| Plan Review Stops For Permit 16041117 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2017-02-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-02-07 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-02-07 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2017-02-07 09:40:15 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16041117 | | | ADD: 6611 S. DIXIE HWY. | | | CONT: T. B. D./ TO BE DETERMINED | | | TEL: 856-6655 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 6TH REVIEW | | | DATE: TUES. FEB. 07/ 2017 | | | ACTION: BUILDING PROVISO | | | | | | 1) SHEET 2 OF 3 INDICATES A NEW ROOF TOP A/C UNIT, | | | PLEASE PROVIDE PRODUCT INFORMATION FOR THE NEW ROOF TOP | | | UNIT AND THE CONNECTION (ATTACHMENT) OF THE ROOF TOP | | | UNIT TO CURB. | | | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND | | | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2017-01-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-01-04 |
Time |
07:02 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-01-04 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2017-01-04 07:02:36 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16041117 | | | ADD: 6611 S. DIXIE HWY. | | | CONT: T. B. D./ TO BE DETERMINED | | | TEL: 856-6655 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 5TH REVIEW | | | DATE: WED. JAN. 04/2017 | | | ACTION: DENIED | | | | | | 1) THE COVERSHEET UNDER THE HEADING SCOPE OF WORK | | | STATEMENT # 8 AIR CONDITIONING EXISTING NO CHANGES. | | | THERE IS A DISCREPANCY IN PLANS, SHEET 2 OF 3 THE ROOF | | | PLAN INDICATES TO INSTALL A SECOND 5 TON ROOF TOP UNIT, | | | MAINTAIN 36 INCHES APART. 2014 FLORIDA BUILDING CODE W | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED, A DISCREPANCY IN PLANS. | | | | | | 2) SHEET 2 OF 3 INDICATING A NEW 5 TON ROOF TOP UNIT, | | | PLEASE PROVIDE THE TYPE OF ROOF SHEATHING/ DECK | | | MATERIAL TO BE PENETRATED, PLEASE PROVIDE THE TYPE OF | | | ROOF FRAMING, IF HEADERS ARE REQUIRED, IF A SECONDARY | | | ROOF JOIST IS REQUIRED( DOUBLER) AND OR IF BAR JOIST | | | SYSTEM AND TYPE & SIZE OF ANGLE IRON TO BE USED FOR | | | FRAMING, IF JOIST STIFFNER IS REQUIRED? | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | 3) SHEET 2 OF 3 INDICATES A NEW ROOF TOP A/C UNIT, | | | PLEASE PROVIDE PRODUCT INFORMATION FOR THE NEW ROOF TOP | | | CURB, ANCHORAGE OF CURB TO ROOF DECK, AND THE | | | CONNECTION OF THE | | | ROOF TOP UNIT TO CURB. FOR ALL ROOF TOP EQUIPMENT, | | | CURBS OR A/C STANDS, DETAILED ATTACHMENT TO THE ROOF | | | FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF STAND | | | TO THE EQUIPMENT ABOVE. | | | | | | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | 4) SHEET 2 OF 3 INDICATES A NEW ROOF TOP A/C UNIT, THE | | | PLANS DO NOT INDICATE THE ELEVATION OF THE ROOF ABOVE | | | GRADE NOR IF THERE IS A PARAPET REQUIREDTO TRANSVERSE | | | BEFORE GAINING ACCESS TO THE ROOF TOP UNIT. 2014 FBC-B | | | 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED | | | STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING | | | ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT | | | A HEIGHT EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL | | | BE PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, | | | THE EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL | | | TO THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. | | | SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER | | | OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) HIGH OR | | | WALKING ON ROOFS. | | | | | | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2016-12-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-12-06 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-12-06 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-11-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-11-09 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-11-09 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-08-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-08-04 |
Time |
06:59 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-08-04 |
Time |
06:30 |
Sent To |
Z |
|
| Notes |
| 2016-08-04 06:56:25 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16041117 | | | ADD: 6611 S. DIXIE HWY. | | | CONT: T. B. D./ TO BE DETERMINED | | | TEL: 856-6655 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: THURS. AUGUST 04/ 2016 | | | ACTION: DENIED | | | | | | 1) COVERSHEET: | | | 1A) COMPLIED. | | | 1B) 2ND REQUEST. THE DESIGNER OF RECORD HAS INDICATED | | | THIS IS A LEVEL 1 ALTERATION. PLEASE REVIEW 2014 | | | EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL | | | NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | 1ST ROUND COMMENT. THE DESIGNER OF RECORD HAS NOT | | | INDICATED COMPLIANCE WITH 2014 FBC-EXISTING BUILDING | | | CODE 301.1 GENERAL. THE REPAIR, ALTERATION, CHANGE OF | | | OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING | | | BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED | | | IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE | | | APPLICANT. APPLICATION OF A METHOD SHALL BE THE SOLE | | | BASIS FOR ASSESSING THE COMPLIANCE OF WORK PERFORMED | | | UNDER A SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE | | | CODE OFFICIAL. SECTIONS 301.1.1 THROUGH 301.1.3 SHALL | | | NOT BE APPLIED IN COMBINATION WITH EACH OTHER. | | | | | | 2) 2ND REQUEST. SHEET 2 OF 3 SHOWS NEW WALLS WITHIN THE | | | ACCESSIBLE REST ROOM. 2014 EXISTING BUILDING CODE LEVEL | | | II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, | | | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. | | | 2014 FBC-ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A | | | WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM | | | MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES | | | (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | | WALL. | | | | | | 3) 2ND REQUEST. SHEET 2 OF 3 SHOWS THE BACK AND SIDE | | | GRAB BARS SHOW 33-36 INCHES CENTER LINE OF THE GRAB | | | BAR. PLEASE SHOW COMPLIANCE WITH | | | ACCESS. CODE 609.4 POSITION OF GRAB BARS. GRAB BARS | | | SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES | | | (840 MM) MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE | | | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING | | | SURFACE, | | | | | | 4)2ND REQUEST. 