Plan Review Details - Permit 16041090
Plan Review Stops For Permit 16041090
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-26 Cont ID  
Sent By cthroop Date 2016-05-26 Time 16:16 Rev Time 0.00
Received By cthroop Date 2016-05-26 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By cthroop Date 2016-05-06 Time 14:55 Rev Time 0.00
Received By cthroop Date 2016-05-06 Time 10:28 Sent To  
Notes
2016-05-06 15:03:361ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-7918
 [email protected]
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
  
 1. FBC-107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS - THE CONSTRUCTION DOCUMENTS
 SHALL BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL
 WHERE REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE, THEN HE OR
 SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL TO SAID
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA, AS
 REQUIRED BY FLORIDA STATUTE.
 FAC 61G1-16.004 - A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS AND
 SPECIFICATION IDENTIFICATION SHEETS THAT ARE REQUIRED
 TO BE SIGNED AND SEALED. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED.
 (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO
 BE A CORPORATION, LIMITED LIABILITY COMPANY,
 PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME,
 OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN
 HIS OR HER OWN NAME.
  
 2. SHEET A103 "PERGOLA" HAS BEEN REMOVED. SEPERATE
 PERMIT REQUIRED.
 3. ELECTRICAL PERMIT REQUIRED.
 4. PROVIDE "STANDARD METHOD OF TEST FOR SURFACE BURNING
 CHARACTERISTICS OF BUILDING MATERIALS" PER ASTM E-84
 FOR ALL FLOORING MATERIALS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-12 Cont ID  
Sent By mvaldes Date 2016-05-12 Time 18:23 Rev Time 0.00
Received By mvaldes Date 2016-05-12 Time 17:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By mvaldes Date 2016-04-28 Time 14:57 Rev Time 0.00
Received By mvaldes Date 2016-04-28 Time 13:51 Sent To  
Notes
2016-04-28 15:08:44JOB PERMIT NUMBER: 16041090
 JOB ADDRESS: 2455 METROCENTRE BLVD
 WEST PALM BEACH FLORIDA
 DATE: APRIL 28 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - SHEET A-101A FBC-E C405.7.3 VOLTAGE DROP. FEEDERS &
 CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A
 MAXIMUM OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE
 SIZED FOR A MAXIMUM OF 3% VOLTAGE DROP. ( RUN FROM
 PANEL L1A TO PERGOLA ) EXTERIOR WIRING INSULATION MUST
 BE THWN.
 - SHEET A-101B DESCRIBE TRENCH DEPTH FOR FLOOR BOXES
 DIVIDING 120 V AND LOW VOLTAGE CAT 6 IN ACCORDANCE WITH
 TABLE 300.5 OF THE NEC.
 - SHEET A-102 F PADDLE FAN BOXES MUST BE RATED 70 LB
 AND CEILING PENDANT BOXES RATED 50 LB , NEC 314.27 D ,
 314.27 A.
 - MAKE A NOTE THAT NEW LIGHTING BEING INSTALLED SHALL
 COMPLY WITH FLORIDA ENERGY CODE SECTION C 405 MANDATORY
 LIGHTING CONTROLS.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-17 Cont ID  
Sent By pleduc Date 2016-05-17 Time   Rev Time 0.00
Received By pleduc Date 2016-05-17 Time 08:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By pleduc Date 2016-05-04 Time   Rev Time 0.00
Received By pleduc Date 2016-05-04 Time 11:02 Sent To  
Notes
2016-05-04 11:23:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHET A 0.00 AND ALL OTHER APPLICABLE SHEETS, THERE
 IS NO REFERNCE TO THE REVIEW AND/OR COMPLIANCE WITH THE
 APPLICABLE FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITIONS OF NFPA 1 AND NFPA 101 INCLUDING, BUT
 NOT LIMITED TO, NFPA 101, CHAPTER 29 EXISTING HOTELS
 AND DORMITORIES AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) THERE IS NO REFERENCE TO IF THE BUILDING WILL BE
 OCCUPIED DURING THE CONSTRUCTION PERIOD. WILL THE WORK
 BE DONE IN PHASES, SEPARATE FLOORS? WILL SOME OF THE
 FLOOORS NEED TO BE INSPECTED, FINALED AND OCCUPIED
 BEFORE OTHER FLOORS ARE STARTED?
  
 PLEASE PROVIDE INFORMATION AND INDICATIONS.
  
 3) IF THE BUILDING WILL BE OCCUPIED, A LIFE SAFETY PLAN
 SHALL BE PROVIDED TO ENSURE PROPER EGRESS.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN. IF PHASED, PLEASE
 PROVIDE THE APPLICABLE PHASED LIFE SAFETY PLANS.
  
 4) PLEASE PROVIDE INDICATION THAT ALL LIFE SAFETY
 SYSTEMS; FIRE ALARM, FIRE SPRINKLER, FIRE PUMP AND
 INCLUDING THE EMRGENCY GENERATOR, IF EXISTING, ETC, AND
 ALL EQUIPMENT SHALL REMAIN ACTIVE DURING ALL
 CONSTRUCTION.
  
 5) PROVIDE INDICATIONS THAT THE FIRE ALARM AND FIRE
 SPRINKLER WORK SHALL BE COMPLETED BY CERTIFIED LIFE
 SAFETY CONTRACTORS UNDER SEPARATE SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-26 Cont ID  
Sent By cthroop Date 2016-05-26 Time 16:16 Rev Time 0.00
Received By cthroop Date 2016-05-11 Time 14:43 Sent To  
Notes
2016-05-11 14:43:34C34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-06 Cont ID  
Sent By cthroop Date 2016-05-06 Time 14:54 Rev Time 0.00
Received By cthroop Date 2016-04-25 Time 09:28 Sent To  
Notes
2016-04-26 09:26:05C31

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-26 Cont ID  
Sent By ajones Date 2016-05-26 Time 10:37 Rev Time 0.00
Received By ajones Date 2016-05-26 Time 10:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-06 Cont ID  
Sent By ajones Date 2016-05-06 Time 10:40 Rev Time 0.00
Received By ajones Date 2016-05-06 Time 10:40 Sent To  
Notes
***NONE***