Plan Review Details - Permit 16041056
Plan Review Stops For Permit 16041056
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-09-15 Cont ID  
Sent By jwitmer Date 2016-09-15 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2016-09-14 Time 16:47 Sent To  
Notes
2016-09-15 16:37:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041056
 ADD: 701 VILLAGE BLVD. SUITES: 201-202
 CONT: GREAT PATRIOT CONSTRUCTION
 TEL: 561-241-4765
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: THURS. SEPT. 15/ 2016
 ACTION: BUILDING PROVISO
  
 ROOFING PROVISO:
 CONTRACTOR SUBMITTED A FLORIDA APPROVAL # FL7804-R9
 ENTEGRA ROOF TILE.
 LIMITATION 5.4 THIS APPROVAL DOES NOT PROVIDE
 ATTACHMENT METHOD FOR MORTAR SET TILE OR ADHESIVE-SET
 ADHESIVE APPLICATIONS PLEASE PROVIDE PRODUCT APPROVALS
 FOR MORTAR SET TILE OR ADHESIVE-SET ADHESIVE
 APPLICATION.
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-08-25 Cont ID  
Sent By jwitmer Date 2016-08-25 Time 08:20 Rev Time 0.00
Received By jwitmer Date 2016-08-25 Time 06:41 Sent To  
Notes
2016-08-25 08:20:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041056
 ADD: 701 VILLAGE BLVD. SUITES: 201-202
 CONT: GREAT PATRIOT CONSTRUCTION
 TEL: 561-241-4765
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: THURS. AUGUST. 25/2016
 ACTION: DENIED
  
 1) COVERSHEET/ 01-A:
  
 1A-E) COMPLIED.
  
 1F)4TH REQUEST. UNDER THE HEADING OF EARTHWORK THERE IS
 NO REQUIREMENT FOR SOILS TESTING. THIS AREA IS IN A
 QUESTIONABLE SOILS ZONE.
 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 2) COMPLIED.
  
 3) 4TH REQUEST. THE YKK AP AMERICA DOES NOT HAVE
 CURRENT PRODUCTS APPROVALS FOR THE STOREFRONT WINDOW
 SYSTEM NOR THE STOREFRONT DOOR SYSTEM. IF SO PLEASE
 SUPPLY THE FLORIDA APPROVAL COVERSHEETS.
  
 WINDOW SCHEDULE / TYPE 01 INDICATES THIS TYPE WINDOW TO
 BE A SLIDER TYPE WINDOW WHEREAS A SINGLE HUNG APPROVAL
 WAS SUBMITTED.
  
 ROOF TILE FLORIDA APPROVAL FL7804-R9 SUBMITTED ON PAGE
 6 OF 6 THE INSTALLATION TYPES MECHANICALLY, MORTAR OR
 ADHESIVE- SET TILE NOR HIP & RIDGE TILE WERE INCLUDED
 IN THIS SUBMITTAL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) COMPLIED.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-07-20 Cont ID  
Sent By jwitmer Date 2016-07-20 Time 10:05 Rev Time 0.00
Received By jwitmer Date 2016-07-20 Time 08:45 Sent To  
Notes
2016-07-20 10:06:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041056
 ADD: 701 VILLAGE BLVD. SUITES: 201-202
 CONT: GREAT PATRIOT CONSTRUCTION
 TEL: 561-241-4765
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JULY 20/2016
 ACTION: DENIED
  
 1) COVERSHEET/ 01-A:
  
 1A-E) COMPLIED.
  
 1F) UNDER THE HEADING OF EARTHWORK THERE IS NO
 REQUIREMENT FOR SOILS TESTING. THIS AREA IS IN A
 QUESTIONABLE SOILS ZONE.
 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 2) COMPLIED.
  
 3) THE YKK AP AMERICA DOES NOT HAVE CURENT PRODCT
 APPROVALS FOR THE STOREFRONT WINDOW SYSTEM NOR THE
 STOREFRONT DOOR SYSTEM.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 ( E ) SHUTTERS THE FABRIC STORM SYSTEM HAS AN EXPIRED
 NOA. NEED TO SUBMIT THE WHOLE REPORT.
  
 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5A) COMPLIED.
  
