time 12:13 Rev Time 0.00
Received By mvaldes Date 2016-12-12 Time 10:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-31 Cont ID  
Sent By mvaldes Date 2016-10-31 Time 09:31 Rev Time 0.00
Received By mvaldes Date 2016-10-31 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-21 Cont ID  
Sent By mvaldes Date 2016-07-21 Time 12:38 Rev Time 0.00
Received By mvaldes Date 2016-07-21 Time 12:00 Sent To  
Notes
2016-07-21 12:50:50JOB PERMIT NUMBER: 16041117
 JOB ADDRESS: 6611 SOUTH DIXIE HIGHWAY
 WEST PALM BEACH FLORIDA "LOS ALTOS DE JALISCO" (
 EXISTING RESTAURANT )
 DATE: JULY 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - QUAD RECEPTACLES IN SMOOTHIE JUICE BAR PREP AREA
 SHALL HAVE GFCI PROTECTION NEC 210.8(B)
 - EMERGENCY LIGHTING WAS SHOWN IN THE KITCHEN, HOWEVER
 PLEASE CORRECT THE NOTE TO STATE THAT EXIT / EMERGENCY
 LIGHTS SHALL BE CONNECTED TO THE LOCAL LIGHTING AHEAD
 SERVED BY AREA. NEC 700.12(F)(4)
 - OCCUPANCY SENSOR IN BATH WAS NOT ADDED AS REQUESTED
 PLEASE COMPLY WITH FBC E SECTION C405.2.2.2. IN
 ADDITION ALL DEVICES IN THE ADA BATHROOM SHALL BE IN
 COMPLIANCE WITH OBSTRUCTED & UNOBSTRUCTED FORWARD REACH
 REQUIREMENTS 48?? HIGH SIDE AND 15?? LOW SIDE ABOVE THE
 FINISH FLOOR. FBC A SECTION 308 ( VERIFY DEPTH IF
 APPLICABLE )
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-02 Cont ID  
Sent By mvaldes Date 2016-05-02 Time 11:03 Rev Time 0.00
Received By mvaldes Date 2016-05-02 Time 10:16 Sent To  
Notes
2016-05-02 11:06:07JOB PERMIT NUMBER: 16041117
 JOB ADDRESS: 6611 S DIXIE HIGHWAY
 WEST PALM BEACH FLORIDA
 DATE: MAY 2 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - MEP SHEET , ALL 125-VOLT, SINGLEPHASE,15- AND
 20-AMPERE RECEPTACLES IN COMMERCIAL KITCHEN REQUIRE NEC
 210.8 GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION(B)
 OTHER THAN DWELLING UNITS.
 - FBC-B 1006.2. EMERGENCY LIGHTING IS REQUIRED , INSIDE
 THE KITCHEN PREP AREA AND DINING ROOM AREA, EMERGENCY
 LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF SAME LOCAL
 AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY THE AREA,
 EM LIGHTS MAY BE ON OWN CIRCUIT NEC 700.12 (F) (4).
 - C405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS SHALL
 BE INSTALLED IN ALL CLASSROOMS, CONFERENCE/MEETING
 ROOMS, EMPLOYEE LUNCH AND BREAK ROOMS, PRIVATE OFFICES,
 RESTROOMS, STORAGE ROOMS AND JANITORIAL CLOSETS, AND
 OTHER SPACES 300 SQUARE FEET (28 M2) OR LESS ENCLOSED
 BY FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC
 CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY
 TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS
 LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR
 SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING
 ON TO NOT MORE THAN 50 PERCENT POWER.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2017-02-03 Cont ID  
Sent By pleduc Date 2017-02-03 Time   Rev Time 0.00
Received By pleduc Date 2017-02-02 Time 15:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2016-12-28 Cont ID  
Sent By pleduc Date 2016-12-27 Time   Rev Time 0.00
Received By pleduc Date 2016-12-27 Time 15:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-12-02 Cont ID  
Sent By pleduc Date 2016-12-02 Time   Rev Time 0.00
Received By pleduc Date 2016-12-02 Time 09:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-10-27 Cont ID  
Sent By pleduc Date 2016-10-27 Time   Rev Time 0.00
Received By pleduc Date 2016-10-27 Time 11:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By pleduc Date 2016-07-18 Time   Rev Time 0.00
Received By pleduc Date 2016-07-18 Time 13:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-27 Cont ID  
Sent By pleduc Date 2016-04-27 Time   Rev Time 0.00
Received By pleduc Date 2016-04-27 Time 14:17 Sent To  
Notes
2016-04-27 14:41:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET 1 OF 3 - THERE IS NO REFERENCE OF COMPLIANCE
 WITH THE CURRENT FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2011
 EDITION.
  
