Plan Review Details - Permit 16041065
Plan Review Stops For Permit 16041065
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 13:29 Rev Time  
Received By jwitmer Date 2016-05-07 Time 12:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-05-05 Cont ID  
Sent By albarran Date 2016-05-05 Time 10:35 Rev Time 0.00
Received By albarran Date 2016-05-05 Time 09:55 Sent To  
Notes
2016-05-05 10:36:56PASSED ELECTRICAL REVIEW AND ADDED SMOKE DETECTOR
 COMPLIANCE NOTE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-28 Cont ID  
Sent By pleduc Date 2016-04-28 Time   Rev Time 0.00
Received By pleduc Date 2016-04-28 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-17 Cont ID  
Sent By ccole Date 2016-05-17 Time 11:42 Rev Time 0.00
Received By ccole Date 2016-05-16 Time 13:54 Sent To  
Notes
2016-05-16 13:54:23RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2016-04-22 Time 12:36 Sent To  
Notes
2016-04-25 12:37:09B33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-07 Cont ID  
Sent By jwitmer Date 2016-05-07 Time 13:11 Rev Time  
Received By jwitmer Date 2016-05-07 Time 12:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-17 Cont ID  
Sent By ccole Date 2016-05-17 Time 11:42 Rev Time 0.00
Received By ccole Date 2016-05-17 Time 11:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By ccole Date 2016-05-05 Time 10:15 Rev Time 0.00
Received By ccole Date 2016-05-05 Time 10:15 Sent To  
Notes
2016-05-05 10:29:401ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16041065
 5/5/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING
 CODE, ALTERED EXISTING SYSTEMS:
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
 PLEASE PROVIDE MINIMUM VENTILATION CALCULATIONS ON THE
 PLAN PER TABLE 403.3 FBC-14 MECHANICAL.
 2) SOME OF THE VAV BOXES SHOWN HAVE TO BE RELOCATED
 FROM ABOVE THE LIGHTING FIXTURES TO ALLOW FOR CLEAR
 ACCESS FOR MAINTENANCE AND REPLACEMENT- SEE SECTION
 306.9 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-02 Cont ID  
Sent By gearl Date 2016-05-02 Time 14:44 Rev Time 0.00
Received By gearl Date 2016-05-02 Time 14:44 Sent To  
Notes
2016-05-02 14:47:44 
  
  
  
 1. FIELD VERTIFTY ROUGH IN OF ACCESSIBLE BATHROOMS
  
 GEORGE EARL- PLUMBING PLANS REVIEWER