Plan Review Details - Permit 16041090
| Plan Review Stops For Permit 16041090 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-05-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-05-26 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-05-26 |
Time |
16:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-05-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-05-06 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-05-06 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2016-05-06 15:03:36 | 1ST REVIEW: FBC 2014 5TH ED | | | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-7918 | | | [email protected] | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | | | | 1. FBC-107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF | | | CONSTRUCTION DOCUMENTS - THE CONSTRUCTION DOCUMENTS | | | SHALL BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL | | | WHERE REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15 | | | FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA | | | STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE, THEN HE OR | | | SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL TO SAID | | | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA, AS | | | REQUIRED BY FLORIDA STATUTE. | | | FAC 61G1-16.004 - A TITLE BLOCK MUST APPEAR ON ALL | | | ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS AND | | | SPECIFICATION IDENTIFICATION SHEETS THAT ARE REQUIRED | | | TO BE SIGNED AND SEALED. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION | | | NUMBER OF THE PERSON SEALING THE DOCUMENT. | | | (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE | | | REVISED. | | | (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO | | | BE A CORPORATION, LIMITED LIABILITY COMPANY, | | | PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME, | | | OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN | | | HIS OR HER OWN NAME. | | | | | | 2. SHEET A103 "PERGOLA" HAS BEEN REMOVED. SEPERATE | | | PERMIT REQUIRED. | | | 3. ELECTRICAL PERMIT REQUIRED. | | | 4. PROVIDE "STANDARD METHOD OF TEST FOR SURFACE BURNING | | | CHARACTERISTICS OF BUILDING MATERIALS" PER ASTM E-84 | | | FOR ALL FLOORING MATERIALS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-05-12 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-12 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-05-12 |
Time |
17:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-04-28 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-04-28 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-04-28 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2016-04-28 15:08:44 | JOB PERMIT NUMBER: 16041090 | | | JOB ADDRESS: 2455 METROCENTRE BLVD | | | WEST PALM BEACH FLORIDA | | | DATE: APRIL 28 2016 | | | ELECTRICAL PLAN REVIEW COMMENTS | | | | | | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF | | | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, | | | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST | | | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. | | | | | | - SHEET A-101A FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & | | | CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A | | | MAXIMUM OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE | | | SIZED FOR A MAXIMUM OF 3% VOLTAGE DROP. ( RUN FROM | | | PANEL L1A TO PERGOLA ) EXTERIOR WIRING INSULATION MUST | | | BE THWN. | | | - SHEET A-101B DESCRIBE TRENCH DEPTH FOR FLOOR BOXES | | | DIVIDING 120 V AND LOW VOLTAGE CAT 6 IN ACCORDANCE WITH | | | TABLE 300.5 OF THE NEC. | | | - SHEET A-102 F PADDLE FAN BOXES MUST BE RATED 70 LB | | | AND CEILING PENDANT BOXES RATED 50 LB , NEC 314.27 D , | | | 314.27 A. | | | - MAKE A NOTE THAT NEW LIGHTING BEING INSTALLED SHALL | | | COMPLY WITH FLORIDA ENERGY CODE SECTION C 405 MANDATORY | | | LIGHTING CONTROLS. | | | | | | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | | MENTIONED DEFICIENCIES. | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD | | | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE | | | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-05-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-05-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-05-17 |
Time |
08:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-05-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-05-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-05-04 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2016-05-04 11:23:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHET A 0.00 AND ALL OTHER APPLICABLE SHEETS, THERE | | | IS NO REFERNCE TO THE REVIEW AND/OR COMPLIANCE WITH THE | | | APPLICABLE FIRE CODE. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITIONS OF NFPA 1 AND NFPA 101 INCLUDING, BUT | | | NOT LIMITED TO, NFPA 101, CHAPTER 29 EXISTING HOTELS | | | AND DORMITORIES AND ALL OTHER APPLICABLE CODES OR | | | STANDARDS. | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2010 EDITION. | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2010 EDITION. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2009 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | 2) THERE IS NO REFERENCE TO IF THE BUILDING WILL BE | | | OCCUPIED DURING THE CONSTRUCTION PERIOD. WILL THE WORK | | | BE DONE IN PHASES, SEPARATE FLOORS? WILL SOME OF THE | | | FLOOORS NEED TO BE INSPECTED, FINALED AND OCCUPIED | | | BEFORE OTHER FLOORS ARE STARTED? | | | | | | PLEASE PROVIDE INFORMATION AND INDICATIONS. | | | | | | 3) IF THE BUILDING WILL BE OCCUPIED, A LIFE SAFETY PLAN | | | SHALL BE PROVIDED TO ENSURE PROPER EGRESS. | | | | | | PLEASE PROVIDE A LIFE SAFETY PLAN. IF PHASED, PLEASE | | | PROVIDE THE APPLICABLE PHASED LIFE SAFETY PLANS. | | | | | | 4) PLEASE PROVIDE INDICATION THAT ALL LIFE SAFETY | | | SYSTEMS; FIRE ALARM, FIRE SPRINKLER, FIRE PUMP AND | | | INCLUDING THE EMRGENCY GENERATOR, IF EXISTING, ETC, AND | | | ALL EQUIPMENT SHALL REMAIN ACTIVE DURING ALL | | | CONSTRUCTION. | | | | | | 5) PROVIDE INDICATIONS THAT THE FIRE ALARM AND FIRE | | | SPRINKLER WORK SHALL BE COMPLETED BY CERTIFIED LIFE | | | SAFETY CONTRACTORS UNDER SEPARATE SHOP DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-05-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-05-26 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-05-11 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-05-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-05-06 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-04-25 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-05-26 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2016-05-26 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2016-05-26 |
Time |
10:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2016-05-06 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2016-05-06 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2016-05-06 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
|