 5B) THE OTHER ISSUE IS THE CONNECTION OF THE I-BEAM TO
 THE STEEL COLUMN, THE PLANS INDICATE A CONTINUOUS WELD,
 BUT THE TYPE OF WELD NOT PROVIDED. THIS WILL BE A SITE
 CONNECTION, PLEASE HAVE THE WELDERS CERTIFICATE ON SITE
 FOR INSPECTOR AT TIME OF INSPECTION. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED. THIS CONNECTION
 WILL BE PART OF THE MWFRS (MAIN WIND FORCE RESISTING
 SYSTEM.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-17 Cont ID  
Sent By jwitmer Date 2016-05-17 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2016-05-17 Time 07:29 Sent To  
Notes
2016-05-17 13:34:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041056
 ADD: 701 VILLAGE BLVD. SUITES: 201-202
 CONT: GREAT PATRIOT CONSTRUCTION
 TEL: 561-241-4765
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 17/2016
 ACTION: DENIED
  
 1) COVERSHEET/ 01-A:
  
 1A) UPPER RIGHT HAND CORNER OF THE PLANS UNDER THE
 HEADING OF NOTES THE BUILDING CLASSIFICATION IS
 INDICATES AS ASSEMBLY AND THE 2ND LINE THE OCCUPANCY
 PER THE FBC CHAPTER 6 ASSEMBLY (NON-SEPARATED).
 PLEASE NOTE THE DESIGNER OF RECORD HAS NOT DECLARED
 WHAT CLASSIFICATION TYPE OF OCCUPANCY, THIS APPEARS TO
 BE AN OCCUPANCY TYPE A2, SEE 2014 FBC-B 303.3.
  
 THE OTHER ISSUE DECLARING ASSEMBLY NON-SEPARATED PER
 CHAPTER 6 WOULD BE THE WRONG CODE SECTION FOR
 NON-SEPARATED USE. THE OTHER OCCUPANCY HAS NOT BEEN
 DECLARED.
  
 SEE 2014 FBC-B 508.3.1 OCCUPANCY CLASSIFICATION.
 NONSEPARATED OCCUPANCIES SHALL BE INDIVIDUALLY
 CLASSIFIED IN ACCORDANCE WITH SECTION 302.1. THE
 REQUIREMENTS OF THIS CODE SHALL APPLY TO EACH PORTION
 OF THE BUILDING BASED ON THE OCCUPANCY CLASSIFICATION
 OF THAT SPACE. IN ADDITION, THE MOST RESTRICTIVE
 PROVISIONS OF CHAPTER 9 WHICH APPLY TO THE NONSEPARATED
 OCCUPANCIES SHALL APPLY TO THE TOTAL NONSEPARATED
 OCCUPANCY AREA.
  
 1B) UNDER BOTH HEADINGS OF NOTES AND LOAD SCHEDULES,
 WIND DESIGN THE PLANS WERE DESIGNED TO A WIND EXPOSURE
 OF ?B?. TO BOTH THE WEST AND EAST THERE ARE VECTORS
 THAT MEET THE QUALIFICATIONS FOR A SURFACE ROUGHNESS
 C.FBC-B 1609.4.2. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 FEET
 (9144 MM). THIS CATEGORY INCLUDES FLAT OPEN COUNTRY,
 AND GRASSLANDS. THIS SURFACE ROUGHNESS SHALL ALSO APPLY
 TO ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET (30 M)
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) IN THE UPWIND DIRECTION AND A WIDTH
 GREATER THAN 150 FEET (46 M). PLEASE UPDATE THE WIND
 EXPOSURE TO AN C EXPOSURE AS WELL AS UPDATE THE
 PRESSURES FOR ALL BUILDING WIND ZONES 1-5, ALL ARE LOW,
 PLEASE ALSO REVIEW TABLE 1609.7(2) ADJUSTMENT FACTOR
 FOR BUILDING HEIGHT AND EXPOSURE .
  
 1C) UNDER THE HEADING OF LOAD SCHEDULE / WIND THE
 BUILDING RISK CATEGORY WAS HAND WRITTEN IN PLEASE
 PROVIDE THE CORRECT RISK FACTOR FOR THIS BUILDING.
 TABLE 1604.5.
  
