2016-05-24 14:03:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. LS1.1, IT IS NOT CLEAR WHETHER OR NOT A CHANGE OF
 OCCUPANCY IS APPLICABLE. REVISE PLAN TO INCLUDE THIS
 INFORMATION.
  
 2. LS1.1, CODE ANALYSIS REFERS TO A LAB, BUT I WAS
 UNABLE TO LOCATE ON THE PLAN, FBC 107.
  
 3. REVISE PLAN TO SHOW THE 18" CLEARANCE, PULL SIDE,
 FBC 5TH ED. ACCESSIBILITY FIGURE 404.2.4.1 FOR DOORS
 106-1, 108-1, 119-2, DOOR TO FEMALE BATHROOM.
  
 4. REVISE PLAN TO SHOW CORRIDOR WIDTH, REQUIRED WIDTH,
 TO SHOW COMPLIANCE WITH FBC 5TH ED. BUILDING 1005.7.1.
  
 5. USE OF THE MULTI PURPOSE ROOM IS NOT ENTIRELY CLEAR.
 SEE FBC 5TH ED. ACCESSIBILITY 221. ALSO CLARIFY THE USE
 OF WHAT APPEARS TO BE WORK STATIONS. REVISE THE PLAN TO
 CLARIFY COMPLIANCE WITH (OR EXEMPTION TO) ACCESSIBILITY
 REQUIREMENTS.
  
 6. A ROOF REPORT WAS PROVIDED. INDICATE THE ASSEMBLY
 PROPOSED AND, IF REQUIRED, PROVIDE ENGINEERING. IF THIS
 IS NOT PROVIDED WITH THE RESUBMITTAL, THIS INFORMATION
 WILL BE REQUIRED WITH THE ROOF PERMIT APPLICATION.
  
 7. SHEET A6.2, HARDWARE AND FIRE RATING FOR DOORS
 COLUMNS ARE BLANK. NOT ALL DOORS ON THE PLAN (FOR
 INSTANCE, THE MULTI PURPOSE ROOM) ARE LABELED. FIRE
 RATED WALLS AND A SMOKE PARTITION ARE SHOWN, BUT THE
 DOOR SCHEDULE DOES NOT INDICATE THAT ANY DOORS WILL BE
 RATED. REVISE TO CLARIFY, FBC 107.
  
 8. IF THIS INCLUDES A CHANGE OF OCCUPANCY, IMPACT FEE
 ASSESSMENT FROM PALM BEACH COUNTY IS REQUIRED.
 561-233-5025 FOR MORE INFORMATION.
  
 9. PLEASE SEE PLUMBING COMMENTS REGARDING ACCESSIBLE
 ELEMENTS.
  
 10. COURTESY ADVISORY TO WARREN JOHNSON, PE; PLEASE SEE
 FS 471.0195 AND 61G15-22.001, AN ADVANCED BUILDING CODE
 COURSE IS REQUIRED BY JUNE 30, 2016. EVIDENCE IS TO BE
 PROVIDED TO FBPE FOR WWW.MYFLORIDALICENSE.COM UPDATE.
  
 FOR MORE INFORMATION, SEE PAGE 4:
  
