Plan Review Details - Permit 16040935
Plan Review Stops For Permit 16040935
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-17 Cont ID  
Sent By skennedy Date 2016-05-17 Time 12:11 Rev Time 0.00
Received By skennedy Date 2016-05-17 Time 12:11 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By shill Date 2016-05-04 Time 10:57 Rev Time 0.00
Received By shill Date 2016-05-04 Time 10:57 Sent To  
Notes
2016-05-04 10:59:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE STRUCTURAL DRAWING PREPARED BY JC KOSINSKI
 ENGINEERING INC REFERS TO ASCE7-05. SEE FBC 2014
 RESIDENTIAL CHAPTER 46; THE CURRENT STANDARD IS
 ASCE7-10. ALTHOUGH IT IS UNLIKELY TO AFFECT THE DESIGN
 OF THIS JOB, PLEASE UPDATE THE REFERENCE.
  
 NOTE THAT, IF THIS HAD PASSED ELECTRICAL REVIEW, THIS
 REVIEW WOULD HAVE BEEN PASSED WITH PROVISO.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-18 Cont ID  
Sent By mvaldes Date 2016-05-18 Time 10:50 Rev Time 0.00
Received By mvaldes Date 2016-05-18 Time 10:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-21 Cont ID  
Sent By mvaldes Date 2016-04-21 Time 12:17 Rev Time 0.00
Received By mvaldes Date 2016-04-21 Time 11:24 Sent To  
Notes
2016-04-21 12:42:49JOB PERMIT NUMBER: 16040935
 JOB ADDRESS: 512 ONTARIO PLACE
 WEST PALM BEACH 33409
 DATE: APRIL 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - PLANS MUST BE SIGN AND SEALED BY DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DRAWING.WPBA 107.2.1
 - CLARIFY TAP CONDUCTOR LENGTH AND MECHANICAL /
 ELECTRICAL CONNECTION IN THE MDP PANEL ? IT SEEMS TO BE
 A SERVICE TAP BEFORE THE MAIN IF SO THE PV DISCONNECT
 MUST BE SERVICE RATED WITH A NEUTRAL TO CASE BOND
 CONNECTION TO FACILITATE THE EFFECTIVE GROUNDING PATH.
 NEC 250 , 230 , 225 , 240.21
 - IDENTIFY PV SOURCE CIRCUIT CONDUCTOR TYPE & SIZE AS
 WELL AS COMBINER ENCLOSURE RATING AND MAKE SURE ALL
 EQUIPMENT IS LISTED FOR SOLAR APPLICATIONS. NEC 690
 - PROVIDE A SITE SPECIFIC PLAN SHOWING ALL ELECTRICAL
 AND SOLAR EQUIPMENT AS IT RELATES TO EACH OTHER. WPBA
 107
 - MAKE A NOTE REFERENCING THAT CONDUCTOR BUNDLING
 ADJUSTMENT FACTORS PLUS ROOFTOP DERATING DEMANDS WERE
 TAKEN INTO CONSIDERATION WHEN SIZING OF PV INPUT ,
 OUTPUT , SOURCE , ARRAY CIRCUITS. NEC 310.15B3(A) &
 310.15B3(C)
 - ON A INTERGRADED GRID TIED SYSTEM A EC CONTRACTOR IS
 REQUIRED FOR THE CONNECTIONS TO THE BUILDING PREMISES
 WIRING PER FLORIDA STATUE 61G4-15.021. ( ELECTRICAL SUB
 PERMIT REQUIRED )
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-18 Cont ID  
Sent By mvaldes Date 2016-05-18 Time 10:50 Rev Time 0.00
Received By mvaldes Date 2016-05-17 Time 12:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-04 Cont ID  
Sent By shill Date 2016-05-04 Time 10:59 Rev Time 0.00
Received By shill Date 2016-04-20 Time 10:13 Sent To  
Notes
2016-05-04 10:54:385/4 TO MISC 2
  
2016-04-21 10:13:48ROUTED TO ELECTRICAL INBOX