 1D) UNDER THE HEADING NOTES, THE 2014 FBC-B WAS THE
 DOCUMENT THE PLANS WERE TO BE DESIGNED TO, PLEASE BE
 AWARE THE 2014 EXISTING BUILDING CODE IS THE OTHER CODE
 THIS REVIEW WILL OCCUR UNDER. THE DESIGNER OF RECORD
 HAS NOT INDICATED TO WHAT METHOD CODE COMPLIANCE WAS
 CONSIDERED. 2014 EXISTING BUILDING CODE 301.1 GENERAL.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 301.1.1
 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER. WHERE THIS CODE
 REQUIRES CONSIDERATION OF THE SEISMIC FORCE-RESISTING
 SYSTEM OF AN EXISTING BUILDING SUBJECT TO REPAIR,
 ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR RELOCATION
 OF EXISTING BUILDINGS, THE SEISMIC EVALUATION AND
 DESIGN SHALL BE BASED ON SECTION 301.1.4 REGARDLESS OF
 WHICH COMPLIANCE METHOD IS USED.
  
 1E) THE SITE AND BUILDING DATA LIST 3,427 SQ. FT. IN
 THIS BAY. SHEET 02-A LIST 17,724 SQ. FT. IN THE
 BUILDING, PLEASE PROVIDE WHEN TABLE 503 FOR AN A2
 OCCUPANCY, BUILDING TYPE III-B, HOW CODE COMPLIANCE WAS
 ACHIEVED WHEN ONLY 9,500 SQ. FT. IS ALLOWED? THE PLAN
 DOES NOT INDICATE THAT ANY INCREASES WERE TAKEN!
 1F) UNDER THE HEADING OF EARTHWORK THERE IS NO
 REQUIREMENT FOR SOILS TESTING. THIS AREA IS IN A
 QUESTIONABLE SOILS ZONE.
 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 2)SHEET 18F APPEARS TO BE THE LIFE SAFETY SHEET. PLEASE
 PROVIDE THE DOORWAYS THAT ARE TO BE THE MEANS OF
 EGRESS. SHEET 09-A THE ELEVATIONS APPEAR TO HAVE A SLAT
 SYSTEM OVER THE OPENINGS IN THE WALLS AND THE ONLY
 EGRESS FROM THE NEW ADDITION IS BACK THROUGH THE
 EXISTING BUILDING. SHOW THE OCCUPANT LOAD FOR THE
 EXISTING TENANT SPACE AS WELL AS THE ADDITION SHOW
 COMPLIANCE WITH;
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD NOTE RECEPTION IS NOT BUSINESS, SEE
 TABLE 1004.1.2 STANDING ONLY 5 NET
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 MINIMUM CONSTRUCTION TYPE
  
  
 3) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 ( E ) SHUTTERS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5A) SHEET 07-A & 11-A BOTH SHOW THE USE OF W12X26
 I-BEAMS. SHEET 11-A INDICATES INFILL WITH (2) 2X12S AND
 ? INCH BOLTS. THE BOLT SPACING HAS NOT BEEN PROVIDED
 NOR THE DIAMETER OF THE HOLE IN THE STEEL.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5B) THE OTHER ISSUE IS THE CONNECTION OF THE I-BEAM TO
 THE STEEL COLUMN, THE PLANS INDICATE A CONTINUOUS WELD,
 BUT THE TYPE OF WELD NOT PROVIDED. THIS WILL BE A SITE
 CONNECTION, PLEASE HAVE THE WELDERS CERTIFICATE ON SITE
 FOR INSPECTOR AT TIME OF INSPECTION. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
 THIS CONNECTION WILL BE PART OF THE MWFRS (MAIN WIND
 FORCE RESISTING SYSTEM.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By gearl Date   Time 11:22 Rev Time 0.00
Received By jwitmer Date 2016-05-17 Time 07:28 Sent To  
Notes
2016-05-05 10:46:03WRONG CODE APPLIED IN SYSTEM
2016-05-03 11:22:02 
  
  
 1. NEED VENT FOR URINAL FBC PLUMBING 901.2
  
 2. NEED TO SHOW ON PLANS WHICH VENT IS GOING THRU ROOF
  
  
  
 NOTE THIS JOB WILL NEED A GAS PERMIT
  
  
 GEORGE EARL PLUMBING PLANS REVIEWER 0013B

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-09-28 Cont ID  
Sent By vperez Date 2016-09-28 Time 11:42 Rev Time 0.00
Received By vperez Date 2016-09-28 Time 11:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-08-29 Cont ID  
Sent By vperez Date 2016-08-29 Time 13:06 Rev Time 0.00
Received By vperez Date 2016-08-29 Time 13:06 Sent To  
Notes
2016-08-29 13:08:463RD ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS:
  
