Plan Review Details - Permit 16041113
Plan Review Stops For Permit 16041113
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2016-05-07 Time 10:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-04-27 Cont ID  
Sent By mvaldes Date 2016-04-27 Time 17:58 Rev Time 0.00
Received By mvaldes Date 2016-04-27 Time 17:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-28 Cont ID  
Sent By scaldero Date 2016-04-28 Time 11:33 Rev Time 0.00
Received By scaldero Date 2016-04-28 Time 11:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-14 Cont ID  
Sent By ccole Date 2016-06-14 Time 09:28 Rev Time 0.00
Received By ccole Date 2016-06-13 Time 15:50 Sent To  
Notes
2016-06-13 15:50:43RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-03 Cont ID  
Sent By ccole Date 2016-06-03 Time 15:41 Rev Time 0.00
Received By ccole Date 2016-06-03 Time 11:37 Sent To  
Notes
2016-06-03 11:37:16RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2016-04-25 Time 08:58 Sent To  
Notes
2016-04-26 08:59:07B10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2016-05-07 Time 10:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-06-14 Cont ID  
Sent By ccole Date 2016-06-14 Time 09:28 Rev Time 0.00
Received By ccole Date 2016-06-14 Time 06:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-06-03 Cont ID  
Sent By ccole Date 2016-06-03 Time 15:21 Rev Time 0.00
Received By ccole Date 2016-06-03 Time 15:21 Sent To  
Notes
2016-06-03 15:41:302ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041113
 6/3/16
  
 1) ENERGY GAUGE TOTAL PERFORMANCE COMPLIANCE
 CALCULATIONS HAVE BEEN SUBMITTED: A) THE PROJECT IS
 INCORRECTLY CLASSIFIED AS A "NEW FINISHED BUILDING" ON
 PAGE 2. B) THE DOCUMENT HAS NOT BEEN SIGNED AND DATED
 BY THE OWNER AGENT, ARCHITECT, ELECTRICAL DESIGNER, AND
 LIGHTING DESIGNER- SEE PAGE 3. REFER TO SECTIONS C401.4
 AND C103.1.1.1.2 FBC-14 ENERGY CONSERVATION.
  
 2) AC COOLING AND HEATING CALCULATIONS HAVE BEEN
 SUBMITTED WITHOUT SIGNATURES AND DATES.
  
 3) IT APPEARS FROM THE CALCULATIONS THAT NEW
 REPLACEMENT HEAT PUMPS ARE TO BE PROVIDED. PLEASE NOTE
 THAT ON THE PLAN AND PROVIDED EQUIPMENT SCHEDULES.
  
 4) SHEET M-1: THE VENTILATION CALCULATIONS DO NOT
 APPEAR TO BE COMPLIANT WITH TABLE 403.3 OR ASHRAE 62.1-
 2010 EACH OF WHICH REQUIRES O/A CFM RATES PER PERSON AS
 WELL AS CFMS PER SQUARE FOOT
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By ccole Date 2016-04-28 Time 14:09 Rev Time 0.00
Received By ccole Date 2016-04-28 Time 14:03 Sent To  
Notes
2016-04-28 14:27:081ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16041113
 4/28/16
  
 1) CONCERNING THE ARCHITECT'S NOTE ON SHEET A-1 THAT
 STATES "ALL MECHANICAL WORK SHALL BE DONE UNDER A
 SEPARATE PERMIT AND SHOWN ON SEPARATE PERMIT DRAWINGS
 PREPARED BY OTHERS", PLEASE REFER TO SECTION 107.3.4
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 IT APPEARS THAT ACCORDING TO THE ABOVE SECTION THAT THE
 ARCHITECT OF RECORD SHALL, AT A MINIMUM, REVIEW AND
 APPROVE THE DEFERRED MECHANICAL PLANS, OR THOSE PANS
 SHALL BE SUBMITTED WITH UNDER THIS PERMIT APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  