| Plan Review Stops For Permit 16041021 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-09-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-09-27 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-09-27 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-08-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-08-24 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-08-24 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2016-08-24 10:27:40 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER ? PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | DATE: 8/24/16 | | | | | | 1. EXISTING PARKING AREAS IN FRONT OF BLDG. A AND IN | | | FRONT OF SINGLE STORY WING ARE SEPERATE PARKING | | | FACILITIES AND SHALL COMPLY WITH FBC ACCESS. PARKING | | | REQUIREMENTS PER TABLE 208.2. | | | 2. IDENTIFY ACCESS. ROUTES FROM PARKING TO BLDG'S. | | | 3. IDENTIFY ACCESS. ENTRANCES. | | | | | | 208.2 MINIMUM NUMBER. | | | PARKING SPACES COMPLYING WITH 502 SHALL BE PROVIDED IN | | | ACCORDANCE WITH TABLE 208.2 EXCEPT AS REQUIRED BY | | | 208.2.1, 208.2.2, AND 208.2.3. WHERE MORE THAN ONE | | | PARKING FACILITY IS PROVIDED ON A SITE, THE NUMBER OF | | | ACCESSIBLE SPACES PROVIDED ON THE SITE SHALL BE | | | CALCULATED ACCORDING TO THE NUMBER OF SPACES REQUIRED | | | FOR EACH PARKING FACILITY. | | | | | | 402 ACCESSIBLE ROUTES | | | 402.2 COMPONENTS. | | | ACCESSIBLE ROUTES SHALL CONSIST OF ONE OR MORE OF THE | | | FOLLOWING COMPONENTS: WALKING SURFACES WITH A RUNNING | | | SLOPE NOT STEEPER THAN 1:20, DOORWAYS, RAMPS, CURB | | | RAMPS EXCLUDING THE FLARED SIDES, ELEVATORS, AND | | | PLATFORM LIFTS. ALL COMPONENTS OF AN ACCESSIBLE ROUTE | | | SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF | | | CHAPTER 4 AND 208.3.1. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-05-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-05-25 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-05-25 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2016-05-25 16:59:42 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 5TH EDITION | | | | | | 1. REVISE PLAN TO PROVIDE THE FOLLOWING INFORMATION: | | | | | | TOTAL NUMBER OF PARKING SPACES | | | NUMBER OF ACCESSIBLE SPACES | | | LOCATION OF ACCESSIBLE ENTRANCES | | | LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES | | | SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY | | | ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE | | | ENTRANCE | | | | | | SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2 | | | (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE | | | ROUTE). | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2016-09-21 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2016-09-21 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2016-09-21 |
Time |
|
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2016-08-23 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2016-08-23 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2016-08-23 |
Time |
|
Sent To |
Z |
|
| Notes |
| 2016-08-23 15:37:02 | NO FURTHER FROM ENGINEERING. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2016-05-09 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2016-05-03 |
Time |
14:40 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2016-05-09 |
Time |
|
Sent To |
B |
|
| Notes |
| 2016-05-09 10:00:20 | FORMALLY SUBMIT PLAN THRU ENGINEERING UNDER DEVELOPMENT | | | PERMIT. | | | HTTP://WPBFL.US/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO | | | RMS,-PERMITS-APPLICATIONS | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-09-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-09-27 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-09-01 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2016-09-01 13:44:39 | RESUB ROUTED TO JROACH VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-08-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-08-24 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-06-30 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2016-06-30 14:38:54 | RESUB ROUTED TO AJONES VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-05-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-05-25 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-04-22 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2016-05-11 16:30:37 | 5/11 TO MISC 2 | | | | | 2016-04-22 15:49:53 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-09-02 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-09-02 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-09-02 |
Time |
09:19 |
Sent To |
ENG |
|
| Notes |
| 2016-09-02 09:19:31 | PROVISO | | | | | | ALL CIVIL DRAWINGS SHALL BE UPDATED TO ACCURATELY MATCH | | | WHAT IS SHOWN ON THE APPROVED SITE PLAN. ANY REVISIONS | | | NECESSARY SHALL BE COMPLETED. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT | | | JOHN ROACH, PRINCIPAL PLANNER, AT | | | [email protected] OR (561) 822-1448. | | | | | 2016-09-02 08:38:38 | ROUTED TO JOHN ROACH |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2016-07-15 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-07-15 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-07-15 |
Time |
09:40 |
Sent To |
ENG |
|
| Notes |
| 2016-07-15 09:41:13 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 07.15.2016 | | | PERMIT NO.: 16041021 | | | ADDRESS: 2823 AUSTRALIAN AVENUE | | | CONTRACTOR/CONTACT: MATT BLACKBURN | | | TELEPHONE NO.: 561.762.7848 | | | SCOPE OF REVIEW: MODIFICATION TO EXISTING PARKING LOT | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. BASED UPON CONVERSATIONS WITH THE SITE | | | PLANNER/LANDSCAPE ARCHITECT, THE PARKING LOT IS BEING | | | MODIFIED SLIGHTLY TO BRING THE SITE INTO CONFORMITY | | | WITH THE CITY?S ZONING AND LAND DEVELOPMENT | | | REGULATIONS. THE PLANS SUBMITTED AS PART OF THIS PERMIT | | | APPLICATION NEED TO BE UPDATED TO THE MOST RECENT | | | PROPOSAL. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-05-03 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2016-04-26 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2016-04-26 |
Time |
17:53 |
Sent To |
ENG |
|
| Notes |
| 2016-05-03 14:40:27 | 5/3/16- FAILED. ZONING NEEDS AN EXISTING SITE PLAN | | | SHOWING THE PARKING LAYOUT AND COUNT. THE SQUARE | | | FOOTAGE OF THE PROPOSED ADDITION NEEDS TO BE SHOWN ON | | | THE SITE PLAN. | | | ANGELLA VANN, AICP | | | [email protected] | | | 561-822-1441 |
|
|