 HTTPS://WWW.FBPE.ORG/INDEX.PHP/FILE-DOWNLOADS/SEND/56-2
 015-2016-FBPE-NEWSLETTERS/377-APRIL-2016-FBPE-NEWSLETTE
 R
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-18 Cont ID  
Sent By mvaldes Date 2016-07-18 Time 16:12 Rev Time 0.00
Received By mvaldes Date 2016-07-18 Time 15:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-28 Cont ID  
Sent By mvaldes Date 2016-04-28 Time 10:42 Rev Time 0.00
Received By mvaldes Date 2016-04-28 Time 08:57 Sent To  
Notes
2016-04-28 10:43:56JOB PERMIT NUMBER: 16040999
 JOB ADDRESS: 2823 AUSTRALIAN AVE
 WEST PALM BEACH FLORIDA
 DATE: APRIL 28 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - SHEET E1.1 NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET.
 A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT OF THE
 EQUIPMENT. MISSING FOR AC UNITS CU 1-3 , RTU 1-1 , QA 1
 , RTU 1-2.
 - CLARIFY IF CIRCUIT L1A-9 IS A DRINKING FOUNTAIN ? IF
 SO IT SHALL BE PROTECTED WITH A GFCI. NEC 422.52
 - SHEET E2.1 PENDANT LIGHTING OUTLET BOX IN THE CEILING
 SHALL BE REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A
 MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON CEILING
 BOXES ON PAGE.
 - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A
 BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 - SHEET E3.1 FIRE ALARM SHALL BE ON A SEPARATE PERMIT.
 - SHEET E4.1 PROVIDE AIC CALCS FOR EQUIPMENT AND
 INTERRUPTING RATING OF OCPD. NEC 110.10 , 110.9.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-08-11 Cont ID  
Sent By skennedy Date 2016-09-26 Time 15:08 Rev Time 1.00
Received By mgonzale Date 2016-09-26 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-07-14 Cont ID  
Sent By pleduc Date 2016-07-14 Time   Rev Time 0.00
Received By pleduc Date 2016-07-14 Time 12:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-05-02 Cont ID  
Sent By pleduc Date 2016-05-02 Time   Rev Time 0.00
Received By pleduc Date 2016-05-02 Time 09:46 Sent To  
Notes
2016-05-02 10:12:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 6.2 - THE DOOR SCHEDULE DOES NOT INCLUDE
 INDICATIONS TO DOORS IN SMOKE PARTITIONS.
  
 PLEASE PROVIDE DETAILS IN THE DOOR SCHEDULE INDICATING
 WHICH DOORS SHALL COMPLY WITH NFPA 101, CHAPTER 14,
 14.3.6 (A) & CHAPTER 8, 8.4. SMOKE PARTITIONS.
  
 2) SHEET A 6.2 - THE DOOR SCHEDULE DOES NOT INDICATE
 EXIT HARDWARE ON EXIT DOORS.
  
 PLEASE PROVIDE DETAILS IN THE DOOR SCHEDULE INDICATING
 WHICH DOORS SHALL COMPLY WITH NFPA 101, CHAPTER 7,
 MEANS OF EGRESS, 7.2.1.7 PANIC HARDWARE AND FIRE EXIT
 HARDWARE.
  
 3) SHEET A 1.1 - DOORS INDICATED AS 100 / 3 SHOW THEM
 OPENING INTO THE EXIT CORRIDOR.
  
 PER SECTION NFPA 101, DOOR SWING DIRECTION, 7.2.1.4.2,
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE REVIEW AND PROVIDE INDICATIONS/DIMENSIONS
 COMPLYING WITH THE THE CODE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-26 Cont ID  
Sent By lmarchan Date 2016-09-26 Time 15:41 Rev Time 0.00
Received By lmarchan Date 2016-09-09 Time 13:25 Sent To  
Notes
2016-09-12 08:41:059/12 TO ENGINEERING BOX
  
  
2016-09-09 13:25:20IMPACT FEES ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-11 Cont ID  
Sent By skennedy Date 2016-08-11 Time 15:08 Rev Time 0.00
Received By skennedy Date 2016-08-04 Time 12:44 Sent To  
Notes
2016-08-11 10:28:008/11 TO SAK DESK TO COORDINATE ENGINEERING REVIEW
  
