Plan Review Details - Permit 16041093
Plan Review Stops For Permit 16041093
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-27 Cont ID  
Sent By skennedy Date 2016-05-27 Time 09:24 Rev Time 0.00
Received By skennedy Date 2016-05-27 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-16 Cont ID  
Sent By skennedy Date 2016-05-16 Time 10:21 Rev Time 0.00
Received By skennedy Date 2016-05-16 Time 10:21 Sent To  
Notes
2016-05-16 10:31:551ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 THE DESIGN IS ACCEPTABLE HOWEVER THE ARCHITECTS SEAL
 AND SIGNATURE IS A PHOTO COPY. SUBMIT PLANS WITH
 ORIGINAL SEAL AND SIGNATURERE. THE CONSTRUCTION
 DOCUMENTS PREPARED BY A REGISTERED DESIGN PROFESSIONAL
 SHALL CONTAIN ORIGINAL SEAL & SIGNATURE PURSUANT TO
 CHAPTER 481, FLORIDA STATUTES & 61G1 FLORIDA
 ADMINISTRATIVE CODE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-27 Cont ID  
Sent By skennedy Date 2016-05-27 Time 09:24 Rev Time 0.00
Received By skennedy Date 2016-05-27 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By mvaldes Date 2016-05-04 Time 13:26 Rev Time 0.00
Received By mvaldes Date 2016-05-04 Time 13:26 Sent To  
Notes
2016-05-06 10:32:56NEC 2011 1ST REVIEW
  
 FBC 107 - ALTHOUGHT THE ELECTRICAL DESIGN IS COMPLIANT,
 THE SUBMITTED PLANS CONTAIN A PHOTO COPY OF THE
 ORIGINAL SEAL AND SIGNATURE OF THE DESIGN PROFESSIONAL.
 PROVIDE DOCUMENTS WITH ORIGINAL SEAL AND SIGNATURE.
  
 MARIO VALDES
 ELECTRICAL PLANS EXAMINER
 561 805-6713

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2016-05-27 Cont ID  
Sent By skennedy Date 2016-05-27 Time 09:23 Rev Time 0.00
Received By skennedy Date 2016-05-27 Time 09:23 Sent To  
Notes
2016-05-27 09:24:22A SEPARATE GAS SUBMITTAL IS REQUIRE. SEE 5/6/16
 COMMENTS BY GEORGE JOHNSON.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By gjohnson Date 2016-05-06 Time 17:01 Rev Time 0.00
Received By gjohnson Date 2016-05-06 Time 17:01 Sent To  
Notes
2016-05-06 17:10:23 
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 GAS COMMENTS: SEPARATE PERMIT REQUIRED
  
 1. SUBMIT AN EXISTING ISOMETRIC DRAWING THAT CLEARLY
 SHOWS PIPE SIZE AND LONGEST DISTANCE FROM METER PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
  
 2. BTU LOAD OF EXISTING AND NEW APPLIANCES AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2014
 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1)
 THRU 402.4(37).
  
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR NEW
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 4. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-16 Cont ID  
Sent By skennedy Date 2016-05-16 Time 10:22 Rev Time 0.00
Received By skennedy Date 2016-04-25 Time 10:06 Sent To  
Notes
2016-04-26 10:07:01TRAVELLING WITH 16041090 - C31

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-12 Cont ID  
Sent By avann Date 2016-05-12 Time 14:19 Rev Time 0.00
Received By njwira Date 2016-05-12 Time 14:19 Sent To B
Notes
***NONE***