 2) SHEET 1 OF 3 - COMMENT # 10 INDICATES A REFERENCE TO
 NEW GAS SERVICE. ALL GAS SERVICE WORK SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS.
  
 3) SHEET 1 OF 3 - NO OCCUPANCY CLASSIFICATION, OCCUPANY
 LOAD, OR LIFE SAFETY PLAN IS PROVIDED. PLEASE PROVIDE
 IN COMPLAINCE WITH THE ABOVE REFERENCED FIRE CODES.
  
 4) SHEET 3 OF 3 - THERE IS A NOTE INDICATING THE
 DIMENSION OF A HOOD. COMMERCIAL COOKING EQUIPMENT SHALL
 COMPLY WITH NFPA 96, 2011 EDITION. THE HOOD SHALL
 EXTEND TO OVER ALL COOKING EQUIPMENT INCLUDING THE DEEP
 FRYER AND GAS GRILL. THE HOOD SYSTEM WORK SHALL BE
 SUBMITTED AND COMPLETED UNDER SEPARATE SHOP DRAWING.
  
 5) SHEET 3 OF 3 - THERE IS NO INDICATION OF A HOOD
 SUPPRESSION SYSTEM. HOOD FIRE PROTECTION SHALL BE
 PROVIDED FOR IN COMPLIANCE WITH NFPA 96 AND APPLICABLE
 CODES UNDER SEPARATE SHOP DRAWINGS.
  
 6) SHEET 3 OF 3 - THERE IS NO INDICATION OF ANY FIRE
 EXTINGUISHERS, INCLUDING ONE CLASS K FOR THE DEEP FAT
 FYER. PLEASE PROVIDE PER NFPA 10.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2017-01-30 Cont ID  
Sent By gjohnson Date 2017-01-30 Time 09:45 Rev Time 0.00
Received By gjohnson Date 2017-01-30 Time 09:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2017-01-13 Cont ID  
Sent By gjohnson Date 2017-01-13 Time 13:28 Rev Time 0.00
Received By gjohnson Date 2017-01-13 Time 13:28 Sent To  
Notes
2017-01-13 13:58:193RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS
  
 PARTIALLY COMPLIED 1. PLEASE SHOW REQUIRED PRESSURE
 REGULATORS AND THE ANSUL SYSTEM EMERGENCY SHUT OFF
 VALVE. PER WPB AMEND TO FBC 107.2.1
  
  
 NOT COMPLIED PLEASE PROVIDE 6. THE MANUFACTURE SPEC
 SHEETS SHALL LIST THE SPECIFIC STANDARD THEY MEET SUCH
 AS NFPA 54, NFPA 58 ALSO FBC FUEL GAS 623.1 COOKING
 APPLIANCES.
 COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
  
  
 NEW COMMENT:
  
 1.THE COMBUSTION AIR CALCULATION INDICATES A SHORTAGE
 OF 9937 CU. FT. OF INDOOR SPACE. PLEASE CLARIFY HOW THE
 SHORTAGE WILL BE COMPENSATED FOR. IF THE AIR IS TO BE
 SUPPLIED MECHANICALLY REFER TO SECTION 304.9 FUEL GAS
 AND PROVIDE A CALCULATION..
  
 2. INDICATE ON THE PLAN THE SYSTEM PRESSURE. PER FBC
 GAS 402.2
  
 3. PROVIDE THE TABLES USED TO SIZE THE SYSTEM. WPB
 AMEND TO FBC 107.2.1
  
 IN ORDER TO TO GET THIS PLAN APPROVED I SUGGEST THAT WE
 MEET TO GO OVER MY COMMENTS ON THE PLAN PLEASE CONTACT
 ME TO SET A DATE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2016-12-15 Cont ID  
Sent By gjohnson Date 2016-12-15 Time 10:39 Rev Time 0.00
Received By gjohnson Date 2016-12-15 Time 10:39 Sent To  
Notes
2016-12-15 10:39:493RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS
  