 1. PLEASE CLARIFY SHEET 13-E SUBMITTED REFLECTING PANEL
 SCHEDULES AND SERVICE ONE-LINE, IS THIS INSERT
 INCORRECT OR IS IT PART OF CONSTRUCTION DOCUMENTS. ONE
 SET HAS IT INCLUDED THE OTHER SET DOESNT. CLARIFY SHEET
 IS NOT SIGNED AND SEALED BY EOR. FBC 107.3.5
 2. PRIOR COMMENTS ADDRESSED.
 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-14 Cont ID  
Sent By vperez Date 2016-07-14 Time 07:50 Rev Time 0.00
Received By vperez Date 2016-07-14 Time 07:50 Sent To  
Notes
2016-07-14 07:53:192ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY SHEET 13-E SUBMITTED REFLECTING PANEL
 SCHEDULES AND SERVICE ONE-LINE, IS THIS INSERT
 INCORRECT OR IS IT PART OF CONSTRUCTION DOCUMENTS.
 SHEET IS NOT SIGNED AND SEALED BY EOR. FBC 107.3.5
 2. PRIOR COMMENTS ADDRESSED.
 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By vperez Date 2016-05-05 Time 07:07 Rev Time 0.00
Received By vperez Date 2016-05-04 Time 15:11 Sent To  
Notes
2016-05-05 07:08:06INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE REFERENCE ALL APPLICABLE FBC ENERGY
 CONSERVATION2014 5TH EDITION C405 REQUIREMENTS RELATED
 TO AUTOMATIC MEANS OF CONTROL FOR ALL LIGHTING.
 2. STATE ON DRAWINGS C405.7.4 COMPLETION
 REQUIREMENTS-(DRAWINGS AND MANUALS. SEE VERBIAGE IN THE
 CODE.
 3. PROVIDE A SHOW ON PLANS THE VOLTAGE DROP
 CALCULATIONS FOR FEEDER AND BRANCH CIRCUITS PER FBC EC
 C405.7 ELECTRICAL POWER MANDATORY
 4. ADDRESS ALL AND ANY FIRE DEPARTMENT COMMENTS RELATED
 TO THE ELECTRICAL SCOPE.
 5. LABEL THE ONE-LINE SERVICE RISER MAINS TO BE RATED
 FOR SERVICE ENTRANCE. A NOTE WILL SUFFICE.
 6. PROVIDE A GENERAL NOTE TO INDICATE NEC 110.16 ARC
 FLASH HAZARD WARNINGS- A NOTE WILL SUFFICE.
 7. PER NEC 110.24 A AND B. INDICATE ON PLANS REQUIRED
 FIELD MARKING OF THE AVAILABLE FAULT CURRENT DUE TO
 MODIFICATIONS.
 8. PLEASE CORRECT SERVICE CONDUCTORS SHOWN ON ONE-LINE
 RISER DIAGRAM FOR 225A SERVICE AT 2/0, SHOULD REFLECT
 4/0 PER TABLE OF AMPACITIES NEC 310.15B16
 9. SHOW SIZE OF THE GROUNDING ELECTRODE CONDUCTOR PER
 NEC 250.66
 10. PROVIDE NEUTRAL CALCULATIONS AS THE NEUTRAL IS
 BEING REDUCED AS SHOWN SERVICE CONDUCTORS. NEC 220.61B
 11. SHOW ON FLOOR PLAN THE LOCATION OF THE SERVICE
 EQUIPMENT. FBC 107.3.5
 12. PER NEC 230.2 YOU ARE SHOWING MULTIPLE SERVICES.
 PROVIDE A NOTE TO INDICATE PROPER SIGNAGE FOR FIRST
 RESPONDERS WITH IDENTIFICATION PER NEC 230.2E
 13. CLARIFY THE LOCATION OF THE MAIN CIRCUIT BREAKER A
 AND B. IS THE CONDUIT ROUTED UNDERGROUND? MAINS TO
 LOCATED AT THE NEAREST POINT OF ENTRANCE PER NEC 230
 14. CLARIFY SHOW WINDOW RECEPTACLE REQUIREMENTS FOR
 COMMERCIAL BUILDINGS PER NEC 220.43 NEC 210.62
 15. LABEL ON FLOOR PLAN ALL RECEPTACLE OUTLETS AT THE
 TERRACE LOCATION TO BE GFCI PROTECTED AND W/P PER NEC
 210.8B
 16. BAR AREA RECEPTACLES AND RECEPTACLE WITHIN 6FT OF
 MOP SINK TO LABELED GFCI PROTECTED. NEC 210.8B7
 17. DRINKING FOUNTAIN CIRCUIT A-8 TO BE A DEDICATED
 CIRCUIT AND LABELED GFCI PROTECTED. OTHER RECEPTACLES
 ON CIRCUIT A-8 TO BE REASSIGNED WITH OTHER CIRCUIT
 DESIGNATION. NEC 422.52
 18. DELETE GENERAL NOTES ON SHEETS 14 AND 15E THAT ARE
 NOT APPLICABLE TO THIS PROJECT. RESIDENTIAL NOTES.
 19. SHOW REQUIRED EXIT AND EMERGENCY LIGHTING FOR AREAS
 AND EGRESS DOORS. FBC 107.3.5
 20. SEPARATE PERMITS REQUIRED FOR ALL LOW VOLTAGE
 SYSTEMS AND FIRE ALARM. PROVIDE A NOTE
 21. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL.
 PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-08-18 Cont ID  
Sent By pleduc Date 2016-08-18 Time   Rev Time 0.00
Received By pleduc Date 2016-08-17 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-14 Cont ID  
Sent By pleduc Date 2016-07-14 Time   Rev Time 0.00
Received By pleduc Date 2016-07-14 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By pleduc Date 2016-04-28 Time   Rev Time 0.00
Received By pleduc Date 2016-04-27 Time 15:02 Sent To  
Notes
2016-04-27 17:00:51THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET 08 A - THERE IS NOTE INDICATING A FIREPIT BY
 SPECIALIST.
  