2016-08-05 12:44:40RESUB ROUTED TO JROACH VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-28 Cont ID  
Sent By gjohnson Date 2016-07-28 Time 10:41 Rev Time 0.00
Received By gjohnson Date 2016-06-30 Time 15:32 Sent To  
Notes
2016-06-30 15:32:56C30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 14:16 Rev Time 0.00
Received By shill Date 2016-04-22 Time 10:35 Sent To  
Notes
2016-04-25 10:35:58C28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-09-12 Cont ID  
Sent By shill Date 2016-09-12 Time 07:35 Rev Time 0.00
Received By shill Date 2016-09-12 Time 07:35 Sent To  
Notes
2016-09-12 07:36:23MU-2016-022139-0000
 $18,728.29 PAID
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-07-26 Cont ID  
Sent By shill Date 2016-07-26 Time 12:35 Rev Time 0.00
Received By shill Date 2016-07-26 Time 12:35 Sent To  
Notes
2016-07-26 12:36:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 PLEASE CONTACT 561-233-5025 FOR MORE INFORMATION.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 14:15 Rev Time 0.00
Received By shill Date 2016-05-24 Time 14:15 Sent To  
Notes
2016-05-24 14:16:04SEE BUILDING COMMENTS
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-05 Cont ID  
Sent By ccole Date 2016-07-05 Time 16:24 Rev Time 0.00
Received By ccole Date 2016-07-05 Time 16:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-05-23 Cont ID  
Sent By ccole Date 2016-05-03 Time 11:23 Rev Time 0.00
Received By ccole Date 2016-05-03 Time 11:45 Sent To  
Notes
2016-05-03 12:54:101ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040999
 5/3/16
  
 1) SHEET AD-1.3: PLEASE SHOW NOTE #2 LOCATIONS ON THE
 PLAN- MECHANICAL EQUIPMENT TO BE REMOVED.
 2) THE OUTDOOR DRY BULB AND WET BULB COOLING
 TEMPERATURES SHOWN ON THE PLANS ARE HIGHER THAN THE
 TEMPERATURES INDICATED IN ACCA MANUUAL N FOR WPB WHICH
 ARE 90 DEGREES AND 78 DEGREES.
 3) SHEET M4.1: THE VENTILATION CALCULATIONS INDICATE
 1523 CFM'S OF O/A REQUIRED FOR PHASE 1, HOWEVER THE AC
 SCHEDULES INDICATE A TOTAL OF 1410 CFM'S TO BE
 PROVIDED.
 4) M2.1: SEE NOTE #10 AND CLARIFY IF, UNDER THIS
 PHASE-1, THE OA-1 WILL SHUT DOWN ALONG WITH THE DAMPER.
 5) M2.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF OA-1- SECTION 606.2.1.
 6) M2.1 & M6.1: THE CONTROL DIAGRAM FOR RTU-1-2 IS
 ERRONEOUSLY SHOWING CONNECTION TO OA-1.
 7) M2.1: INDICATE HOW O/A IS BEING PROVIDED TO STORAGE
 ROOM 100A
 8) M5.2 & S3.4: PROVIDE COMPLETE ENGINEERED DETAILS FOR
 INSTALLATION OF THE ROOFTOP UNITS, AND SUBMIT A FL.
 PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE THYBAR CURBS
 APPROVED WITH SIGNATURE BY THE EOR. PLEASE NOTE THE
 STRUCTURAL DETAIL SHOWS A WELDED CONNECTION FOR THE
 CURB TO THE ROOF STRUCTURE.
 9) PROVIDE WIND LOAD ENGINEERING FOR THE INSTALLATION
 OF CU-1-3 ON THE HOUSEKEEPING- SECTION 301.15.
 10) PROVIDE A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE EXHAUST LOUVERS.
 11) THE EOR MUST COMPLETE HIS MANDATORY REQUIREMENTS
 CHECKLIST ON PAGE 10 OF THE ENERGY COMPLIANCE
 SUBMITTAL.
 12) REFER TO SECTION C403.3.1.1.1: THE ECONOMIZER SHALL
 BE CAPABLE OF MODULATING OUTDOOR AIR AND RETURN AIR
 DAMPERS TO PROVIDE UP TO 100 PERCENT OF THE DESIGN
 SUPPLY AIR QUANTITY AS OUTDOOR AIR FOR COOLING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-08-02 Cont ID  
Sent By gjohnson Date 2016-08-02 Time 18:20 Rev Time 0.00
Received By gjohnson Date 2016-08-02 Time 18:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-07-28 Cont ID  
Sent By gjohnson Date 2016-07-28 Time 10:33 Rev Time 0.00
Received By gjohnson Date 2016-07-28 Time 10:33 Sent To  
Notes
2016-07-28 10:41:132ND REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. A GREASE INTERCEPTOR WAS ADDED TO PLAN PLEASE
 PROVIDE SIZING CALCULATION FROM THE MANUFACTURE SCHIER
 WILL SUPPLY A FORM FOR YOU TO SUBMIT. PER WPB AMEND. TO
 FBC 107.2.1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By gjohnson Date 2016-05-06 Time 17:20 Rev Time 0.00
Received By gjohnson Date 2016-05-04 Time 13:19 Sent To  
Notes
2016-05-06 17:45:26 
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PROPOSED OCCUPANT LOAD AND USE FOR
 SECOND FLOOR I UNDERSTAND ITS UNDER DIFFERENT PERMIT.
 WPB AMEND. TO FBC SEC. 107.2.1
  