 PARTIALLY COMPLIED 1. PLEASE SHOW REQUIRED SHUT OFF
 VALVES DRIP LEGS AND PRESSURE REGULATORS AND THE ANSUL
 SYSTEM EMERGENCY SHUT OFF VALVE. PER WPB AMEND TO FBC
 107.2.1
 SHOW PRESSURE REGULATORS PLAN IS INDICATING 2PSI SYSTEM
 BUT IT IS SIZED TO A .5PSI SYSTEM PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 NOT COMPLIED PLEASE PROVIDE 6. THE MANUFACTURE SPEC
 SHEETS SHALL LIST THE SPECIFIC STANDARD THEY MEET SUCH
 AS NFPA 54, NFPA 58 ALSO FBC FUEL GAS 623.1 COOKING
 APPLIANCES.
 COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
 NEW COMMENT:
  
 1. THE COMBUSTION AIR CALCULATIONS ARE NOT ACCURATE THE
 TOTAL BTU LISTED IN CALCULATION IS 156,000 THE TOTAL
 BTU LISTED ON GAS RISER IS 437,140 . BY MY CALCULATIONS
 21'857 CU FT OF AIR IS REQUIRED. PLEASE CLARIFY PER
 FBC-2014 FUEL GAS CODE SEC. 304.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-11-08 Cont ID  
Sent By gjohnson Date 2016-11-08 Time 09:35 Rev Time 0.00
Received By gjohnson Date 2016-11-08 Time 09:35 Sent To  
Notes
2016-11-08 09:55:322ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW REQUIRED SHUT OFF VALVES DRIP LEGS AND
 PRESSURE REGULATORS AND THE ANSUL SYSTEM EMERGENCY SHUT
 OFF VALVE. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE INDICATE THE MODELS ON MANUFACTURE SPEC
 SHEET. PER WPB AMEND TO FBC 107.2.1
  
 3. THE BTU LOADS ON THE RISER DO NOT MATCH BTU LOAD ON
 MANUFACTURE SPECS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. MANUFACTURE SPECS SHOW 3/4 GAS SUPPLY'S THE RISER
 SHOWS 1/2 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5., THE VERTICAL BROILER YOU PROVIDED MANUFACTURE SPECS
 FOR IS NOT SHOWN ON THE FLOOR PLAN OR RISER DIAGRAM
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 6. THE MANUFACTURE SPEC SHEETS SHALL LIST THE SPECIFIC
 STANDARD THEY MEET SUCH AS NFPA 54, NFPA 58 ALSO FBC
 FUEL GAS 623.1 COOKING APPLIANCES.
 COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-07-31 Cont ID  
Sent By tklarge Date 2016-07-31 Time 10:11 Rev Time 0.00
Received By tklarge Date 2016-07-31 Time 09:45 Sent To  
Notes
2016-07-31 09:51:23GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. IS THE TACOS BROILER GAS OR ELECTRIC? IF IT IS GAS,
 ADD IT ONTO THE GAS RISER.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS (IF ANY) PER 2014 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 THE GAS SHALL BE A SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2017-02-08 Cont ID  
Sent By vperez Date 2017-02-08 Time 11:07 Rev Time 0.00
Received By vperez Date 2017-02-08 Time 11:07 Sent To  
Notes
2017-01-27 10:07:21B27

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-01-18 Cont ID  
Sent By mvaldes Date 2017-01-18 Time 13:49 Rev Time 0.00
Received By mvaldes Date 2016-12-22 Time 16:08 Sent To  
Notes
2016-12-22 16:08:26B20

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-12-15 Cont ID  
Sent By cpuell Date 2016-12-15 Time 13:27 Rev Time 0.00
Received By cpuell Date 2016-11-29 Time 09:59 Sent To  
Notes
2016-11-30 10:02:32B20

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-11-09 Cont ID  
Sent By jwitmer Date 2016-11-09 Time 16:16 Rev Time 0.00
Received By jwitmer Date 2016-10-25 Time 13:00 Sent To  
Notes
2016-10-25 13:00:36B09

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-22 Cont ID  
Sent By cpuell Date 2016-08-22 Time 16:15 Rev Time 0.00
Received By cpuell Date 2016-07-12 Time 13:27 Sent To  
Notes
2016-07-13 13:27:31B09

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-17 Cont ID  
Sent By vperez Date 2016-06-17 Time 13:05 Rev Time 0.00
Received By vperez Date 2016-06-17 Time 13:05 Sent To  
Notes
2016-06-17 13:06:21THESE PLANS WERE PUT BACK IN SHELF BY ZONING. VP ROUTED
 TO CAROLINE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-05 Cont ID  
Sent By ccole Date 2016-05-05 Time 11:07 Rev Time 0.00
Received By ccole Date 2016-04-25 Time 15:14 Sent To  
Notes
2016-04-25 15:14:26B24