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART,? DO NOT RECITE CODE SECTIONS!!! | | | SHEET 2 OF 3 ON THE FLOOR PLAN INDICATES A NEW PASS | | | THROUGH WINDOW BUT NO ELEVATIONS. PLEASE PROVIDE | | | COMPLIANCE WITH: 2014 FBC-ACCESS. CODE : | | | 904.5 FOOD SERVICE LINES. COUNTERS IN FOOD SERVICE | | | LINES SHALL COMPLY WITH 904.5. 904.5.1 SELF-SERVICE | | | SHELVES AND DISPENSING DEVICES. SELF-SERVICE SHELVES | | | AND DISPENSING DEVICES FOR TABLEWARE, DISHWARE, | | | CONDIMENTS, FOOD AND BEVERAGES SHALL COMPLY WITH 308. | | | | | | 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE | | | 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 5) 2ND REQUEST. 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART,? DO NOT RECITE CODE SECTIONS!!! | | | SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014 | | | FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING | | | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 6) 2ND REQUEST. 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART,? DO NOT RECITE CODE SECTIONS!!! | | | SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014 | | | FBC-ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND | | | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE | | | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING | | | DINING SURFACES AND WORK SURFACES. PLEASE NOTE IF THE | | | DINING COUNTER AT THE FRONT WINDOW IS A HIGH-TOP OR | | | NOT. IF HIGH TOP ACCESSIBLE SEATING MUST BE THERE AS | | | WELL. | | | | | | 7) NOTATION ONLY!!! ADDITIONAL PERMITS ARE REQUIRED, | | | FOR GAS APPLIANCES, AND THE HOOD, ANSEL SYSTEMS AND | | | EXHAUST SYSTEMS. | | | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW | | | COMMENTS FROM ALL DISCIPLINES: | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-05-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-05-05 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-05-05 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2016-05-05 07:57:31 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 16041117 | | | ADD: 6611 S. DIXIE HWY. | | | CONT: T. B. D./ TO BE DETERMINED | | | TEL: 856-6655 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. MAY 05/ 2016 | | | ACTION: DENIED | | | | | | 1) COVERSHEET: | | | 1A) THE DESIGNER OF RECORD HAS NOT INDICATED TO WHAT | | | CODE THESE PLANS WERE DESIGNED? 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 1B) THE DESIGNER OF RECORD HAS NOT INDICATED COMPLIANCE | | | WITH 2014 FBC-EXISITNG BUILDING CODE 301.1 GENERAL. THE | | | REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR | | | RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH | | | ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH | | | 301.1.3 AS SELECTED BY THE APPLICANT. APPLICATION OF A | | | METHOD SHALL BE THE SOLE BASIS FOR ASSESSING THE | | | COMPLIANCE OF WORK PERFORMED UNDER A SINGLE PERMIT | | | UNLESS OTHERWISE APPROVED BY THE CODE OFFICIAL. | | | SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED | | | IN COMBINATION WITH EACH OTHER. | | | | | | 2) SHEET 2 OF 3 SHOWS NEW WALLS WITHIN THE ACCESSIBLE | | | REST ROOM. 2014 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | 2014 FBC-ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A | | | WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM | | | MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES | | | (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | | WALL. | | | | | | 3) SHEET 2 OF 3 SHOWS THE BACK AND SIDE GRAB BARS SHOW | | | 33-36 INCHES CENTER LINE OF THE GRAB BAR. PLEASE SHOW | | | COMPLIANCE WITH | | | ACCESS. CODE 609.4 POSITION OF GRAB BARS. GRAB BARS | | | SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES | | | (840 MM) MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE | | | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING | | | SURFACE, | | | | | | 4) SHEET 2 OF 3 ON THE FLOOR PLAN INDICATES A NEW PASS | | | THROUGH WINDOW BUT NO ELEVATIONS. PLEASE PROVIDE | | | COMPLIANCE WITH: 2014 FBC-ACCESS. CODE : | | | 904.5 FOOD SERVICE LINES. | | | COUNTERS IN FOOD SERVICE LINES SHALL COMPLY WITH 904.5. | | | | | | 904.5.1 SELF-SERVICE SHELVES AND DISPENSING DEVICES. | | | SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR | | | TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES | | | SHALL COMPLY WITH 308. | | | | | | 904.5.2 TRAY SLIDES. | | | THE TOPS OF TRAY SLIDES SHALL BE 28 INCHES (710 MM) | | | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | | | | 5) SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014 | | | FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING | | | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 6) SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014 | | | FBC-ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND | | | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE | | | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING | | | DINING SURFACES AND WORK SURFACES. PLEASE NOTE IF THE | | | DINING COUNTER AT THE FRONT WINDOW IS A HIGH-TOP OR | | | NOT. IF HIGH TOP ACCESSIBLE SEATING MUST BE THERE AS | | | WELL. | | | | | | 7) NOTATION ONLY!!! ADDITIONAL PERMITS ARE REQUIRED, | | | FOR GAS APPLIANCES, AND THE HOOD AND EXHAUST SYSTEMS. | | | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW | | | COMMENTS FROM ALL DISCIPLINES: | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2017-02-08 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-02-08 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-02-08 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2017-01-18 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2017-01-18 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2017-01-18 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2017-01-18 13:47:51 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] COMPLY WITH OTHER TRADES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2016-12-12 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-12-12 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-12-12 |