 2. SHT. LS 1.1 ON THE PLUMBING FIXTURE REQUIREMENT DOES
 YOUR OCCUPANT LOAD INCLUDE SECOND FLOOR. WPB AMEND. TO
 FBC SEC. 107.2.1
  
 3. SHT LS 1.1 YOU CALL OUT 7 TOILETS FOR MALE STUDENTS
 I ONLY COUNT 6 INCLUDING 2ND FLOOR PLEASE CLARIFY.
 609.4
  
 4. SHT A-8.1 SHOW 16IN. MIN AND 18IN. MAX FROM SIDE
 WALL TO CENTER OF TOILET COMPLY WITH 609.4
  
 5. SHT A-8.1 SHOW 33IN. MIN TO 36IN MAX MEASURED TO THE
 TOP OF GRIPPING SURFACE ON THE GRAB BARS. FBC ACC. SEC.
 609.4
  
 6. SHT P 3.1 UP STREAM OF THE BACK TO BACK HANDICAP
 TOILETS A HORIZONTAL DRY VENT IS NOT ALLOWED. PER FBC
 PL 905.3 AND 4
  
 7. PROVIDE MANUFATURE SPEC SHEETS FOR OIL MINDER SUMP
 PUMP AND WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1
  
 8. PROVIDE STORM WATER RISER DIAGRAM WITH THE SQ FT. OF
 AREA BEING DRAINED.WPB AMEND. TO FBC SEC.
 107.3.5.1.3(13)

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-07-26 Cont ID  
Sent By shill Date 2016-07-26 Time 14:25 Rev Time 0.00
Received By shill Date 2016-07-26 Time 14:25 Sent To  
Notes
2016-07-26 14:27:36ROOF PERMIT APPLICATION AND ROOF ASSEMBLY (ALONG WITH
 ENHANCED FASTENING ENGINEERING IF REQUIRED), TO BE
 SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
 FL 17013 SUBMITTED (JOHNS MANVILLE MODIFIED); PRESSURES
 TO COMPLY WITH DPS ON SHEET S0.2.
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 14:15 Rev Time 0.00
Received By shill Date 2016-05-24 Time 14:15 Sent To  
Notes
2016-05-24 14:15:19SEE BUILDING COMMENTS
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status N Date 2016-07-26 Cont ID  
Sent By shill Date 2016-07-26 Time 17:33 Rev Time 0.00
Received By shill Date 2016-07-26 Time 17:33 Sent To  
Notes
2016-07-26 17:33:37SEE SHEET LS1.2. THE PERMIT DOCUMENTS SHOW A TWO STORY
 BUILDING WITH A SMALL ONE STORY ADDITION. THE PERMIT
 DOCUMENTS DEPICT FUTURE RENOVATIONS (PHASE 2 AND PHASE
 3). THIS FUTURE WORK IS NOT INCLUDED IN THE SCOPE OF
 THIS PERMIT, WITH THE EXCEPTION OF DEMOLITION (SHEET
 AD1.1). THE FUTURE OCCUPANT LOAD, INCLUDING THE PHASE 2
 AND 3 BUILDOUTS, ARE INCLUDED IN THE PERMIT DOCUMENTS
 TO FACILITATE THE FUTURE CONSTRUCTION. HOWEVER, THE
 BUILDING AS IS TODAY DOES NOT FIT THE DEFINITION OF A
 "THRESHOLD BUILDING" AS THE OCCUPANT LOAD OF THE