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-05 Cont ID  
Sent By jwitmer Date 2016-05-05 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2016-05-05 Time 07:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2017-02-02 Cont ID  
Sent By ccole Date 2017-02-02 Time 09:48 Rev Time 0.00
Received By ccole Date 2017-02-02 Time 08:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2016-12-29 Cont ID  
Sent By ccole Date 2016-12-29 Time 07:34 Rev Time 0.00
Received By ccole Date 2016-12-28 Time 17:00 Sent To  
Notes
2016-12-29 08:14:105TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16041117
 12/28/16
  
 THE FOLLOWING REVIEW IS BASED ON THE REVISED PLANS FROM
 MESSLER AND ASSOCIATES DATED 12/14/16
  
 1) CORRECT SCOPE OF WORK #8 ON THE COVER SHEET THAT
 INDICATES NO CHANGE TO THE AC SYSTEM TO MATCH THE SCOPE
 OF WORK SHOWN.
  
 2) THE REVISED PLAN IS NOW INDICATING TWO 5-TON RTU'S A
 SHARING A RETURN AIR PLENUM WHICH REQUIRES A SMOKE
 DETECTOR PER SECTION 606.2.2.
  
 3) THE EQUIPMENT SCHEDULE FOR THE NEW 5-TON SYSTEM IS
 INCOMPLETE- PROVIDED THE MANUFACTURER, THE AHRI
 CERTIFICATION NUMBER, AND THE ELECTRICAL DATA.
  
 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW TOILET
 ROOM EXHAUST FAN, AND SHOW THE EXHAUST DUCT TERMINATION
 LOCATION.
  
 5) THE COMBUSTION AIR CALCULATION INDICATES A SHORTAGE
 OF 9937 CU. FT. OF INDOOR SPACE. PLEASE CLARIFY HOW THE
 SHORTAGE WILL BE COMPENSATED FOR. IF THE AIR IS TO BE
 SUPPLIED MECHANICALLY REFER TO SECTION 304.9 FUEL GAS
 AND PROVIDE A CALCULATION.
  
 6) THE AC CALCULATIONS INDICATE A HEATING LOAD OF 39864
 BTUH. THE AC SCHEDULE INDICATES A SHORTAGRE OF 17664
 BTUH.
  
 7) PLEASE REMOVE THE AC LAYOUT PLANS FROM THE AC
 CALCULATIONS UNLESS THEY ARE TO BE USED ON THE
 PROJECT.\
  
 8) REFER TO SECTION 301.15 AND PROVIDE SITE SPECIFIC
 WIND LOAD ENGINEERING FOR INSTALLATION OF THE NEW RTU
 IN COMPLIANCE WITH SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-12-05 Cont ID  
Sent By ccole Date 2016-12-05 Time 16:28 Rev Time 0.00
Received By ccole Date 2016-12-05 Time 16:28 Sent To  
Notes
2016-12-05 16:50:084TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16041117
 12/5/16
  
 1) THE REVISED SHEET 2 SHOWS THE NEW 5TON AIR HANDLER
 PRODUCING 3267 CFMS, HOWEVER PER THE SCHEDULE THE
 SYSTEM IS LIMITIED TO 2000 CFMS. IF THERE IS A SECOND
 AIR HANDLER IN THE CLOSET PLEASE SHOW IT AND REDESIGN
 THE DUCT LAYOUT ACCORDINGLY.
  
 2) THE REVISED SHEET 2 SHOWS TWO 5TON PACKAGED UNITS IN
 A SECTION DRAWING AT THE TOP RIGHT OF THE PAGE. THE
 SCHEDULE SHOWS ONLY ONE PACKAGE UNIT- PLEASE CORRECT
 AND PROVIDE GUARDS AT THE ROOF EDGES IN COMPLIANCE WITH
 SECTION 304.11.
  
 3) AS PREVIOUSLY NOTED, THE SUMMARY AC LOAD
 CALCULATIONS MUST BEAR THE SIGNATURE AND SEAL OF THE
 ENGINEER OF RECORD.
  