 THE FIREPIT SHALL BE SUBMITTED UNDER SEPARATE SHOP
 DRAWINGS IN COMPLIANCE WITH NFPA 1, CHAPTER 10,
  
 10.11.8 INCINERATORS AND FIREPLACES.
 10.11.8.1 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT
 BARBECUES, AND GRILLS SHALL NOT BE BUILT, INSTALLED, OR
 MAINTAINED WITHOUT PRIOR APPROVAL OF THE AHJ.
 10.11.8.2 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT
 BARBECUES, AND GRILLS SHALL BE MAINTAINED IN GOOD
 REPAIR AND IN A SAFE CONDITION AT ALL TIMES.
 10.11.8.3 OPENINGS IN INCINERATORS, OUTDOOR FIREPLACES,
 PERMANENT BARBECUES, AND GRILLS SHALL BE PROVIDED WITH
 AN APPROVED SPARK ARRESTER, SCREEN, OR DOOR.
 10.11.9 OPEN-FLAME DEVICES.
 10.11.9.1* WELDING TORCHES, TAR POTS, DECORATIVE
 TORCHES, AND OTHER DEVICES, MACHINES, OR PROCESSES
 LIABLE TO START OR CAUSE FIRE SHALL NOT BE OPERATED OR
 USED IN OR UPON ANY AREAS, EXCEPT BY PERMIT FROM THE
 AHJ.
  
 THE FLAME OF THE PIT SHALL BE PROTECTED AGAINST
 ACCIDENTAL AND/OR INTENTIONAL USE AND/OR MISUSE.
  
 IT IS IMPERATIVE FOR THE APPROVAL OF THIS DEVICE TO BE
 INSTALLED, SOMESORT OF DESIGN FEATURE SHALL BE
 INSTALLED TO PREVENT FLAME CONTACT WITH THE GENRAL
 PUBLIC.
  
 2) SHEET 18 F - THERE IS A NOTE INDICATING FIRE
 SPRINKLER BY SPECIALIST.
  
 ANY AND ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 3) SHEET 18 F - THE EXIT SIGN IN THE MIDDLE OF THE
 INTERIOR WALL SHALL BE MOVED TO THE AREA OF THE DOOR
 WAY LEADING TO THE CORRIDOR.
  