 OCCUPIED AREA IS 413. THE FUTURE PHASE 2 & 3 SPACES ARE
 UNOCCUPIED PENDING FUTURE CONSTRUCTION.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By shill Date 2016-07-26 Time 13:51 Rev Time 0.00
Received By shill Date 2016-07-26 Time 12:03 Sent To  
Notes
2016-07-26 13:51:22PENDING EMAIL FROM ARCHITECT
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-08-08 Cont ID  
Sent By jroach Date 2016-08-08 Time 16:27 Rev Time 0.00
Received By jroach Date 2016-08-08 Time 16:25 Sent To B
Notes
2016-08-08 16:38:16PROVISO
  
 A SEPARATE LANDSCAPE PERMIT SHALL BE ISSUED. ALL
 LANDSCAPING SHALL BE INSTALLED AND PASS INSPECTION
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY /
 COMPLETION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-07-07 Cont ID  
Sent By jroach Date 2016-07-07 Time 13:37 Rev Time 0.00
Received By jroach Date 2016-07-06 Time 09:30 Sent To  
Notes
2016-07-07 13:48:00ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.07.2016
 PERMIT NO.: 16040999
 ADDRESS: 2823 AUSTRALIAN AVENUE
 CONTRACTOR/CONTACT: MATT BLACKMAN
 TELEPHONE NO.: 561.762.7848
 SCOPE OF REVIEW: NEW ADDITION.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A DATA TABLE SHALL BE PROVIDED INDICATING THE
 FOLLOWING:
  
  A. TOTAL GROSS BUILDING SQUARE FOOTAGE (EXISTING AND
 PROPOSED).
  
  D. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE & IMPERMEABLE SURFACE (EXISTING AND PROPOSED).
  
  E. PARKING COMPUTATIONS (PARKING REQUIRED, PROVIDED,
 ETC. FOR EXISTING AND PROPOSED)
  
  F. FLOOR AREA RATIO (FAR) (EXISTING AND PROPOSED).
  
 2. SITE PLAN SHALL INDICATE THE FLOOR AREA FOR THE
 PROPOSED ADDITION.
  
 3. LANDSCAPE ISLANDS AT THE ENDS OF PARKING ROWS SHALL
 BE A MINIMUM OF FIVE (5) FEET IN WIDTH, AS MEASURED
 FROM THE INSIDE OF THE CURB. BASED UPON CONVERSATION
 WITH JON SCHMIDT, THE FOLLOWING MODIFICATIONS ARE GOING
 TO BE MADE:
  
  A. IMMEDIATELY NORTH OF BUILDING A, THE EASTERN-MOST
 LANDSCAPE ISLAND WILL BE EXPANDED TO AT LEAST FIVE (5)
 FEET IN WIDTH BY CONVERTING ONE (1) PARKING SPACE INTO
 A COMPACT SPACE (8 FEET WIDE).
  
  B. IMMEDIATELY SOUTH OF THE DUMPSTER ENCLOSURE, THE
 ROW OF FOUR (4) PARKING SPACES WILL BE SHIFTED IN A
 WESTERLY DIRECTION TO PROVIDE A LANDSCAPE ISLAND OF AT
 LEAST FIVE (5) FEET IN WIDTH ADJACENT TO AUSTRALIAN
 AVENUE.
  