 4) AS PREVIOUSLY REQUESTED, PROVIDE AN AIR BALANCE
 CALCULATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-11-08 Cont ID  
Sent By ccole Date 2016-11-01 Time 09:23 Rev Time 0.00
Received By ccole Date 2016-11-01 Time 08:44 Sent To  
Notes
2016-11-08 09:23:493RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16041117
 11/1/16
  
 1) THE AC PLANS AND SUBMITTALS ARE IN CONFLICT:
  
 A) SHEET 2 SHOWS A GROUND-MOUNTED 10 TON CONDENSER,
 SHEET 3 SHOWS A 5-RON ROOF MOUNTED CONDENSER.
 B) THE RESPONSE NARRATIVE INDICATES A REPLACED 5-TON
 SYSTEM AND A NEW 5-TON SYSTEM TO BE INSTALLED.
 CONSISTENTLY LABEL AND IDENTIFY THE LOCATIONS OF THE
 TWO SYSTEMS ON SHEETS 2 & 3.
 C) NEITHER SHEET 2 OR 3 PROVIDE COMPLETE DUCT LAYOUT
 PLANS. SHEET 2 DOES NOT SHOW ANY AIR DISTRIBUTION IN
 THE JUICE BAR AREA OR DINING ROOM. AN AIR DISTRIBUTION
 PLAN FROM ENERGY HOUSE TECHNOLOGY HAS BEEN SUBMITTED
 ALONG WITH CALCULATIONS THAT DO NOT MATCH WITH SHEET 2.
 D) THE SUBMITTED AC LOAD SUMMARY CALCULATIONS MUST BE
 SIGNED AND SEALED BY AN ENGINEER PER SECTION C403.2.1
 EXCEPTION FBC-14 ENERGY CONSERVATION.
 E) THE 10" DUCTS SUPPLYING 500 CFMS OF AIR ON SHEET 2
 ARE UNDERSIZED AT 0.1 FRICTION RATE.
  
 2) AS PREVIOUSLY REQUESTED PROVIDE AC EQUIPMENT
 SCHEDULES ON THE PLAN.
  
 3) AS PREVIOUSLY PROVIDE AIR BALANCE CALCULATIONS.
  
 4) AS PREVIOUSLY REQUESTED PROVIDE A ROOF PLAN SHOWING
 ALL REQUIRED CLEARANCE DISTANCE MEASUREMENTS FOR AIR
 INTAKES TO EXHAUST OUTLETS, AND FROM EQUIPMENT TO ROOF
 EDGES.
  
 5) MANUFACTURER'S SPECIFICATIONS FOR A GAS-FIRED
 CHARBROILER AND VERTICAL BROILER HAVE BEEN SUBMITTED,
 HOWEVER NEITHER APPLIANCE IS SHOWN ON THE PLAN. PLEASE
 REMOVE THE SUBMITTALS OR SHOW THE LOCATIONS OF THE
 APPLIANCES ON NTHE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-19 Cont ID  
Sent By ccole Date 2016-07-19 Time 12:14 Rev Time 0.00
Received By ccole Date 2016-07-19 Time 12:14 Sent To  
Notes
2016-07-19 12:24:202ND REVIEW MECHANICAL
 PERMIT #16041117
 7/19/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 DINING ROOM AND KITCHEN PER TABLE 403.3 FBC-14
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR FOR THE DINIG
 ROOM, AND EXHAUST AIR FOR THE KITCHEN- REFER TO TABLE
 403.3 FOOTNOTE B, AND SECTION 403.2.1- ALL AIR FROM THE
 KITCHEN SHALL BE EXHAUSTED AND RECIRCULATION OF AIR TO
 OTHER ROOMS OR SPACES IS PROHIBITED- SEE COMMENT #1
 FROM THE 1ST REVIEW PRINTED BELOW.
  
 2) THE REVISED PLANS DO NOT INDICATE IF THERE IS AN
 EXISTING OR NEW KITCHEN EXHAUST HOOD TO BE INSTALLED
 ABOVE THE NEW GAS-FIRED APPLIANCES- SEE COMMENT #2 FROM
 THE 1ST REVIEW PRINTED BELOW.
  
 3) A NEW 10 TON CONDENSER IS SHOWN ON THE PLAN. PROVIDE
 AN AC EQUIPMENT SCHEDULE ON THE PLAN FOR BOTH THE
 CONDENSER AND THE MATCHING AIR HANDLER- REFER TO
 SECTION C101.4.7 FBC-14 ENERGY CONSERVATION. PLEASE
 REVIEW COMMENT #4 FROM THE 1ST REVIEW AND PROVIDE AC
 COOLING AND HEATING CALCULATIONS.
  