 4) SHEET 18 F - THERE ARE NO EXIT SIGNS LOCATED IN THE
 TERRACE AREA. ADD AN EXIT SIGN AT EACH END OF THE
 TERRACE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-28 Cont ID  
Sent By ccole Date 2016-09-28 Time 16:05 Rev Time 0.00
Received By ccole Date 2016-09-23 Time 11:13 Sent To  
Notes
2016-09-26 11:14:00RESUB ROUTED TO AWOOTEN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-29 Cont ID  
Sent By cpuell Date 2016-08-29 Time 16:57 Rev Time 0.00
Received By cpuell Date 2016-08-11 Time 10:19 Sent To  
Notes
2016-08-12 10:19:54C25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-02 Cont ID  
Sent By cpuell Date 2016-08-02 Time 10:03 Rev Time 0.00
Received By cpuell Date 2016-07-08 Time 14:33 Sent To  
Notes
2016-07-08 14:34:03C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-17 Cont ID  
Sent By jwitmer Date 2016-05-17 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2016-04-22 Time 11:55 Sent To  
Notes
2016-04-25 11:55:45C25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2016-09-14 Cont ID  
Sent By jwitmer Date 2016-09-14 Time   Rev Time 0.00
Received By jwitmer Date 2016-09-14 Time   Sent To  
Notes
2016-09-14 16:46:34P. B. COUNTY IMPACT FEE OFFICE
 TRACKING NO. MU-2016-022577-0000
 RECEIPT NO. 2016-0913-298
 FEES: $7,038.83

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-08-25 Cont ID  
Sent By jwitmer Date 2016-08-25 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2016-08-25 Time 06:44 Sent To  
Notes
2016-08-25 06:44:48IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-05-17 Cont ID  
Sent By   Date 2016-05-17 Time   Rev Time 0.00
Received By   Date 2016-05-17 Time   Sent To  
Notes
2016-08-25 06:44:16IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-17 Cont ID  
Sent By jwitmer Date 2016-05-17 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2016-05-17 Time 13:30 Sent To  
Notes
2016-05-17 13:31:14IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-09-28 Cont ID  
Sent By ccole Date 2016-09-28 Time 11:06 Rev Time 0.00
Received By ccole Date 2016-09-28 Time 11:06 Sent To  
Notes
2016-09-28 11:12:55MECHANICAL PROVISO
 PERMIT #16041056
 9/28/16
  
 THE CURRENT MECHANICAL PLANS ARE APPROVED WITH A
 CONTINGENCY FOR A REVISION TO BE SUBMITTED TO CORRECT A
 DEFICIENCY IN THE SMOKING LOUNGE EXHAUST VENTILATION
 SYSTEM.
 AS PREVIOUSLY NOTED IN PRIOR REVIEWS, RECIRCULATION OF
 AIR IN THE LOUNGE AREA IS PROHIBITED PER TABLE 403.3
 FOOTNOTE B, AND SECTION 403.2.1 ITEM 3. ALL AIR
 SUPPLIED TO SUCH AREAS SHALL BE EXHAUSTED, HOWEVER THE
 PLAN INDICATES ONLY 2700 CFMS OF THE 3000 CFMS SUPPLED
 ARE BEING EXHAUSTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-08-24 Cont ID  
Sent By ccole Date 2016-08-24 Time 16:02 Rev Time 0.00
Received By ccole Date 2016-08-24 Time 16:01 Sent To  
Notes
2016-08-24 16:22:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16041056
 8/24/16
  
 1) ENERGY FORM C402 MAY BE USED FOR ALTERATIONS,
 RENOVATIONS, AND BUILDING SYSTEMS, HOWEVER THE PROJECT
 IS A CHANGE OF OCCUPANCY- SEE SECTION C101.5.1.1 FBC-14
 ENERGY CONSERVATION.
  
 2) REFER TO TABLE 403.3 FOOTNOTE B, AND SECTION
 403.2.1(3)- RECIRCULATION OF AIR IN THE SMOKING LOUNGE
 IS PROHIBITED. THE CALCULATIONS INDICATE COMPLIANCE,
 HOWEVER ERV'S WILL TYPICALLY LEAK A SMALL PERCENTAGE OF
 RETURN AIR BACK INTO THE SUPPLY AIRSTREAM WHICH IS
 LIMITED TO 10% PER SECTION 514.4. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS INDICATING THE LEAKAGE
 RATE OF THE ERV.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-18 Cont ID  
Sent By ccole Date 2016-07-18 Time 09:32 Rev Time 0.00
Received By ccole Date 2016-07-18 Time 08:37 Sent To  
Notes
2016-07-18 09:44:282ND REVIEW MECHANICAL
 PERMIT #16041056
 7/18/16
  
 1) THE RESUBMITTED PLANS INDICATE A CHANGE OF OCCUPANCY
 TO A2- PLEASE SUBMIT ENERGY CALCULATIONS PER SECTION
 C101.4.4 AND C401.2 FBC-14 ENERGY CONSERVATION.
  
 2) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, SUBMIT AC
 COOLING AND HEATING CALCULATIONS PER SECTION 403.2.1
 FBC-14 ENERGY CONSERVATION.
  
 3) M-1: THE VENTILATION CALCULATION FOR THE LOUNGE AREA
 BASED ON 45 PERSONS IS INCORRECT. THE OCCUPANT DENSITY
 PER TABLE 403.3 IS BASED ON 70 PERSONS PER SQ. FT.
 REFER TO SHEET 18-F- THE INTERIOR LOUNGE IS LISTED AT
 944 SQ. FT. WHICH RESULTS IN A 66 PERSON OCCUPANT
 DENSITY PER TABLE 403.3- PLEASE CORRECT.
  
 4) M-1: THE VENTILATION CALCULATION DOES NOT INCLUDE
 THE HUMIDOR ROOM, THE CORRIDOR/HALL 03, AND THE STORAGE
 ROOMS 1 & 2, . PLEASE NOTE THE HUMIDOR ROOM HAS A
 LISTED OCCUPANT LOAD OF 50 ON THE LIFE SAFETY PLAN-
 SHEET 18-F. A) CLARIFY WAT TYPE OF PRODUCTS, OR
 MATERIALS ARE BEING STORED IN THE STORAGE ROOMS.
  
 5) M-1: REFER TO TABLE 403.3 FOOTNOTE E AND INDICATE
 HOW EF-1 AND EF-2 WILL OPERATE- INTERMITTENTLY OR
 CONTINUOUSLY.
  
 6) AS PREVIOUSLY REQUESTED PROVIDE A COMPLETE
 CONDENSATE DISPOSAL PLAN THAT INCLUDES THE NEW 100 %
 O/A UNIT.
  
 7) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL REQUIRED
 CLEARANCES FOR THE OUTDOOR AIR INTAKES TO EXHAUST AND
 VENT OUTLETS- SEE SECTION 401.4.
  
 8) 2ND REQUEST FOR AN AIR DEVICE SCHEDULE.
  
 9) M-2 PROVIDE THE WIND LOAD DESIGN CRITERIA INCLUDING
 THE WIND SPEED, IMPORTANCE FACTOR, EXPOSURE CATEGORY,
 AND HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT- SECTION
 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By ccole Date 2016-05-06 Time 17:02 Rev Time 0.00
Received By ccole Date 2016-05-06 Time 17:02 Sent To  
Notes
2016-05-06 17:20:321ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING.
 PERMIT #16041056
 5/6/16
  
 1) THE MECHANICAL PLANS FOR THE PROPOSED PROJECT DO NOT
 PROVIDE ENOUGH INFORMATION FOR PERMITTING. IN
 ACCORDANCE WITH SECTION 1009.1 FBC-14 EXISTING
 BUILDING, PLEASE PROVIDE THE FOLLOWING:
 A) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 403.3 FBC-14 MECHANICALL. PROVIDE A
 SCHEDULE INDICATING THE REQUIRED AND PROVIDED CFM'S OF
 OUTDOOR AIR. PLEASE NOTE ALL AIR SUPPLIED TO INDOOR
 SMOKING LOUNGES SHALL BE EXHAUSTED AND SHALL NOT BE
 RE-CIRCULATED- SEE TABLE 403.3 FOOTNOTE B, AND SECTION
 403.2.1 (3).
 B) AC COOLING AND HEATING CALCULATIONS FOR THE NEW
 HUMIDOR SYSTEM PER SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
 C) AC EQUIPMENT SCHEDULES FOR ALL NEW AND EXISTING AC
 SYSTEMS.
 D) SUPPLY AND RETURN CFM'S AT ALL DIFFUSER AND RETURN
 GRILL LOCATIONS.
 E) AIR BALANCE CALCULATIONS- SEE SECTION 501.4 FBC-14
 MECHANCIAL.
 F) AIR DEVICE SCHEDULE
 G) DUCT HANGING, SUPPORT, AND CONNECTION AND
 REINFORCEMENT DETAILS.
 H) CONDENSATE DISPOSAL DETAILS PER SECTION 307
 I) WIND LOAD TIE-DOWN ENGINEERING FOR THE NEW ROOF TOP
 AC SYSTEM- SECTION 301.15.
 2) CLARIFY WHY NO RETURN SYSTEMS ARE SHOWN FOR THE AC
 SYSTEMS SUPPLYING THE RETAIL AREA- SEE SECTION 601.5
 FBC-=14 MECHANICAL.
 3) PLEASE NOTE ADDITIONAL COMMENTS MAY FOLLOW AFTER
 CORRECTED PLANS ARE SUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-07-20 Cont ID  
Sent By gjohnson Date 2016-07-20 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2016-07-20 Time 12:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-16 Cont ID  
Sent By gearl Date 2016-05-16 Time 11:18 Rev Time 0.00
Received By gjohnson Date 2016-05-03 Time 11:18 Sent To  
Notes
2016-05-16 16:22:03 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS
  
  
  
  
 1. NEED VENT FOR URINAL FBC PLUMBING 901.2
  
 2. NEED TO SHOW ON PLANS WHICH VENT IS GOING THRU ROOF.
 PER WPB AMEND. TO FBC 107.2.1
  
  
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.

Review Stop Z ZONING
Rev No 4 Status P Date 2016-09-27 Cont ID  
Sent By awooten Date 2016-09-27 Time   Rev Time 0.00
Received By awooten Date 2016-09-27 Time 15:25 Sent To  
Notes
2016-09-26 15:08:59ROUTED TO ALANA WOOTEN

Review Stop Z ZONING
Rev No 3 Status F Date 2016-08-24 Cont ID  
Sent By awooten Date 2016-08-24 Time 09:27 Rev Time 0.00
Received By awooten Date 2016-08-22 Time 16:50 Sent To  
Notes
2016-08-24 09:48:12***ZONING FAILED****
  
 THERE IS A LANDSCAPE PLAN THAT IS A PART OF THE
 APPROVAL FOR THE MINOR AMENDMENT PB812M TO THE VILLAGE
 COMMONS PLANNED DEVELOPMENT FOR THIS PERMIT. PLEASE
 SUBMIT SEPARATE LANDSCAPE AND IRRIGATION PLANS
 ACCORDING TO APPROVED LANDSCAPE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 ALANA WOOTEN, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1449
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-07-26 Cont ID  
Sent By awooten Date 2016-07-26 Time 15:24 Rev Time 0.00
Received By awooten Date 2016-07-26 Time 15:23 Sent To  
Notes
2016-07-26 15:35:08THE LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH
 ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2)
 COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE
 SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING
 MATERIAL TO BRING THE SITE INTO CONFORMITY.
  
 PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON THE
 PROPERTY, A TREE ALTERATION PERMIT SHALL BE SUBMITTED,
 REVIEWED AND APPROVED BY THE DEVELOPMENT SERVICES
 DEPARTMENT, PLANNING DIVISION. PLEASE CONTACT THE
 PLANNING DIVISION FOR MORE INFORMATION. (561) 822-1435,
 401 CLEMATIS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 ALANA WOOTEN, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1449
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By awooten Date 2016-05-06 Time 16:04 Rev Time 0.00
Received By dkittred Date 2016-05-06 Time 12:10 Sent To  
Notes
2016-05-06 16:08:45PLANNING AND ZONING COMMENTS: ***FAILED***
  
 5/6/16
  
 1. THE PROPOSED ADDITION TO THE SITE REQUIRES A MINOR
 PLANNED DEVELOPMENT (PD) APPROVAL THROUGH THE PLANNING
 DIVISION PRIOR ZONING APPROVAL OF THE BUIDLING PERMIT.
 A MINOR PD AMENDMENT APPLICANTION HAS BEEN SUBMITTED
 AND IS STILL UNDER REVIEW BY THE PLANNING DIVISION. AT
 THE TIME OF THIS REVIEW, A MINOR PD AMENDMENT APPROVAL
 HAS NOT YET BEEN ISSUED.
  