Time |
10:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-10-31 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-10-31 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-07-21 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-07-21 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-07-21 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2016-07-21 12:50:50 | JOB PERMIT NUMBER: 16041117 | | | JOB ADDRESS: 6611 SOUTH DIXIE HIGHWAY | | | WEST PALM BEACH FLORIDA "LOS ALTOS DE JALISCO" ( | | | EXISTING RESTAURANT ) | | | DATE: JULY 21 2016 | | | ELECTRICAL PLAN REVIEW COMMENTS | | | | | | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF | | | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, | | | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST | | | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. | | | | | | - QUAD RECEPTACLES IN SMOOTHIE JUICE BAR PREP AREA | | | SHALL HAVE GFCI PROTECTION NEC 210.8(B) | | | - EMERGENCY LIGHTING WAS SHOWN IN THE KITCHEN, HOWEVER | | | PLEASE CORRECT THE NOTE TO STATE THAT EXIT / EMERGENCY | | | LIGHTS SHALL BE CONNECTED TO THE LOCAL LIGHTING AHEAD | | | SERVED BY AREA. NEC 700.12(F)(4) | | | - OCCUPANCY SENSOR IN BATH WAS NOT ADDED AS REQUESTED | | | PLEASE COMPLY WITH FBC E SECTION C405.2.2.2. IN | | | ADDITION ALL DEVICES IN THE ADA BATHROOM SHALL BE IN | | | COMPLIANCE WITH OBSTRUCTED & UNOBSTRUCTED FORWARD REACH | | | REQUIREMENTS 48?? HIGH SIDE AND 15?? LOW SIDE ABOVE THE | | | FINISH FLOOR. FBC A SECTION 308 ( VERIFY DEPTH IF | | | APPLICABLE ) | | | | | | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | | MENTIONED DEFICIENCIES. | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD | | | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE | | | OR ACTION TO SAME. | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE | | | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARISON. | | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-05-02 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-02 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-05-02 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2016-05-02 11:06:07 | JOB PERMIT NUMBER: 16041117 | | | JOB ADDRESS: 6611 S DIXIE HIGHWAY | | | WEST PALM BEACH FLORIDA | | | DATE: MAY 2 2016 | | | ELECTRICAL PLAN REVIEW COMMENTS | | | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF | | | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, | | | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST | | | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. | | | | | | - MEP SHEET , ALL 125-VOLT, SINGLEPHASE,15- AND | | | 20-AMPERE RECEPTACLES IN COMMERCIAL KITCHEN REQUIRE NEC | | | 210.8 GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION(B) | | | OTHER THAN DWELLING UNITS. | | | - FBC-B 1006.2. EMERGENCY LIGHTING IS REQUIRED , INSIDE | | | THE KITCHEN PREP AREA AND DINING ROOM AREA, EMERGENCY | | | LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF SAME LOCAL | | | AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY THE AREA, | | | EM LIGHTS MAY BE ON OWN CIRCUIT NEC 700.12 (F) (4). | | | - C405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS SHALL | | | BE INSTALLED IN ALL CLASSROOMS, CONFERENCE/MEETING | | | ROOMS, EMPLOYEE LUNCH AND BREAK ROOMS, PRIVATE OFFICES, | | | RESTROOMS, STORAGE ROOMS AND JANITORIAL CLOSETS, AND | | | OTHER SPACES 300 SQUARE FEET (28 M2) OR LESS ENCLOSED | | | BY FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC | | | CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY | | | TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS | | | LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR | | | SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING | | | ON TO NOT MORE THAN 50 PERCENT POWER. | | | | | | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | | MENTIONED DEFICIENCIES. | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD | | | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE | | | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2017-02-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-02-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-02-02 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2016-12-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-12-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-12-27 |
Time |
15:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2016-12-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-12-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-12-02 |
Time |
09:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2016-10-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-10-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-10-27 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-07-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-07-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-07-18 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-04-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-04-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-04-27 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2016-04-27 14:41:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET 1 OF 3 - THERE IS NO REFERENCE OF COMPLIANCE | | | WITH THE CURRENT FIRE CODE. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012 | | | EDITION. | | | COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2011 | | | EDITION. | | | | | | 2) SHEET 1 OF 3 - COMMENT # 10 INDICATES A REFERENCE TO | | | NEW GAS SERVICE. ALL GAS SERVICE WORK SHALL BE DONE | | | UNDER SEPARATE SHOP DRAWINGS. | | | | | | 3) SHEET 1 OF 3 - NO OCCUPANCY CLASSIFICATION, OCCUPANY | | | LOAD, OR LIFE SAFETY PLAN IS PROVIDED. PLEASE PROVIDE | | | IN COMPLAINCE WITH THE ABOVE REFERENCED FIRE CODES. | | | | | | 4) SHEET 3 OF 3 - THERE IS A NOTE INDICATING THE | | | DIMENSION OF A HOOD. COMMERCIAL COOKING EQUIPMENT SHALL | | | COMPLY WITH NFPA 96, 2011 EDITION. THE HOOD SHALL | | | EXTEND TO OVER ALL COOKING EQUIPMENT INCLUDING THE DEEP | | | FRYER AND GAS GRILL. THE HOOD SYSTEM WORK SHALL BE | | | SUBMITTED AND COMPLETED UNDER SEPARATE SHOP DRAWING. | | | | | | 5) SHEET 3 OF 3 - THERE IS NO INDICATION OF A HOOD | | | SUPPRESSION SYSTEM. HOOD FIRE PROTECTION SHALL BE | | | PROVIDED FOR IN COMPLIANCE WITH NFPA 96 AND APPLICABLE | | | CODES UNDER SEPARATE SHOP DRAWINGS. | | | | | | 6) SHEET 3 OF 3 - THERE IS NO INDICATION OF ANY FIRE | | | EXTINGUISHERS, INCLUDING ONE CLASS K FOR THE DEEP FAT | | | FYER. PLEASE PROVIDE PER NFPA 10. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2017-01-30 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-30 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-30 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2017-01-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-13 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-13 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2017-01-13 13:58:19 | 3RD REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: PREVIOUS | | | | | | PARTIALLY COMPLIED 1. PLEASE SHOW REQUIRED PRESSURE | | | REGULATORS AND THE ANSUL SYSTEM EMERGENCY SHUT OFF | | | VALVE. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | NOT COMPLIED PLEASE PROVIDE 6. THE MANUFACTURE SPEC | | | SHEETS SHALL LIST THE SPECIFIC STANDARD THEY MEET SUCH | | | AS NFPA 54, NFPA 58 ALSO FBC FUEL GAS 623.1 COOKING | | | APPLIANCES. | | | COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT | | | INSTALLATION, INCLUDING RANGES, OVENS, STOVES, | | | BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND | | | BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI | | | Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE | | | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS. | | | | | | | | | | | | NEW COMMENT: | | | | | | 1.THE COMBUSTION AIR CALCULATION INDICATES A SHORTAGE | | | OF 9937 CU. FT. OF INDOOR SPACE. PLEASE CLARIFY HOW THE | | | SHORTAGE WILL BE COMPENSATED FOR. IF THE AIR IS TO BE | | | SUPPLIED MECHANICALLY REFER TO SECTION 304.9 FUEL GAS | | | AND PROVIDE A CALCULATION.. | | | | | | 2. INDICATE ON THE PLAN THE SYSTEM PRESSURE. PER FBC | | | GAS 402.2 | | | | | | 3. PROVIDE THE TABLES USED TO SIZE THE SYSTEM. WPB | | | AMEND TO FBC 107.2.1 | | | | | | IN ORDER TO TO GET THIS PLAN APPROVED I SUGGEST THAT WE | | | MEET TO GO OVER MY COMMENTS ON THE PLAN PLEASE CONTACT | | | ME TO SET A DATE. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-12-15 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-12-15 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2016-12-15 10:39:49 | 3RD REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: PREVIOUS | | | | | | PARTIALLY COMPLIED 1. PLEASE SHOW REQUIRED SHUT OFF | | | VALVES DRIP LEGS AND PRESSURE REGULATORS AND THE ANSUL | | | SYSTEM EMERGENCY SHUT OFF VALVE. PER WPB AMEND TO FBC | | | 107.2.1 | | | SHOW PRESSURE REGULATORS PLAN IS INDICATING 2PSI SYSTEM | | | BUT IT IS SIZED TO A .5PSI SYSTEM PLEASE CLARIFY. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | NOT COMPLIED PLEASE PROVIDE 6. THE MANUFACTURE SPEC | | | SHEETS SHALL LIST THE SPECIFIC STANDARD THEY MEET SUCH | | | AS NFPA 54, NFPA 58 ALSO FBC FUEL GAS 623.1 COOKING | | | APPLIANCES. | | | COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT | | | INSTALLATION, INCLUDING RANGES, OVENS, STOVES, | | | BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND | | | BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI | | | Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE | | | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS. | | | | | | NEW COMMENT: | | | | | | 1. THE COMBUSTION AIR CALCULATIONS ARE NOT ACCURATE THE | | | TOTAL BTU LISTED IN CALCULATION IS 156,000 THE TOTAL | | | BTU LISTED ON GAS RISER IS 437,140 . BY MY CALCULATIONS | | | 21'857 CU FT OF AIR IS REQUIRED. PLEASE CLARIFY PER | | | FBC-2014 FUEL GAS CODE SEC. 304. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2016-11-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-11-08 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-11-08 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2016-11-08 09:55:32 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE SHOW REQUIRED SHUT OFF VALVES DRIP LEGS AND | | | PRESSURE REGULATORS AND THE ANSUL SYSTEM EMERGENCY SHUT | | | OFF VALVE. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. PLEASE INDICATE THE MODELS ON MANUFACTURE SPEC | | | SHEET. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE BTU LOADS ON THE RISER DO NOT MATCH BTU LOAD ON | | | MANUFACTURE SPECS PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 4. MANUFACTURE SPECS SHOW 3/4 GAS SUPPLY'S THE RISER | | | SHOWS 1/2 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5., THE VERTICAL BROILER YOU PROVIDED MANUFACTURE SPECS | | | FOR IS NOT SHOWN ON THE FLOOR PLAN OR RISER DIAGRAM | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 6. THE MANUFACTURE SPEC SHEETS SHALL LIST THE SPECIFIC | | | STANDARD THEY MEET SUCH AS NFPA 54, NFPA 58 ALSO FBC | | | FUEL GAS 623.1 COOKING APPLIANCES. | | | COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT | | | INSTALLATION, INCLUDING RANGES, OVENS, STOVES, | | | BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND | | | BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI | | | Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE | | | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2016-07-31 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-07-31 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-07-31 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2016-07-31 09:51:23 | GAS | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL | | | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. | | | G2413. | | | | | | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE | | | CORRUGATED STAINLESS STEEL TUBING | | | | | | (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO | | | FBC SEC.107.2.1. | | | | | | 3. IS THE TACOS BROILER GAS OR ELECTRIC? IF IT IS GAS, | | | ADD IT ONTO THE GAS RISER. | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER | | | OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE | | | BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS | | | SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 | | | FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G | | | 2407. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. | | | SEC. G2413.2. . | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS (IF ANY) PER 2014 FBC-FUEL | | | GAS SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426. | | | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | | | THE GAS SHALL BE A SEPARATE PERMIT. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2017-02-08 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-02-08 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-02-08 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2017-01-18 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2017-01-18 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-12-22 |
Time |
16:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-12-15 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-11-29 |
Time |
09:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-11-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-11-09 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-10-25 |
Time |
13:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-08-22 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-08-22 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-07-12 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-06-17 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-06-17 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-06-17 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2016-06-17 13:06:21 | THESE PLANS WERE PUT BACK IN SHELF BY ZONING. VP ROUTED | | | TO CAROLINE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-05-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-05-05 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-04-25 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2016-05-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-05-05 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-05-05 |
Time |
07:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2017-02-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-02-02 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-02-02 |
Time |
08:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2016-12-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-29 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-28 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2016-12-29 08:14:10 | 5TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16041117 | | | 12/28/16 | | | | | | THE FOLLOWING REVIEW IS BASED ON THE REVISED PLANS FROM | | | MESSLER AND ASSOCIATES DATED 12/14/16 | | | | | | 1) CORRECT SCOPE OF WORK #8 ON THE COVER SHEET THAT | | | INDICATES NO CHANGE TO THE AC SYSTEM TO MATCH THE SCOPE | | | OF WORK SHOWN. | | | | | | 2) THE REVISED PLAN IS NOW INDICATING TWO 5-TON RTU'S A | | | SHARING A RETURN AIR PLENUM WHICH REQUIRES A SMOKE | | | DETECTOR PER SECTION 606.2.2. | | | | | | 3) THE EQUIPMENT SCHEDULE FOR THE NEW 5-TON SYSTEM IS | | | INCOMPLETE- PROVIDED THE MANUFACTURER, THE AHRI | | | CERTIFICATION NUMBER, AND THE ELECTRICAL DATA. | | | | | | 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW TOILET | | | ROOM EXHAUST FAN, AND SHOW THE EXHAUST DUCT TERMINATION | | | LOCATION. | | | | | | 5) THE COMBUSTION AIR CALCULATION INDICATES A SHORTAGE | | | OF 9937 CU. FT. OF INDOOR SPACE. PLEASE CLARIFY HOW THE | | | SHORTAGE WILL BE COMPENSATED FOR. IF THE AIR IS TO BE | | | SUPPLIED MECHANICALLY REFER TO SECTION 304.9 FUEL GAS | | | AND PROVIDE A CALCULATION. | | | | | | 6) THE AC CALCULATIONS INDICATE A HEATING LOAD OF 39864 | | | BTUH. THE AC SCHEDULE INDICATES A SHORTAGRE OF 17664 | | | BTUH. | | | | | | 7) PLEASE REMOVE THE AC LAYOUT PLANS FROM THE AC | | | CALCULATIONS UNLESS THEY ARE TO BE USED ON THE | | | PROJECT.\ | | | | | | 8) REFER TO SECTION 301.15 AND PROVIDE SITE SPECIFIC | | | WIND LOAD ENGINEERING FOR INSTALLATION OF THE NEW RTU | | | IN COMPLIANCE WITH SECTION 1609 FBC-14 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2016-12-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-05 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-05 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2016-12-05 16:50:08 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16041117 | | | 12/5/16 | | | | | | 1) THE REVISED SHEET 2 SHOWS THE NEW 5TON AIR HANDLER | | | PRODUCING 3267 CFMS, HOWEVER PER THE SCHEDULE THE | | | SYSTEM IS LIMITIED TO 2000 CFMS. IF THERE IS A SECOND | | | AIR HANDLER IN THE CLOSET PLEASE SHOW IT AND REDESIGN | | | THE DUCT LAYOUT ACCORDINGLY. | | | | | | 2) THE REVISED SHEET 2 SHOWS TWO 5TON PACKAGED UNITS IN | | | A SECTION DRAWING AT THE TOP RIGHT OF THE PAGE. THE | | | SCHEDULE SHOWS ONLY ONE PACKAGE UNIT- PLEASE CORRECT | | | AND PROVIDE GUARDS AT THE ROOF EDGES IN COMPLIANCE WITH | | | SECTION 304.11. | | | | | | 3) AS PREVIOUSLY NOTED, THE SUMMARY AC LOAD | | | CALCULATIONS MUST BEAR THE SIGNATURE AND SEAL OF THE | | | ENGINEER OF RECORD. | | | | | | 4) AS PREVIOUSLY REQUESTED, PROVIDE AN AIR BALANCE | | | CALCULATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2016-11-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-11-01 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-11-01 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2016-11-08 09:23:49 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16041117 | | | 11/1/16 | | | | | | 1) THE AC PLANS AND SUBMITTALS ARE IN CONFLICT: | | | | | | A) SHEET 2 SHOWS A GROUND-MOUNTED 10 TON CONDENSER, | | | SHEET 3 SHOWS A 5-RON ROOF MOUNTED CONDENSER. | | | B) THE RESPONSE NARRATIVE INDICATES A REPLACED 5-TON | | | SYSTEM AND A NEW 5-TON SYSTEM TO BE INSTALLED. | | | CONSISTENTLY LABEL AND IDENTIFY THE LOCATIONS OF THE | | | TWO SYSTEMS ON SHEETS 2 & 3. | | | C) NEITHER SHEET 2 OR 3 PROVIDE COMPLETE DUCT LAYOUT | | | PLANS. SHEET 2 DOES NOT SHOW ANY AIR DISTRIBUTION IN | | | THE JUICE BAR AREA OR DINING ROOM. AN AIR DISTRIBUTION | | | PLAN FROM ENERGY HOUSE TECHNOLOGY HAS BEEN SUBMITTED | | | ALONG WITH CALCULATIONS THAT DO NOT MATCH WITH SHEET 2. | | | D) THE SUBMITTED AC LOAD SUMMARY CALCULATIONS MUST BE | | | SIGNED AND SEALED BY AN ENGINEER PER SECTION C403.2.1 | | | EXCEPTION FBC-14 ENERGY CONSERVATION. | | | E) THE 10" DUCTS SUPPLYING 500 CFMS OF AIR ON SHEET 2 | | | ARE UNDERSIZED AT 0.1 FRICTION RATE. | | | | | | 2) AS PREVIOUSLY REQUESTED PROVIDE AC EQUIPMENT | | | SCHEDULES ON THE PLAN. | | | | | | 3) AS PREVIOUSLY PROVIDE AIR BALANCE CALCULATIONS. | | | | | | 4) AS PREVIOUSLY REQUESTED PROVIDE A ROOF PLAN SHOWING | | | ALL REQUIRED CLEARANCE DISTANCE MEASUREMENTS FOR AIR | | | INTAKES TO EXHAUST OUTLETS, AND FROM EQUIPMENT TO ROOF | | | EDGES. | | | | | | 5) MANUFACTURER'S SPECIFICATIONS FOR A GAS-FIRED | | | CHARBROILER AND VERTICAL BROILER HAVE BEEN SUBMITTED, | | | HOWEVER NEITHER APPLIANCE IS SHOWN ON THE PLAN. PLEASE | | | REMOVE THE SUBMITTALS OR SHOW THE LOCATIONS OF THE | | | APPLIANCES ON NTHE PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-07-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-07-19 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-07-19 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2016-07-19 12:24:20 | 2ND REVIEW MECHANICAL | | | PERMIT #16041117 | | | 7/19/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | DINING ROOM AND KITCHEN PER TABLE 403.3 FBC-14 | | | MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE | | | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR FOR THE DINIG | | | ROOM, AND EXHAUST AIR FOR THE KITCHEN- REFER TO TABLE | | | 403.3 FOOTNOTE B, AND SECTION 403.2.1- ALL AIR FROM THE | | | KITCHEN SHALL BE EXHAUSTED AND RECIRCULATION OF AIR TO | | | OTHER ROOMS OR SPACES IS PROHIBITED- SEE COMMENT #1 | | | FROM THE 1ST REVIEW PRINTED BELOW. | | | | | | 2) THE REVISED PLANS DO NOT INDICATE IF THERE IS AN | | | EXISTING OR NEW KITCHEN EXHAUST HOOD TO BE INSTALLED | | | ABOVE THE NEW GAS-FIRED APPLIANCES- SEE COMMENT #2 FROM | | | THE 1ST REVIEW PRINTED BELOW. | | | | | | 3) A NEW 10 TON CONDENSER IS SHOWN ON THE PLAN. PROVIDE | | | AN AC EQUIPMENT SCHEDULE ON THE PLAN FOR BOTH THE | | | CONDENSER AND THE MATCHING AIR HANDLER- REFER TO | | | SECTION C101.4.7 FBC-14 ENERGY CONSERVATION. PLEASE | | | REVIEW COMMENT #4 FROM THE 1ST REVIEW AND PROVIDE AC | | | COOLING AND HEATING CALCULATIONS. | | | | | | 4) AS PREVIOUSLY REQUESTED, PROVIDE COMBUSTION AIR | | | CALCULATIONS FOR THE COPOKING APPLIANCES- SEE COMMENT | | | #5 PRINTED BELOW. | | | | | | 5) SEE COMMENT #6 PRINTED BELOW. | | | | | | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #16041117 | | | 5/5/16 | | | | | | 1) A NEW EXHAUST HOOD IS BEING INSTALLED IN THE | | | KITCHEN: PLEASE PROVIDE MINIMUM VENTILATION AND AIR | | | BALANCE CALCULATIONS FOR THE RESTAURANT- SEE TABLE | | | 403.3 FOR REQUIRED OUTDOOR AIR AND EXHAUST CFM'S AND | | | RATES. | | | 2) THE WPB DEVELOPMENT SERVICES DEPARTMENT/BUILDING | | | DIVISION REQUIRES SEPARATE PERMITS FOR KITCHEN HOOD | | | EXHAUST AND FIRE SUPPRESSION SYSTEMS- PLEASE PLACE A | | | NOTE ON THE PLAN ACCORDINGLY. | | | 3) THE PLAN IS ALSO INDICATING A NEW DISHWASHER WHICH | | | REQUIRES A TYPE II EXHAUST HOOD AS NOTED IN SECTION | | | 507.2.2.. PLEASE PLACE A NOTE INDICATING PLANS TO BE | | | SUBMITTED UNDER A SEPARATE PERMIT. | | | 4) NEW HEAT-PRODUCING APPLIANCES ARE SHOWN IN THE | | | KITCHEN WHICH WILL CONTRIBUTE TO THE TOTAL HEAT LOAD OF | | | THE SPACE- PLEASE PROVIDE AC COOLING AND HEATING | | | CALCULATIONS AND VERIFY THAT THE EXISTING AC SYSTEMS | | | CAN HANDLE THE INCREASED LOAD, OR PROVIDE PLANS AND | | | SPECIFICATIONS FOR ANY NEW UPGRADES. | | | 5) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW GAS | | | APPLIANCES AND INDICATE HOW THE AIR IS BEING PROVIDED- | | | SEE SECTION 304 FBC-14 FUEL GAS. | | | 6) ALTHOUGH THE HOODS, FANS AND EXHAUST OUTLETS WILL BE | | | UNDER SEPARATE PERMIT, PLEASE INDICATE WHERE THE | | | EXHAUST OUTLETS WILL TERMINATE AND SHOW THE REQUIRED | | | CLEARANCE DISTANCE MEASUREMENTS AS INDICATED IN | | | SECTIONS 501.3.1 (2), 506.3.13.2, & 506.4.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-05-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-05-05 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-05-05 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2016-05-05 10:45:15 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #16041117 | | | 5/5/16 | | | | | | 1) A NEW EXHAUST HOOD IS BEING INSTALLED IN THE | | | KITCHEN: PLEASE PROVIDE MINIMUM VENTILATION AND AIR | | | BALANCE CALCULATIONS FOR THE RESTAURANT- SEE TABLE | | | 403.3 FOR REQUIRED OUTDOOR AIR AND EXHAUST CFM'S AND | | | RATES. | | | 2) THE WPB DEVELOPMENT SERVICES DEPARTMENT/BUILDING | | | DIVISION REQUIRES SEPARATE PERMITS FOR KITCHEN HOOD | | | EXHAUST AND FIRE SUPPRESSION SYSTEMS- PLEASE PLACE A | | | NOTE ON THE PLAN ACCORDINGLY. | | | 3) THE PLAN IS ALSO INDICATING A NEW DISHWASHER WHICH | | | REQUIRES A TYPE II EXHAUST HOOD AS NOTED IN SECTION | | | 507.2.2.. PLEASE PLACE A NOTE INDICATING PLANS TO BE | | | SUBMITTED UNDER A SEPARATE PERMIT. | | | 4) NEW HEAT-PRODUCING APPLIANCES ARE SHOWN IN THE | | | KITCHEN WHICH WILL CONTRIBUTE TO THE TOTAL HEAT LOAD OF | | | THE SPACE- PLEASE PROVIDE AC COOLING AND HEATING | | | CALCULATIONS AND VERIFY THAT THE EXISTING AC SYSTEMS | | | CAN HANDLE THE INCREASED LOAD, OR PROVIDE PLANS AND | | | SPECIFICATIONS FOR ANY NEW UPGRADES. | | | 5) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW GAS | | | APPLIANCES AND INDICATE HOW THE AIR IS BEING PROVIDED- | | | SEE SECTION 304 FBC-14 FUEL GAS. | | | 6) ALTHOUGH THE HOODS, FANS AND EXHAUST OUTLETS WILL BE | | | UNDER SEPARATE PERMIT, PLEASE INDICATE WHERE THE | | | EXHAUST OUTLETS WILL TERMINATE AND SHOW THE REQUIRED | | | CLEARANCE DISTANCE MEASUREMENTS AS INDICATED IN | | | SECTIONS 501.3.1 (2), 506.3.13.2, & 506.4.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2017-01-30 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-30 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-30 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2017-01-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-13 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-13 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2017-01-13 13:27:01 | 5TH REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED | | | | | | 1.HAS NOT COMPLIED RISER STILL SHOWS HORIZONTAL DRY | | | VENTS 3. THE HORIZONTAL DRY VENT AT THE END OF THE | | | RISER DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO | | | VENT SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT | | | CONNECTION TO DRAINAGE SYSTEM. | | | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL | | | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN | | | PIPE. | | | 905.4 VERTICAL RISE OF VENT. | | | EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT | | | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM | | | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. | | | | | | 2.NOT COMPLIED SHOW WC CONNECTING TO HORIZONTAL DRAIN | | | DOES NOT NEED TO BE INDIVIDUALLY VENTED 5. IF THE | | | TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO THE | | | HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB AMEND | | | TO FBC 107.2.1 | | | | | | 3.PARTIALLY COMPLIED DISHWASHER SHALL DRAIN INTO A | | | INDIRECT WASTE RECEPTOR NOT A AIR GAP FITTING 6. THE | | | THREE COMPARTMENT SINK AND THE DISH WASHER SHALL BE | | | INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL | | | DISHWASHING MACHINES. | | | THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE | | | SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A | | | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION | | | 802.2. | | | 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. | | | SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF | | | UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN | | | THE PREPARATION, SERVING OR EATING OF FOOD SHALL | | | DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK | | | TO THE DRAINAGE SYSTEM. | | | | | | NEW COMMENT | | | | | | 1. VENTS FOR DISWASHER AND THREE COMPARTMENT SINK ARE | | | MISSING PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1 | | | | | | IN ORDER TO TO GET THIS PLAN APPROVED I SUGGEST THAT WE | | | MEET TO GO OVER MY COMMENTS ON THE PLAN PLEASE CONTACT | | | ME TO SET A DATE. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-12-15 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-12-15 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2016-12-15 10:40:31 | 4TH REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS | | | | | | 1.HAS NOT COMPLIED RISER STILL SHOWS HORIZONTAL DRY | | | VENTS 3. THE HORIZONTAL DRY VENT AT THE END OF THE | | | RISER DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO | | | VENT SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT | | | CONNECTION TO DRAINAGE SYSTEM. | | | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL | | | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN | | | PIPE. | | | 905.4 VERTICAL RISE OF VENT. | | | EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT | | | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM | | | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. | | | | | | 2.NOT COMPLIED SHOW WC CONNECTING TO HORIZONTAL DRAIN | | | DOES NOT NEED TO BE INDIVIDUALLY VENTED 5. IF THE | | | TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO THE | | | HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB AMEND | | | TO FBC 107.2.1 | | | | | | 3.PARTIALLY COMPLIED DISHWASHER SHALL DRAIN INTO A | | | INDIRECT WASTE RECEPTOR NOT A AIR GAP FITTING 6. THE | | | THREE COMPARTMENT SINK AND THE DISH WASHER SHALL BE | | | INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL | | | DISHWASHING MACHINES. | | | THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE | | | SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A | | | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION | | | 802.2. | | | 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. | | | SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF | | | UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN | | | THE PREPARATION, SERVING OR EATING OF FOOD SHALL | | | DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK | | | TO THE DRAINAGE SYSTEM. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2016-11-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-11-08 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-11-07 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2016-11-08 08:49:35 | 3RD REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHOW TOILET DISPENSER 7"-9" OFF THE FRONT EDGE OF | | | TOILET. PER FBC ACC 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 | | | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND | | | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL | | | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES | | | NOT ALLOW CONTINUOUS PAPER FLOW. | | | | | | 2. SHOW THE WATER CLOSET 16" MIN AND 18" MAX OFF THE | | | SIDE WALL TO CENTERLINE OF TOILET. PER FBC ACC 604.2 | | | LOCATION. | | | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM | | | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR | | | PARTITION | | | | | | 3. THE HORIZONTAL DRY VENT AT THE END OF THE RISER | | | DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO VENT | | | SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT CONNECTION | | | TO DRAINAGE SYSTEM. | | | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL | | | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN | | | PIPE. | | | 905.4 VERTICAL RISE OF VENT. | | | EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT | | | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM | | | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. | | | | | | 4.THE NOTE ON THE RISER ABOVE THE TOILET READS 11/2" IS | | | THIS INDICATING PIPE SIZE WATER CLOSET SHALL BE ON MIN | | | OF 3" PIPE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. IF THE TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO | | | THE HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 6. THE THREE COMPARTMENT SINK AND THE DISH WASHER SHALL | | | BE INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL | | | DISHWASHING MACHINES. | | | THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE | | | SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A | | | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION | | | 802.2. | | | 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. | | | SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF | | | UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN | | | THE PREPARATION, SERVING OR EATING OF FOOD SHALL | | | DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK | | | TO THE DRAINAGE SYSTEM. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-07-31 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-07-31 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-07-31 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2016-07-31 09:43:38 | 1) SHT. 2 - THE TOILET PAPER DISPENSER SHALL COMPLY | | | WITH FBC-ACCESS.SEC.604.9.6. | | | 2) THE GRAB BARS SHALL BE INSTALLED IN ACCORDANCE WITH | | | FBC-ACCESS. SEC. 609.4. | | | 3) THE WATER CLOSET SHALL BE PROVIDED WITH A CLEAR | | | FLOOR SPACE OF 60 INCHES WIDE BY 56 INCHES DEEP IN | | | ACCORDANCE WITH 2014 FBC-ACCESS SEC.604.3.1, 604.3.2. | | | AS DESIIGNED, THE TOILET ROOM IS NOT WIDE ENOUGH. | | | 4) THE SANITARY RISERS DO COMPLY WITH THE | | | FBC-PLUMBING.FIXTURES ARE NOT VENTED, FLAT,DRY VENTS | | | NOT PERRMITTED BY CODE, NO CLEANOUTS IN STACKS. 2014 | | | FBC-PLUMBING SECS.905.3,901.2.1, 708.3.4. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-05-04 |
|
|
Cont ID |
|
| Sent By |
gearl |
Date |
2016-05-04 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
gearl |
Date |
2016-05-04 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2016-05-04 14:16:03 | | | | | | | | | | | | | 1. NEED GAS RISER DIAGRAM TO INCLUDE BTU FOR GRILL - | | | CITY OF WEST PALM BEACH LOCAL AMENDMENTS SECTION | | | 107.3.5.1.3 | | | | | | | | | 2. NEED TO HAVE D/W DISCHARGE THRU GREASE TRAP FBC | | | PLUMBING 1003.3.1 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-02-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2017-02-07 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2017-01-04 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2017-01-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2017-01-04 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2016-12-15 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2016-12-07 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-10-28 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2016-10-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2016-10-28 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-10-28 11:25:43 | ZONING APPROVAL IS FOR INTERIOR REMODELING ONLY. | | | | | | ALANA WOOTEN | | | 561-822-1449 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-08-22 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2016-08-22 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2016-08-22 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2016-08-22 16:08:42 | ZONING APPROVAL IS FOR INTERIOR REMODELING ONLY. | | | | | | ALANA WOOTEN | | | 561-822-1449 | | 2016-08-18 13:36:07 | ROUTED TO ALANA WOOTEN |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-06-15 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2016-06-15 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2016-06-15 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2016-06-15 15:48:27 | THE SCOPE OF THIS WORK IS INTERIOR REMODELING ONLY. | | | LOOKING ON GOOGLE STREET VIEW IT APPEARS THAT THE FRONT | | | FACED IS ANGLED, BUT THE PLANS SHOW A SQUARED OFF | | | BUILDING. BASED ON THE INFORMATION PROVIDED, NO | | | ADDITIONAL SQUARE FOOTAGE CAN BE ADDED. IS THE PLANTER | | | BEING REMOVED? | | | | | | THE PARKING WILL REQUIRE A SEPARATE PERMIT WITH PLANS | | | AND AN ADDITIONAL REVIEW WILL OCCUR AFTER PARKING PLAN | | | SUBMITTAL. | | | |
|
|