| 2016-06-22 11:02:20 | |
| | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | DATE: 6/22/16 |
| | ACTION: DENIED |
| | |
| | 1. ALL PROPOSED DOORS ARE TO BE INSTALLED IN RATED |
| | CORRIDORS. PROVIDE DOCUMENTATION THAT DOORS WILL COMPLY |
| | WITH THE FOLLOWING REQUIREMENTS: |
| | |
| | 716.5.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE |
| | BARRIERS. |
| | FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE |
| | PROTECTION RATING OF 20 MINUTES WHERE LOCATED IN |
| | CORRIDOR WALLS OR SMOKE BARRIER WALLS HAVING A |
| | FIRE-RESISTANCE RATING IN ACCORDANCE WITH TABLE 716.5 |
| | SHALL BE TESTED IN ACCORDANCE WITH NFPA 252 OR UL 10C |
| | WITHOUT THE HOSE STREAM TEST. |
| | |
| | 716.5 FIRE DOOR AND SHUTTER ASSEMBLIES. |
| | APPROVED FIRE DOOR AND FIRE SHUTTER ASSEMBLIES SHALL BE |
| | CONSTRUCTED OF ANY MATERIAL OR ASSEMBLY OF COMPONENT |
| | MATERIALS THAT CONFORMS TO THE TEST REQUIREMENTS OF |
| | SECTION 716.5.1, 716.5.2 OR 716.5.3 AND THE FIRE |
| | PROTECTION RATING INDICATED IN TABLE 716.5. FIRE DOOR |
| | FRAMES WITH TRANSOM LIGHTS, SIDELIGHTS OR BOTH SHALL BE |
| | PERMITTED IN ACCORDANCE WITH SECTION 716.5.6. FIRE DOOR |
| | ASSEMBLIES AND SHUTTERS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND NFPA |
| | 80. |
| | |
| | 716.5.7.1 FIRE DOOR LABELING REQUIREMENTS. |
| | FIRE DOORS SHALL BE LABELED SHOWING THE NAME OF THE |
| | MANUFACTURER OR OTHER IDENTIFICATION READILY TRACEABLE |
| | BACK TO THE MANUFACTURER, THE NAME OR TRADEMARK OF THE |
| | THIRD PARTY INSPECTION AGENCY, THE FIRE PROTECTION |
| | RATING AND, WHERE REQUIRED FOR FIRE DOORS IN INTERIOR |
| | EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS BY |
| | SECTION 716.5.5, THE MAXIMUM TRANSMITTED TEMPERATURE |
| | END POINT. SMOKE AND DRAFT CONTROL DOORS COMPLYING WITH |
| | UL 1784 SHALL BE LABELED AS SUCH AND SHALL ALSO COMPLY |
| | WITH SECTION 716.5.7.3. LABELS SHALL BE APPROVED AND |
| | PERMANENTLY AFFIXED. THE LABEL SHALL BE APPLIED AT THE |
| | FACTORY OR LOCATION WHERE FABRICATION AND ASSEMBLY ARE |
| | PERFORMED. |
| | |
| | 2. COMPLY WITH FIRE REVIEW COMMENTS. |
| | |