| Plan Review Stops For Permit 16040973 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-04-27 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-04-27 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-04-27 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2016-04-27 12:43:05 | THERE WAS A TYPO ON THE PLANS SPOKE TO PROJECT MANAGER | | | , I ATTACHED THE EMAIL WITH THE APPLICATIONS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-04-27 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-04-27 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-04-27 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2016-04-27 11:07:16 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | NEC 240.21 C(1) , NEC 240.21 C(4) TRANSFORMER SECONDARY | | | CONDUCTORS MUST TERMINATE TO A OVERCURRENT PROTECTION | | | DEVICE. REFERENCE TABLE NEC 450.3 (B) | | | NEC 240.21 B(5) FEEDER TAP CONDUCTORS MUST BE PROTECTED | | | BY A OVERCURRENT PROTECTION. REFERENCE NEC 408.36 | | | PANELBOARD PROTECTION. | | | RISER DIAGRAM SHOWS EQUIPMENT "T1" , "T2" , "TL" AS MLO | | | AND PANEL SCHEDULE REFLECTS MCB ? CLARIFY AND RE-ADJUST | | | ACCORDINGLY. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-04-27 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-04-27 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-04-26 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2016-04-26 15:23:24 | REVISION ROUTED TO MVALDES |
|
|
|