| Plan Review Stops For Permit 16040967 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-07-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-26 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-26 |
Time |
15:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-07-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-01 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-01 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2016-07-01 18:46:54 | COORDINATE THE SITE PLAN WITH THE SURVEY/DRAINAGE PLAN | | | PER ZONING COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-05-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-24 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-23 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2016-05-24 16:16:29 | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A SURFACE WATER DRAINAGE PLAN THAT SHOWS | | | COMPLIANCE WITH FBC-R401.3. | | | | | | 2) A CORPORATION CAN NOT SIGN THE ENERGY FORM FOR THE | | | OWNER/AGENT. THE OWNER/AGENT LINE ON THE ENERGY FORM | | | NEEDS TO BE SIGNED BY A PERSON, SUCH AS A PRINCIPLE IN | | | THE CORPORATION. | | | | | | 3) THE CLIMATE ZONE FOR PALM BEACH IS 1A NOT 2. SEE FBC | | | ENERGY CONSERVATION TABLE R301.1. | | | | | | 4) THE ENERGY FORM INDICATES THAT THE CROSS VENTILATION | | | OPTION IS BEING USED. SHOW ON THE PLANS THE | | | INSTALLATION CRITERIA IN FBC ENERGY CONSERVATION | | | SECTION R405.7.4 THAT IS REQUIRED. PROVIDE CALCULATIONS | | | THAT SHOW THE OPERABLE APERTURE AREAS TOTAL A MINIMUM | | | OF 12 PERCENT OF THE FLOOR AREA FOR ALL PRIMARY LIVING | | | AREAS AND BEDROOMS. SPECIFY THAT INSECT SCREENS ARE | | | REQUIRED FOR ALL WINDOWS AND DOORS THAT ARE TO BE | | | CONSIDERED OPERABLE AREA. ALL SCREENED ENTRY DOORS AND | | | INTERIOR DOORS IN THE VENTILATED AREAS SHALL BE | | | PROVIDED WITH DEVICES TO HOLD THE DOOR IN AN OPEN | | | POSITION OR OPERABLE LOUVERS. | | | | | | 5) THE DETAILS ON SHEET S.2 SPECIFY A STANDING SEAM | | | METAL ROOF AND SHEET S.1 SPECIFIES ASPHALT SHINGLES. | | | PLEASE CLARIFY. | | | | | | 6) SUBMIT TWO SETS OF THE INSTALLATION INSTRUCTIONS FOR | | | THE MASONITE INTERNATIONAL EXTERIOR DOORS (FL 4904-R7). | | | DCA RULE 9N-3 | | | | | | 7) ON SHEET S.2 THE WRONG PRODUCT APPROVAL IS LISTED IN | | | THE SCHEDULE FOR DOOR #3, THE 100 SERIES OUTSWING | | | FRENCH DOORS. IT SHOULD BE NOA NO. 15-0706.03. | | | | | | 8) THE VALUE HAS BEEN INCREASED TO $249,257.00 BASED ON | | | ICC VALUATION DATA. FBC 109.3 | | | | | | 9) A SEPARATE PERMIT, APPLICATION AND REVIEW IS | | | REQUIRED FOR THE DRIVEWAY AND APRON. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-05-02 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-05-02 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-05-02 |
Time |
11:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-07-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-26 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-06 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2016-07-06 14:06:41 | RESUB ROUTED TO ESCHNEID VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-07-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-01 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-13 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2016-06-13 10:40:10 | RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-05-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-24 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-04-21 |
Time |
15:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2016-07-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-26 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-26 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2016-07-26 15:51:24 | MU 2016-16866, NO FEES WERE DUE. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2016-07-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-01 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-01 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2016-07-01 16:58:18 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-23 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-23 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2016-05-23 14:10:32 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-23 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-23 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-05-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-05-02 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-05-02 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2016-07-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-07-26 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-07-26 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2016-07-26 15:45:09 | ROOFING MATERIALS | | | -GAF ASPHALT SHINGLES FL#10124.1 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-07-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-07-26 |
Time |
10:22 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2016-07-26 |
Time |
10:22 |
Sent To |
B |
|
| Notes |
| 2016-07-26 10:57:01 | THIS PLANS WITH THIS PERMIT ARE FOR THE FENCE AND | | | DRIVEWAY PERMITS AS WELL. ZONING DID NOT PASS FENCE | | | PERMIT, SO PLANS MAY NOT BE ISSUED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2016-06-17 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-06-17 |
Time |
17:39 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2016-06-17 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2016-06-17 17:39:06 | FAILED | | | | | | 1) THE PROPOSED SITE PLAN ON SHEET S.1 SHOWS THE HOUSE | | | HAVING SETBACKS OF 9 FEET 2 INCHES AND 7 FEET 6 INCHES. | | | THE SURVEY SITE PLAN SHOWS THE HOUSE HAVING 8 FEET 3 | | | INCHES ON BOTH SIDES OF THE HOUSE. ALL PLANS SHALL SHOW | | | THE SAME CONDITIONS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-05-13 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-05-13 |
Time |
08:47 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2016-05-12 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2016-05-13 08:54:42 | FAILED | | | | | | 1) THE PROPOSED PLAN VIEW ON SHEET S.2 SHALL SHOW THE | | | DIMENSIONS OF THE A/C PAD AND THE A/C. | | | | | | 2) THE PROPOSED SITE PLAN ON SHEET S.1 SHALL SHOW THE | | | SETBACK DIMENSION FROM THE PROPERTY LINE TO THE A/C | | | PAD. THE A/C PAD SHALL BE NO CLOSER THAN 4 FEET 4 | | | INCHES FROM THE PROPERTY LINE. | | | | | | 3) ZONING WILL NOT APPROVE THIS PERMIT UNTIL A | | | LANDSCAPE PERMIT HAS BEEN SUBMITTED. | | | | | | 4) THE LANDSCAPE, IRRIGATION, FENCE AND DRIVEWAY | | | REQUIRE SEPARATE PERMITS, WITH PLANS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|