 4) AS PREVIOUSLY REQUESTED, PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE COPOKING APPLIANCES- SEE COMMENT
 #5 PRINTED BELOW.
  
 5) SEE COMMENT #6 PRINTED BELOW.
  
 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16041117
 5/5/16
  
 1) A NEW EXHAUST HOOD IS BEING INSTALLED IN THE
 KITCHEN: PLEASE PROVIDE MINIMUM VENTILATION AND AIR
 BALANCE CALCULATIONS FOR THE RESTAURANT- SEE TABLE
 403.3 FOR REQUIRED OUTDOOR AIR AND EXHAUST CFM'S AND
 RATES.
 2) THE WPB DEVELOPMENT SERVICES DEPARTMENT/BUILDING
 DIVISION REQUIRES SEPARATE PERMITS FOR KITCHEN HOOD
 EXHAUST AND FIRE SUPPRESSION SYSTEMS- PLEASE PLACE A
 NOTE ON THE PLAN ACCORDINGLY.
 3) THE PLAN IS ALSO INDICATING A NEW DISHWASHER WHICH
 REQUIRES A TYPE II EXHAUST HOOD AS NOTED IN SECTION
 507.2.2.. PLEASE PLACE A NOTE INDICATING PLANS TO BE
 SUBMITTED UNDER A SEPARATE PERMIT.
 4) NEW HEAT-PRODUCING APPLIANCES ARE SHOWN IN THE
 KITCHEN WHICH WILL CONTRIBUTE TO THE TOTAL HEAT LOAD OF
 THE SPACE- PLEASE PROVIDE AC COOLING AND HEATING
 CALCULATIONS AND VERIFY THAT THE EXISTING AC SYSTEMS
 CAN HANDLE THE INCREASED LOAD, OR PROVIDE PLANS AND
 SPECIFICATIONS FOR ANY NEW UPGRADES.
 5) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW GAS
 APPLIANCES AND INDICATE HOW THE AIR IS BEING PROVIDED-
 SEE SECTION 304 FBC-14 FUEL GAS.
 6) ALTHOUGH THE HOODS, FANS AND EXHAUST OUTLETS WILL BE
 UNDER SEPARATE PERMIT, PLEASE INDICATE WHERE THE
 EXHAUST OUTLETS WILL TERMINATE AND SHOW THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS AS INDICATED IN
 SECTIONS 501.3.1 (2), 506.3.13.2, & 506.4.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By ccole Date 2016-05-05 Time 10:41 Rev Time 0.00
Received By ccole Date 2016-05-05 Time 10:40 Sent To  
Notes
2016-05-05 10:45:151ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16041117
 5/5/16
  