  C. THE ROW OF PARKING ADJACENT TO THE SOUTHEAST CORNER
 OF BUILDING "C" WILL BE SHIFTED IN AN EASTERLY
 DIRECTION TO CREATE A LANDSCAPE AREA ALONG THE
 FOUNDATION OF THE FORMER GARAGE.
  
 4. PLEASE EVALUATE THE CURRENT CONDITION OF THE DOOR
 EXISTING THE NORTH SIDE OF BUILDING "A" INTO THE
 PARKING SPACE. A CAR PARKED IN THE SPACE MAY PREVENT
 THIS DOOR FROM BEING UTILIZED AND COULD BE A POTENTIAL
 SAFETY HAZARD. IF SO, ADJUSTMENTS WILL NEED TO BE MADE
 ACCORDINGLY.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-05-06 Cont ID  
Sent By jroach Date 2016-05-06 Time 16:51 Rev Time 0.00
Received By jroach Date 2016-05-06 Time 16:51 Sent To  
Notes
2016-05-06 16:51:39ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.06.2016
 PERMIT NO.: 16040999
 ADDRESS: 2823 AUSTRALIAN AVENUE
 CONTRACTOR/CONTACT: MATT BLACKMAN
 TELEPHONE NO.: 561.762.7848
 SCOPE OF REVIEW: NEW ADDITION.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A DATA TABLE SHALL BE PROVIDED INDICATING THE
 FOLLOWING:
  
  A. EXISTING/PROPOSED LAND USE AND ZONING.
  
  B. TOTAL ACRES OF THE PROJECT.
  
  C. TOTAL GROSS BUILDING SQUARE FOOTAGE (EXISTING AND
 PROPOSED).
  
  D. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE & IMPERMEABLE SURFACE (EXISTING AND PROPOSED).
  
  E. PARKING COMPUTATIONS (PARKING REQUIRED, PROVIDED,
 ETC. FOR EXISTING AND PROPOSED)
  
  F. FLOOR AREA RATIO (FAR) (EXISTING AND PROPOSED).
  
 2. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 3. SITE PLAN SHALL INDICATE THE SETBACKS, DIMENSIONS,
 FLOOR AREA, ETC. FOR THE PROPOSED ADDITION.
  
 4. THE GATE UTILIZED FOR THE DUMPSTER SCREENING SHALL
 CONSIST OF A PERMANENT OPAQUE MATERIAL?CHAINLINK WITH
 SLATS SHALL NOT BE PERMITTED.
  
 5. A PARKING DETAIL IN CONFORMANCE WITH THE CITY?S
 ZLDRS SHALL BE PROVIDED.
  
 6. LANDSCAPE ISLANDS AT THE ENDS OF PARKING ROWS SHALL
 BE A MINIMUM OF FIVE (5) FEET IN WIDTH, AS MEASURED
 FROM THE INSIDE OF THE CURB (ISLANDS/BUFFER ALONG
 AUSTRALIAN AVENUE DOES NOT APPEAR TO MEET THIS
 REQUIREMENT).
  
 7. IT APPEARS THAT THERE IS A LOSS OF PARKING FROM WHAT
 CURRENTLY EXISTS ON THE PROPERTY; PARKING DATA SHALL BE
 PROVIDED INDICATING THAT THE SITE CONFORMS TO THE
 MINIMUM REQUIREMENTS OF THE CITY?S ZLDRS. IF THE SITE
 IS CURRENTLY NONCONFORMING, THAT IS FINE AND MAY
 CONTINUE, BUT PARKING WOULD HAVE TO BE PROVIDED FOR THE
 ADDITIONAL SQUARE FOOTAGE (NO PARKING COULD BE
 REMOVED).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved