Plan Review Details - Permit 16041054
Plan Review Stops For Permit 16041054
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-06-03 Cont ID  
Sent By jwitmer Date 2016-06-03 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2016-06-03 Time 09:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-06-03 Cont ID  
Sent By jwitmer Date 2016-06-03 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2016-06-03 Time 06:59 Sent To  
Notes
2016-06-03 07:19:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041054
 ADD: 1610 PALM BEACH LAKES
 CONT: DOSDOURIAN ENTERPRISES INC.
 TEL: 561-844-2990
 E-MAIL: CONYATFIXDIRT.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JUNE 03/2016
 ACTION: DENIED
  
 1) COMPLIED. THE DESIGNER OF RECORD HAS NEGLECTED TO
 PROVIDE TO WHAT CODE THE DOCUMENTS WERE DESIGNED TOO?
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, JUNE 30, 2015 THE 2014 FBC/ 5TH EDITION
 WAS ADOPTED STATEWIDE.
  
 2) COMPLIED. THE DESIGNER OF RECORD HAS NEGLECTED TO
 PROVIDE COMPLIANCE WITH 2014 FBC-EXISTING BLDG. CODE
 SECTION 301.1 GENERAL. THE REPAIR, ALTERATION, CHANGE
 OF OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED
 IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE
 APPLICANT. APPLICATION OF A METHOD SHALL BE THE SOLE
 BASIS FOR ASSESSING THE COMPLIANCE OF WORK PERFORMED
 UNDER A SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE
 CODE OFFICIAL. SECTIONS 301.1.1 THROUGH 301.1.3 SHALL
 NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
  
 3) NOTICE, RESPONSE INDICATES THE INSPECTIONS ARE TO BE
 COMPLETED BY TEW TAYLOR PRIVATE PROVIDER. NO PAPERWORK
 HAS BEEN PROVIDED FOR THESE SERVICES AND SUBMITTED TO
 THE BUILDING DEPARTMENT.
  
 COMMENT FROM 1ST REVIEW. RESIDENT INSPECTOR. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS
 SERVICES. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO
 BE MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION:
 BOLTED OR WELDED CONNECTIONS.
  
 RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES
 NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT.
  
 3A) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'.
  
 3B) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3C) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED FOR REVIEW AND 2 SETS IN THE FIELD. THE TWO
 SETS OF PLANS WILL NEED TO BE FOR THE RESIDENT
 INSPECTOR, THE OTHER FOR THE MEP INSPECTORS.
  
 3D) NOTICE!!! PLEASE CALL THE CITY OF WEST PALM BEACH?S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-18 Cont ID  
Sent By jwitmer Date 2016-05-18 Time 16:35 Rev Time 0.00
Received By jwitmer Date 2016-05-18 Time 16:35 Sent To  
Notes
2016-05-18 16:42:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041054
 ADD: 1610 PALM BEACH LAKES
 CONT: DOSDOURIAN ENTERPRISES INC.
 TEL: 561-844-2990
 E-MAIL: AMYATFIXDIRT.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MAY 18/2016
 ACTION: DENIED
  
 1) PLANS WERE RESUBMITTED TODAY WITH HAND WRITTEN
 LANGUAGE ON THE PLANS. NO SIGNATURE NOR DATE!!!! I
 CALLED THE DESIGNER OF RECORD, GEORGE WINN HE HAD NOT
 BEEN IN THE BUILDING DEPARTMENT TODAY NOR HAS HE HAND
 WRITTEN LANUAGE ON THE PLAN. HE DID STATE THEY ARE
 CURRENTLY UPDATING THE PLANS FOR CODE COMPLIANCE.
  
 THE DESIGNER OF RECORD HAS NEGLECTED TO PROVIDE TO WHAT
 CODE THE DOCUMENTS WERE DESIGNED TOO?
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, JUNE 30, 2015 THE 2014 FBC/ 5TH EDITION
 WAS ADOPTED STATEWIDE.
  
 2) THE DESIGNER OF RECORD HAS NEGLECTED TO PROVIDE
 COMPLIANCE WITH 2014 FBC-EXISTING BLDG. CODE SECTION
 301.1 GENERAL. THE REPAIR, ALTERATION, CHANGE OF
 OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED
 IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE
 APPLICANT. APPLICATION OF A METHOD SHALL BE THE SOLE
 BASIS FOR ASSESSING THE COMPLIANCE OF WORK PERFORMED
 UNDER A SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE
 CODE OFFICIAL. SECTIONS 301.1.1 THROUGH 301.1.3 SHALL
 NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
  
 3) TODAY A LETTER WAS DROPPED OFF STATING THAT TEW AND
 TAYLOR ARE GOING TO BE DOING THE ONSITE INSPECTIONS,
 BUT NO DOCUMENTS WERE SUBMITTED FROM TEW & TAYLOR WERE
 SUBMITTED CONFORMING THEY WILL BE COMPLETING THE SITE
 INSPECTIONS.
 RESIDENT INSPECTOR. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION:
 BOLTED OR WELDED CONNECTIONS.
  
 RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES
 NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT.
  
 3A) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'.
  
 3B) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3C) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED FOR REVIEW AND 2 SETS IN THE FIELD. THE TWO
 SETS OF PLANS WILL NEED TO BE FOR THE RESIDENT
 INSPECTOR, THE OTHER FOR THE MEP INSPECTORS.
  
 3D) NOTICE!!! PLEASE CALL THE CITY OF WEST PALM BEACH?S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By jwitmer Date 2016-05-05 Time 09:53 Rev Time 0.00
Received By jwitmer Date 2016-05-05 Time 08:33 Sent To  
Notes
2016-05-05 09:37:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041054
 ADD: 1610 PALM BEACH LAKES
 CONT: DOSDOURIAN ENTERPRISES INC.
 TEL: 561-844-2990
 E-MAIL: CONYATFIXDIRT.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 05/2016
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD HAS NEGLECTED TO PROVIDE TO
 WHAT CODE THE DOCUMENTS WERE DESIGNED TOO?
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, JUNE 30, 2015 THE 2014 FBC/ 5TH EDITION
 WAS ADOPTED STATEWIDE.
  
 2) THE DESIGNER OF RECORD HAS NEGLECTED TO PROVIDE
 COMPLIANCE WITH 2014 FBC-EXISTING BLDG. CODE SECTION
 301.1 GENERAL. THE REPAIR, ALTERATION, CHANGE OF
 OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED
 IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE
 APPLICANT. APPLICATION OF A METHOD SHALL BE THE SOLE
 BASIS FOR ASSESSING THE COMPLIANCE OF WORK PERFORMED
 UNDER A SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE
 CODE OFFICIAL. SECTIONS 301.1.1 THROUGH 301.1.3 SHALL
 NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
  
 3) RESIDENT INSPECTOR. 2010 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES. THE
 BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY
 OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE
 MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED
 INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION
 HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND
 RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION
 OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH
 REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY
 A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION:
 BOLTED OR WELDED CONNECTIONS.
  
 RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES
 NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT.
  
 3A) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'.
  
 3B) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3C) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED FOR REVIEW AND 2 SETS IN THE FIELD. THE TWO
 SETS OF PLANS WILL NEED TO BE FOR THE RESIDENT
 INSPECTOR, THE OTHER FOR THE MEP INSPECTORS.
  
 3D) NOTICE!!! PLEASE CALL THE CITY OF WEST PALM BEACH?S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-04-28 Cont ID  
Sent By mvaldes Date 2016-04-28 Time 12:46 Rev Time 0.00
Received By mvaldes Date 2016-04-28 Time 12:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-26 Cont ID  
Sent By scaldero Date 2016-04-26 Time 17:13 Rev Time 0.00
Received By scaldero Date 2016-04-26 Time 17:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-03 Cont ID  
Sent By jwitmer Date 2016-06-03 Time 07:20 Rev Time 0.00
Received By jwitmer Date 2016-05-24 Time 15:28 Sent To  
Notes
2016-05-24 15:28:34RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-18 Cont ID  
Sent By jwitmer Date 2016-05-18 Time 16:42 Rev Time 0.00
Received By jwitmer Date 2016-05-18 Time 12:35 Sent To  
Notes
2016-05-18 12:35:48RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-05 Cont ID  
Sent By jwitmer Date 2016-05-05 Time 09:53 Rev Time 0.00
Received By jwitmer Date 2016-04-22 Time 15:44 Sent To  
Notes
2016-04-22 15:45:01B23

Review Stop Z ZONING
Rev No 1 Status N Date 2016-04-22 Cont ID  
Sent By lmarchan Date 2016-04-22 Time 15:44 Rev Time 0.00
Received By lmarchan Date 2016-04-22 Time 15:44 Sent To  
Notes
2016-04-22 15:44:42ZONING NOT REQUIRED, ENTERED BY MISTAKE.