 1) A NEW EXHAUST HOOD IS BEING INSTALLED IN THE
 KITCHEN: PLEASE PROVIDE MINIMUM VENTILATION AND AIR
 BALANCE CALCULATIONS FOR THE RESTAURANT- SEE TABLE
 403.3 FOR REQUIRED OUTDOOR AIR AND EXHAUST CFM'S AND
 RATES.
 2) THE WPB DEVELOPMENT SERVICES DEPARTMENT/BUILDING
 DIVISION REQUIRES SEPARATE PERMITS FOR KITCHEN HOOD
 EXHAUST AND FIRE SUPPRESSION SYSTEMS- PLEASE PLACE A
 NOTE ON THE PLAN ACCORDINGLY.
 3) THE PLAN IS ALSO INDICATING A NEW DISHWASHER WHICH
 REQUIRES A TYPE II EXHAUST HOOD AS NOTED IN SECTION
 507.2.2.. PLEASE PLACE A NOTE INDICATING PLANS TO BE
 SUBMITTED UNDER A SEPARATE PERMIT.
 4) NEW HEAT-PRODUCING APPLIANCES ARE SHOWN IN THE
 KITCHEN WHICH WILL CONTRIBUTE TO THE TOTAL HEAT LOAD OF
 THE SPACE- PLEASE PROVIDE AC COOLING AND HEATING
 CALCULATIONS AND VERIFY THAT THE EXISTING AC SYSTEMS
 CAN HANDLE THE INCREASED LOAD, OR PROVIDE PLANS AND
 SPECIFICATIONS FOR ANY NEW UPGRADES.
 5) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW GAS
 APPLIANCES AND INDICATE HOW THE AIR IS BEING PROVIDED-
 SEE SECTION 304 FBC-14 FUEL GAS.
 6) ALTHOUGH THE HOODS, FANS AND EXHAUST OUTLETS WILL BE
 UNDER SEPARATE PERMIT, PLEASE INDICATE WHERE THE
 EXHAUST OUTLETS WILL TERMINATE AND SHOW THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS AS INDICATED IN
 SECTIONS 501.3.1 (2), 506.3.13.2, & 506.4.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2017-01-30 Cont ID  
Sent By gjohnson Date 2017-01-30 Time 09:45 Rev Time 0.00
Received By gjohnson Date 2017-01-30 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2017-01-13 Cont ID  
Sent By gjohnson Date 2017-01-13 Time 12:44 Rev Time 0.00
Received By gjohnson Date 2017-01-13 Time 12:44 Sent To  
Notes
2017-01-13 13:27:015TH REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 1.HAS NOT COMPLIED RISER STILL SHOWS HORIZONTAL DRY
 VENTS 3. THE HORIZONTAL DRY VENT AT THE END OF THE
 RISER DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO
 VENT SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT
 CONNECTION TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 2.NOT COMPLIED SHOW WC CONNECTING TO HORIZONTAL DRAIN
 DOES NOT NEED TO BE INDIVIDUALLY VENTED 5. IF THE
 TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO THE
 HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 3.PARTIALLY COMPLIED DISHWASHER SHALL DRAIN INTO A
 INDIRECT WASTE RECEPTOR NOT A AIR GAP FITTING 6. THE
 THREE COMPARTMENT SINK AND THE DISH WASHER SHALL BE
 INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL
 DISHWASHING MACHINES.
 THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE
 SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2.
 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN
 THE PREPARATION, SERVING OR EATING OF FOOD SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK
 TO THE DRAINAGE SYSTEM.
  
 NEW COMMENT
  
 1. VENTS FOR DISWASHER AND THREE COMPARTMENT SINK ARE
 MISSING PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1
  
 IN ORDER TO TO GET THIS PLAN APPROVED I SUGGEST THAT WE
 MEET TO GO OVER MY COMMENTS ON THE PLAN PLEASE CONTACT
 ME TO SET A DATE.
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2016-12-15 Cont ID  
Sent By gjohnson Date 2016-12-15 Time 10:40 Rev Time 0.00
Received By gjohnson Date 2016-12-15 Time 09:39 Sent To  
Notes
2016-12-15 10:40:314TH REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS
  
 1.HAS NOT COMPLIED RISER STILL SHOWS HORIZONTAL DRY
 VENTS 3. THE HORIZONTAL DRY VENT AT THE END OF THE
 RISER DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO
 VENT SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT
 CONNECTION TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 2.NOT COMPLIED SHOW WC CONNECTING TO HORIZONTAL DRAIN
 DOES NOT NEED TO BE INDIVIDUALLY VENTED 5. IF THE
 TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO THE
 HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 3.PARTIALLY COMPLIED DISHWASHER SHALL DRAIN INTO A
 INDIRECT WASTE RECEPTOR NOT A AIR GAP FITTING 6. THE
 THREE COMPARTMENT SINK AND THE DISH WASHER SHALL BE
 INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL
 DISHWASHING MACHINES.
 THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE
 SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2.
 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN
 THE PREPARATION, SERVING OR EATING OF FOOD SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK
 TO THE DRAINAGE SYSTEM.
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-11-08 Cont ID  
Sent By gjohnson Date 2016-11-08 Time 09:14 Rev Time 0.00
Received By gjohnson Date 2016-11-07 Time 16:11 Sent To  
Notes
2016-11-08 08:49:353RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW TOILET DISPENSER 7"-9" OFF THE FRONT EDGE OF
 TOILET. PER FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 2. SHOW THE WATER CLOSET 16" MIN AND 18" MAX OFF THE
 SIDE WALL TO CENTERLINE OF TOILET. PER FBC ACC 604.2
 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION
  
 3. THE HORIZONTAL DRY VENT AT THE END OF THE RISER
 DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO VENT
 SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT CONNECTION
 TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 4.THE NOTE ON THE RISER ABOVE THE TOILET READS 11/2" IS
 THIS INDICATING PIPE SIZE WATER CLOSET SHALL BE ON MIN
 OF 3" PIPE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. IF THE TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO
 THE HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 6. THE THREE COMPARTMENT SINK AND THE DISH WASHER SHALL
 BE INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL
 DISHWASHING MACHINES.
 THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE
 SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2.
 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN
 THE PREPARATION, SERVING OR EATING OF FOOD SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK
 TO THE DRAINAGE SYSTEM.
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-07-31 Cont ID  
Sent By tklarge Date 2016-07-31 Time 10:01 Rev Time 0.00
Received By tklarge Date 2016-07-31 Time 09:45 Sent To  
Notes
2016-07-31 09:43:381) SHT. 2 - THE TOILET PAPER DISPENSER SHALL COMPLY
 WITH FBC-ACCESS.SEC.604.9.6.
 2) THE GRAB BARS SHALL BE INSTALLED IN ACCORDANCE WITH
 FBC-ACCESS. SEC. 609.4.
 3) THE WATER CLOSET SHALL BE PROVIDED WITH A CLEAR
 FLOOR SPACE OF 60 INCHES WIDE BY 56 INCHES DEEP IN
 ACCORDANCE WITH 2014 FBC-ACCESS SEC.604.3.1, 604.3.2.
 AS DESIIGNED, THE TOILET ROOM IS NOT WIDE ENOUGH.
 4) THE SANITARY RISERS DO COMPLY WITH THE
 FBC-PLUMBING.FIXTURES ARE NOT VENTED, FLAT,DRY VENTS
 NOT PERRMITTED BY CODE, NO CLEANOUTS IN STACKS. 2014
 FBC-PLUMBING SECS.905.3,901.2.1, 708.3.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By gearl Date 2016-05-04 Time 14:04 Rev Time 0.00
Received By gearl Date 2016-05-04 Time 14:04 Sent To  
Notes
2016-05-04 14:16:03 
  
  
  
 1. NEED GAS RISER DIAGRAM TO INCLUDE BTU FOR GRILL -
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS SECTION
 107.3.5.1.3
  
  
 2. NEED TO HAVE D/W DISCHARGE THRU GREASE TRAP FBC
 PLUMBING 1003.3.1
  

Review Stop Z ZONING
Rev No 6 Status P Date   Cont ID  
Sent By   Date 2017-02-07 Time   Rev Time 0.00
Received By   Date 2017-02-07 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2017-01-04 Cont ID  
Sent By awooten Date 2017-01-04 Time   Rev Time 0.00
Received By awooten Date 2017-01-04 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2016-12-15 Cont ID  
Sent By awooten Date 2016-12-15 Time 13:09 Rev Time 0.00
Received By awooten Date 2016-12-07 Time 11:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-10-28 Cont ID  
Sent By awooten Date 2016-10-28 Time   Rev Time 0.00
Received By awooten Date 2016-10-28 Time   Sent To  
Notes
2016-10-28 11:25:43ZONING APPROVAL IS FOR INTERIOR REMODELING ONLY.
  
 ALANA WOOTEN
 561-822-1449

Review Stop Z ZONING
Rev No 2 Status P Date 2016-08-22 Cont ID  
Sent By awooten Date 2016-08-22 Time 16:07 Rev Time 0.00
Received By awooten Date 2016-08-22 Time 16:07 Sent To  
Notes
2016-08-22 16:08:42ZONING APPROVAL IS FOR INTERIOR REMODELING ONLY.
  
 ALANA WOOTEN
 561-822-1449
2016-08-18 13:36:07ROUTED TO ALANA WOOTEN

Review Stop Z ZONING
Rev No 1 Status F Date 2016-06-15 Cont ID  
Sent By awooten Date 2016-06-15 Time 15:32 Rev Time 0.00
Received By awooten Date 2016-06-15 Time 15:31 Sent To  
Notes
2016-06-15 15:48:27THE SCOPE OF THIS WORK IS INTERIOR REMODELING ONLY.
 LOOKING ON GOOGLE STREET VIEW IT APPEARS THAT THE FRONT
 FACED IS ANGLED, BUT THE PLANS SHOW A SQUARED OFF
 BUILDING. BASED ON THE INFORMATION PROVIDED, NO
 ADDITIONAL SQUARE FOOTAGE CAN BE ADDED. IS THE PLANTER
 BEING REMOVED?
  
 THE PARKING WILL REQUIRE A SEPARATE PERMIT WITH PLANS
 AND AN ADDITIONAL REVIEW WILL OCCUR AFTER PARKING PLAN
 SUBMITTAL.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved