Plan Review Details - Permit 16040915
Plan Review Stops For Permit 16040915
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-12-30 Cont ID  
Sent By jgomez Date 2016-12-30 Time 11:36 Rev Time 0.00
Received By jgomez Date 2016-12-30 Time 11:36 Sent To  
Notes
2016-12-27 17:01:56 
  
 NOTE: REVISION FEES ARE NO PAID. NEED TO PAY REVISION
 FEES FOR FURTHER REVIEW.
  
  
  
 RESIDENTIAL (R3) FRONT BUILDING REVISION, THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED A FOUR TIMES THE PLAN
 REVIEW FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE
 FLORIDA STATUTE 553.80(2)(B).
  
 1- STEEL SHOP DRAWINGS SUBMITTED FROM JAMES F. GIAGI,
 P.E. DON'T MATCH STRUCTURAL DRAWINGS SHOWN BY THE
 ENGINEER OF RECORD DONALD M. DIXON. STRUCTURAL ENGINEER
 OF RECORD SHOWS TWO C10X20 STEEL CHANNELS RESTING ON
 EXISTING DOUBLE WOOD PLATES. STEEL SHOP DRAWINGS SHOW
 ONE W10X60 RESTING ON STEEL COLUMNS AND CORRESPONDING
 FOOTING. STEEL SHOP DRAWINGS SEEM TO BE MORE
 STRUCTURALLY SOUND. STRUCTURAL ENGINEER OF RECORD TO
 PROVIDE STRUCTURAL ANALYSIS OF ALL THE FRAMING MEMBERS
 SHOWING THE COMPLETE LOAD PATH OF THE PROPOSED STEEL
 BEAM. AND, PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR ALL FRAMING MEMBERS. SEC. R301.1 FBC-RESIDENTIAL-
 5TH EDITION, (2014).
  
 2- ENGINEER OF RECORD REVISED THE WIND DESIGN
 INFORMATION ON SHEET A1. CLARIFY WHY THE DESIGN WIND
 SPEED WAS REVISED FROM 175 MPH TO 140 MPH?. IS THIS THE
 ULTIMATE WIND LOAD OR THE NOMINAL WIND LOAD. IT IS NOT
 CLEAR. REVISE AS REQUIRED. SEC. R301.2.1.3
 FBC-RESIDENTIAL.
  
 3- NOTE #1 OF GENERAL SCOPE OF WORK ON SHEET A1 NOW
 SPECIFIES "DEMOLISH ENTIRE REMAINS OF THE FIRE DAMAGED
 ROOF AND INSTALL TOTALLY NEW ROOF". DRAWINGS SUBMITTED
 DON'T PROVIDE ANY DETAILS AND SPECIFICATIONS. COMPLETE
 FRAMING DETAILS AND SPECIFICATIONS FOR THE
 RE-CONSTRUCTION OF THE DAMAGED ROOF. SEC. R301.1
 FBC-RESIDENTIAL.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS. (NEED HISTORIC
 APPROVAL).
  
 B) ROOF TO BE INSTALLED. COORDINATE WITH ITEM #3 ABOVE.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE ROOF PRODUCT APPROVAL
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT
 OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-03 Cont ID  
Sent By jgomez Date 2016-11-03 Time 17:25 Rev Time 0.00
Received By jgomez Date 2016-11-03 Time 14:33 Sent To P
Notes
2016-11-03 14:34:28RESIDENTIAL (R3) FRONT BUILDING REVISION, SECOND
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER MAY BE CHARGED A FOUR TIMES THE PLAN REVIEW
 FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE FLORIDA
 STATUTE 553.80(2)(B).
  
 1- THE NEW A/C CLOSET ON THE SECOND FLOOR IS REDUCING
 THE WIDTH OF THE STAIRS. THIS IS NOT ALLOWED. SEC.
 701.2 FBC-EXISTING BUILDING, 5TH EDITION (2014). REVISE
 AS REQUIRED.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- SCOPE OF WORK IS NOT CLEAR. PROVIDE WALL LEGEND AND
 CLEARLY IDENTIFY ON PLANS WHICH ARE THE EXISTING WALLS
 TO BE DEMOLISHED, WHICH WALLS ARE EXISTING TO REMAIN
 AND WHICH WALLS ARE NEW. SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- NEW A/C CLOSET ON THE SECOND FLOOR ABOVE THE
 STAIRWAY. PROVIDE DETAIL/SPECS SHOWING COMPLIANCE WITH
 THE STAIRWAY HEADROOM SEC. R311.7.2 FBC-RESIDENTIAL,
 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- A) REVISE DOOR AND WINDOW SCHEDULE AND FLOOR PLANS.
 ALL WINDOWS AND DOORS SHOWN ON PLANS ARE DENOMINATED AS
 "A". THIS IS INCORRECT. COORDINATE INFORMATION SHOWN ON
 PLANS WITH DOOR AND WINDOW SCHEDULE. CLARIFY SIZE OF
 EXTERIOR DOORS. SEC. 107.2.1 CITY AMENDMENTS. AND,
 CLEARLY IDENTIFY WHICH DOORS AND WINDOWS ARE GOING TO
 BE REPLACED.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 (SPECIALLY BEDROOM WINDOWS) AND SIZE AND TYPE OF
 PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH THE BEDROOM
 EGRESS REQUIREMENTS OF SEC. 704 OF FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
 NOTE: DOOR AND WINDOW SCHEDULE SPECIFIES WINDOW TYPE
 "A" AS "(2)SH 24SH". 2 WINDOWS OF THIS SIZE DON'T FIT
 ON THE OPENINGS SHOWN ON PLANS. REVISE AS REQUIRED.
 ALSO, KEEP IN MIND THAT 24 SINGLE HUNG WINDOWS DON'T
 COMPLY WITH EGRESS, SPECIALLY FOR THE SECOND FLOOR.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS.
 RESPONSE:
 DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL14569 DON'T MEET THE DESIGN PRESSURES CALCULATED BY
 THE ENGINEER OF RECORD. NEED TO PROVIDE PRODUCT
 APPROVAL FOR DOORS THAT MEET THE CALCULATED DESIGN
 PRESSURES. SEE ENGINEER DRAWING A1 OF 4.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- SHEET A1: CLARIFY WHAT'S FEBC CLASS OF WORK?,
 ALTERATION LEVEL 11? SPECIFIED ON THE SPECIAL NOTES.
 NOTE: ACCORDING TO SEC. 505 FBC-EXISTING BUILDING, THIS
 IS ALT. LEVEL 3. REVISE INFORMATION ON PLANS AS
 REQUIRED.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT
 OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-27 Cont ID  
Sent By jgomez Date 2016-05-27 Time 13:46 Rev Time 0.00
Received By jgomez Date 2016-05-27 Time 13:46 Sent To  
Notes
2016-05-27 13:50:21RESIDENTIAL (R3) ADDITION/ REVISION TO FRONT BUILDING
 MASTER #15070950
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT FOR
 THE NEW ADDITION. BRING BACK COUNTY STAMPED PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW FOR THE ADDITIONAL SCOPE OF WORK (ADDITION AND
 COMPLETE REMODELING OF THE HOUSE). VALUATION TO INCLUDE
 ALL LABOR, MATERIALS CONTRACTOR'S OVERHEAD AND PROFIT
 AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED TO +/-
 #50,000. THE PERMIT FEE BALANCE IS $3637.50. THIS
 INCLUDES THE 4X FEE FOR WORK WITHOUT PERMIT.
  
 3- SCOPE OF WORK IS NOT CLEAR. PROVIDE WALL LEGEND AND
 CLEARLY IDENTIFY ON PLANS WHICH ARE THE EXISTING WALLS
 TO BE DEMOLISHED, WHICH WALLS ARE EXISTING TO REMAIN
 AND WHICH WALLS ARE NEW. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- A) IT LOOKS LIKE THERE IS A NEW A/C CLOSET ON THE
 SECOND FLOOR ABOVE THE STAIRWAY. PROVIDE DETAIL/SPECS
 SHOWING COMPLIANCE WITH THE STAIRWAY HEADROOM SEC.
 R311.7.2 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) THE NEW A/C CLOSET IS REDUCING THE WIDTH OF THE
 STAIRS. THIS IS NOT ALLOWED. SEC. 701.2 FBC-EXISTING
 BUILDING, 5TH EDITION (2014). REVISE AS REQUIRED.
  
 5- A) REVISE DOOR AND WINDOW SCHEDULE AND FLOOR PLANS.
 ALL WINDOWS AND DOORS SHOWN ON PLANS ARE DENOMINATED AS
 "A". THIS IS INCORRECT. COORDINATE INFORMATION SHOWN ON
 PLANS WITH DOOR AND WINDOW SCHEDULE. CLARIFY SIZE OF
 EXTERIOR DOORS. SEC. 107.2.1 CITY AMENDMENTS. AND,
 CLEARLY IDENTIFY WHICH DOORS AND WINDOWS ARE GOING TO
 BE REPLACED.
  
 B) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 (SPECIALLY BEDROOM WINDOWS) AND SIZE AND TYPE OF
 PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH THE BEDROOM
 EGRESS REQUIREMENTS OF SEC. 704 OF FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
 NOTE: DOOR AND WINDOW SCHEDULE SPECIFIES WINDOW TYPE
 "A" AS "(2)SH 24SH". 2 WINDOWS OF THIS SIZE DON'T FIT
 ON THE OPENINGS SHOWN ON PLANS. REVISE AS REQUIRED.
 ALSO, KEEP IN MIND THAT 24 SINGLE HUNG WINDOWS DON'T
 COMPLY WITH EGRESS, SPECIALLY FOR THE SECOND FLOOR.
  
 6- TYPICAL WALL SECTION ON SHEET A2:
 A) REVISE TYPICAL WALL SECTION AND FOOTING SIZE IN
 FOUNDATION SCHEDULE ON SHEET A2 TO SHOW COMPLIANCE WITH
 THE 6" CLEARANCE REQUIRED BY SEC. R404.1.6
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 NOTE: SIZE OF FOOTING SHOWN ON THE TYPICAL WALL SECTION
 DOESN'T MATCH SIZE SHOWN ON THE FOUNDATION SCHEDULE.
 COORDINATE SIZE WITH THE REQUIRED 6" CLEARANCE.
  
 B) CLARIFY IF THIS IS A TYP. WALL SECTION FOR THE NEW
 ADDITION WHY IT SAYS EXISTING GALV. MTL DRIP, EXISTING
 STRAP @ EA, RAFTER, ETC. REVISE AS REQUIRED. CLEARLY
 SPECIFY ALL NEW MATERIALS AND CONNECTORS. SEC. 107.2.1
 CITY AMENDMENTS.
  
 C) SPECIFY ROOF PITCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) CLARIFY WALL STUD SIZE. THERE ARE SPECIFICATIONS FOR
 2 X4 STUDS AND 2X6 STUDS. SEC. 107.2.1 CITY AMENDMENTS.
  
 E) SPECIFY CEILING FINISH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 F) SPECIFY INSULATION LOCATION AND R-VALUE. NOTE: R-30
 INSULATION DOESN'T FIT ON 2X10 ROOF JOIST. IT DOESN'T
 ALLOW THE 1" AIR GAP FOR ROOF CROSS VENTILATION. R806.3
 FBC-RESIDENTIAL.
  
 G) SPECIFY 7/8" STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1) FBC-RESIDENTIAL.
  
 H) PROVIDE COMPLETE SIZE SPECIFICATIONS FOR ANCHOR BOLT
 THAT IS CONNECTING THE 2X BOTTOM WOOD PLATE TO THE
 CONCRETE FOOTING. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- ROOF FRAMING PLAN ON SHEET A2:
 A) SPECIFY CONNECTOR "B" SHOWN ON THE ROOF FRAMING
 PLAN. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) PROVIDE DETAIL AND SPECIFICATIONS (SIZE AND
 ANCHORING) FOR LEDGER LOCATED AT THE NEW PARAPET WALL
 AND SUPPORTING THE 2X10 ROOF JOISTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE NEW PARAPETS, INCLUDING THE ONE
 LOCATED BETWEEN THE EXISTING HOUSE AND NEW ADDITION.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOORS (SINGLE AND DOUBLE) AS SHOWN ON
 PLANS. FLORIDA PRODUCT APPROVAL FL13540-R3 SUBMITTED IS
 NOT LEGIBLE. PROVIDE CLEAR AND LEGIBLE COVER PAGES AND
 DRAWINGS. AND, MAKE SURE DOOR MEETS THE DESIGN
 PRESSURES RESIST THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER OF RECORD.
  
 B) ROOF MATERIAL TO BE INSTALLED ON NEW ADDITION. IS
 THIS A LOW SLOPE ROOF?. THEN, CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES
 AND IT ALLOWS TO DO NAIL ENHANCEMENT.
  
 C) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 BY THE ENGINEER ON PLANS AND DETAILS. PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR ENGINEER TO LIST THE FLORIDA
 PRODUCT APPROVAL NEXT TO EACH SPECIFIED CONNECTOR.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- SHEET A1: CLARIFY WHAT'S FEBC CLASS OF WORK?,
 ALTERATION LEVEL 11? SPECIFIED ON THE SPECIAL NOTES.
 NOTE: ACCORDING TO SEC. 505 AND SEC. 507 FBC-EXISTING
 BUILDING, THIS IS ALT. LEVEL 3 AND ADDITION. REVISE
 INFORMATION ON PLANS AS REQUIRED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS..
 ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT
 OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-03 Cont ID  
Sent By rlecky Date 2017-01-03 Time 14:27 Rev Time 0.00
Received By rlecky Date 2017-01-03 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-11-01 Cont ID  
Sent By rlecky Date 2016-11-01 Time 14:09 Rev Time 0.00
Received By rlecky Date 2016-11-01 Time 12:14 Sent To  
Notes
2016-11-01 14:10:49TUESDAY, NOVEMBER 01, 2016
  
 16040915
 354 MARLBOROUGH ST.
 SF REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS. ALSO NOTE THAT THE PREVIOUS
 ELECTRICAL COMMENTS FROM 4/27/2016 STILL NEED TO BE
 ADDRESSED WITHIN THE GENERAL NOTES.
  
 PROVIDE THE LOCATION OF THE ELECTRIC SERVICE, MAIN
 DISCONNECT AND PANEL BOARD. NEC 230.70, FBC R E3601.6.2
  
 VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC
 406.2; FBC R E4002.14
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
 SHOW THE LOCATION OF THE WATER HEATER AND DISCONNECT.
 THE WATER HEATER REQUIRES A DISCONNECT LOCATED WITHIN
 SIGHT OF THE WATER HEATER OR A LOCKABLE DISCONNECT. NEC
 422.30 FBC R E4101.5
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-27 Cont ID  
Sent By mvaldes Date 2016-04-27 Time 16:37 Rev Time 0.00
Received By albarran Date 2016-04-27 Time 12:53 Sent To  
Notes
2016-04-27 16:44:03FAILED 2ND ELECTRICAL REVIEW
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 1. YOUR GENERAL NOTES SECTION ON NOTE 7 INDICATES THAT
 ALL CONDUCTORS SHALL BE THHN. PLEASE NOTE THAT IT IS
 NOT CONDUCTOR GAUGE BUT THE AMBIENT CONDITIONS WHICH
 DETERMINE CONDUCTOR INSULATION, HENCE: WET OR DRY
 LOCATIONS.
 2. NEC 404.2(C). WHERE SWITCHES CONTROLLING LIGHTING
 LOADS SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE
 GROUNDED BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED
 LIGHTING CIRCUIT SHALL BE PROVIDED AT THE SWITCH.
 3. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 4. NEC 406.12 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT,
 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
 5. IDENTIFY THE LOCATION OF THE ELECTRIC WATER HEATER
 ON THE PLANS.
 6. NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT.
 OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. THIS
 REFERS PRIMARILY TO THE AREA BELOW THE FIRST FLOOR
 STAIRS OR ALONG THAT SAME WALL.
 7. NEC 210.52(H). IN DWELLING UNITS, HALLWAYS OF 10 FT
 OR MORE IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE
 OUTLET.
 8. NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 9. FBC-R402.4.4. RECESSED LIGHTING INSTALLED IN THE
 BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED &
 UNCONDITIONED SPACES.
 10. FBC-R404.1 A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2017-01-12 Cont ID  
Sent By destabro Date 2017-01-12 Time 09:49 Rev Time 0.00
Received By destabro Date 2017-01-12 Time 09:49 Sent To B
Notes
2017-01-12 09:54:421/12/2017 - NEW PLANS DETAIL HORIZONTAL SLIDER WINDOWS
 FOR THE SECOND FLOOR (EAST, FRONT) ELEVATION NOT
 PREVIOUSLY APPROVED. PLEASE CHANGE TO MATCH SINGLE AND
 PAIRED SHS WINDOWS FOUND ON OTHER ELEVATIONS. ALSO, THE
 PREVIOUSLY REQUESTED APPLIED MUNTIN DETAIL HAS BEEN
 REMOVED FROM THE WINDOW SCHEDULE. REPLACEMENT WINDOW
 PRODUCTS SHOULD MATCH THE 6/6-LIGHT COLONIAL GRID WHITE
 FRAME ALUMINUM PRODUCTS PREVIOUSLY APPROVED OCTOBER 25,
 2016. MUNTINS SHOULD HAVE OGEE RAISED PROFILE AND BE
 APPLIED TO THE EXTERIOR. DLE
2016-12-27 16:53:09NEW REVISED PLANS AND PRODUCT APPROVALS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-10-28 Cont ID  
Sent By destabro Date 2016-10-28 Time 13:06 Rev Time 0.00
Received By destabro Date 2016-10-28 Time 13:06 Sent To B
Notes
2016-10-28 13:09:5610/28/16 - CONDITIONAL APPROVAL. THIS IS A CONTRIBUTING
 PROPERTY TO THE PROSPECT PARK/SOUTHLAND PARK HISTORIC
 DISTRICT. SCOPE OF WORK CHANGED TO INTERIOR REMODEL AND
 REPLACEMENT OF NON-HISTORIC WINDOWS ONLY. REPLACEMENT
 WINDOWS MUST UTILIZE CLEAR BUTACITE PVB LAYER ONLY
 (CLEAR GLASS, NO TINTING) AND EXTRUDED ALUMINUM MUNTINS
 WITH RAISED PROFILES FOR THE COLONIAL GRIDS. NO PVC
 INNER GLASS MULLIONS ALLOWED. FAILURE TO ADHERE TO
 GUIDELINES WILL REQUIRE CORRECTION TO WINDOWS AFTER
 INSTALLATION. PLEASE DIRECT QUESTIONS TO DESIREE
 ESTABROOK, HISTORIC PRESERVATION PLANNER, AT
 561.822.1428

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-05-25 Cont ID  
Sent By fmittner Date 2016-05-25 Time 15:29 Rev Time 0.00
Received By destabro Date 2016-05-25 Time 15:29 Sent To  
Notes
2016-05-25 15:30:365/25/16 - GAVE APPLICANT COA APPLICATION 5/13 - NOT YET
 RECEIVED. COA IS NEEDED TO APPROVE REAR ADDITION. DLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-22 Cont ID  
Sent By cpuell Date 2017-02-22 Time 14:46 Rev Time 0.00
Received By cpuell Date 2016-12-06 Time 13:18 Sent To  
Notes
2016-12-07 13:18:33R20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-04 Cont ID  
Sent By gjohnson Date 2016-11-04 Time 13:53 Rev Time 0.00
Received By gjohnson Date 2016-10-20 Time 15:39 Sent To  
Notes
2016-10-24 15:39:52R12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-06 Cont ID  
Sent By hmoser Date 2016-06-06 Time 14:06 Rev Time 0.00
Received By hmoser Date 2016-04-20 Time 12:43 Sent To  
Notes
2016-04-21 12:43:47R11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-11-03 Cont ID  
Sent By jgomez Date 2016-11-03 Time 16:30 Rev Time 0.00
Received By jgomez Date 2016-11-03 Time 16:30 Sent To  
Notes
2016-11-03 16:30:49THE ADDITION WAS REMOVED FROM THE PLANS. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-27 Cont ID  
Sent By jgomez Date 2016-05-27 Time 13:52 Rev Time 0.00
Received By jgomez Date 2016-05-27 Time 13:50 Sent To  
Notes
2016-05-27 13:53:131- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT FOR
 THE NEW ADDITION. BRING BACK COUNTY STAMPED PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-12-30 Cont ID  
Sent By jgomez Date 2016-12-30 Time 14:07 Rev Time 0.00
Received By jgomez Date 2016-12-30 Time 12:11 Sent To  
Notes
2016-12-30 14:07:57RESIDENTIAL (R3) FRONT REVISION, THIRD MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED A FOUR TIMES THE PLAN
 REVIEW FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE
 FLORIDA STATUTE 553.80(2)(B).
  
 ORIGINAL COMMENT:
 1- PLANS NEED TO PROVIDE COMPLIANCE WITH THE BALANCED
 RETURN AIR OF ALL ROOMS AS REQUIRED BY SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE:
 SIZE OF TRANSFER DUCTS SPECIFIED ON SHEET A3 DON'T
 COMPLY WITH SEC. M1602.4 FBC-RESIDENTIAL. BEDROOM #4
 NEEDS AT LEAST 9" DUCT AND BEDROOMS #2 AND #3 NEED AT
 LEAST 10" DUCT. REVISE AS REQUIRED. NOTE: ALSO, REVISED
 BEDROOM # TO MATCH FLOOR PLAN ON SHEET A1. THERE ARE
 ONLY 3 BEDROOMS IN THIS HOUSE NOT 4. REVISE AS
 REQUIRED.
  
  
 ORIGINAL COMMENT:
 2- REVISE THE EQUIPMENT SIZING CALCULATIONS. PLANS WERE
 REVISED TO DISCARD THE ADDITION. EQUIPMENT SIZING
 CALCULATIONS WERE NOT REVISED. NOTE: CALCULATIONS
 SUBMITTED ARE DONE USING OLD SOFTWARE. PROVIDE REVISED
 EQUIPMENT SIZING CALCULATIONS USING CURRENT VERSION OF
 ENERGY SOFTWARE. (OR USE ANY OTHER APPROVED SOFTWARE).
 PLEASE MAKE SURE CALCULATIONS ARE DONE BASED ON THE
 ACTUAL ORIENTATION OF THE BUILDING TO AVOID
 CONFLICTS/DELAYS. SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. REVISED CALCULATIONS
 WERE NOT RE-SUBMITTED.
  
  
 ORIGINAL COMMENT:
 3- EQUIPMENT LISTED ON THE A/C PLAN SUBMITTED DOESN'T
 MATCH EQUIPMENT LISTED IN THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED. SEC. R403.6.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 RESPONSE:
 THIS CAN NOT BE REVIEWED AT THIS TIME BECAUSE REVISED
 EQUIPMENT SIZING CALCULATIONS WERE NOT SUBMITTED.
  
  
 NOTE: PROVIDE AHRI CERTIFICATE FOR FINAL INSPECTION.
  
  
 ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT
 OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-04 Cont ID  
Sent By jgomez Date 2016-11-04 Time 08:10 Rev Time 0.00
Received By jgomez Date 2016-11-04 Time 07:44 Sent To P
Notes
2016-11-04 08:21:26RESIDENTIAL (R3) FRONT REVISION, SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER MAY BE CHARGED A FOUR TIMES THE PLAN REVIEW
 FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE FLORIDA
 STATUTE 553.80(2)(B).
  
 1- PLANS NEED TO PROVIDE COMPLIANCE WITH THE BALANCED
 RETURN AIR OF ALL ROOMS AS REQUIRED BY SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- REVISE THE EQUIPMENT SIZING CALCULATIONS. PLANS WERE
 REVISED TO DISCARD THE ADDITION. EQUIPMENT SIZING
 CALCULATIONS WERE NOT REVISED. NOTE: CALCULATIONS
 SUBMITTED ARE DONE USING OLD SOFTWARE. PROVIDE REVISED
 EQUIPMENT SIZING CALCULATIONS USING CURRENT VERSION OF
 ENERGYGAUGE SOFTWARE. (OR USE ANY OTHER APPROVED
 SOFTWARE). PLEASE MAKE SURE CALCULATIONS ARE DONE BASED
 ON THE ACTUAL ORIENTATION OF THE BUILDING TO AVOID
 CONFLICTS/DELAYS. SEC. R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 3- EQUIPMENT LISTED ON THE A/C PLAN SUBMITTED DOESN'T
 MATCH EQUIPMENT LISTED IN THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED. SEC. R403.6.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- A/C PLAN SUBMITTED SHOWS A/C CONDENSER UNIT ON TOP
 OF THE FLAT ROOF. PACKAGE UNIT MOUNTING DETAIL PROVIDED
 DOESN'T APPLY TO UNITS MOUNTED ON A FLAT ROOF. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE PROPOSED
 MOUNTING LOCATION. SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 NOTE: PROVIDE AHRI SHEETS FOR FINAL INSPECTION.
  
  
 ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT
 OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-06 Cont ID  
Sent By hmoser Date 2016-06-06 Time 14:06 Rev Time 0.00
Received By hmoser Date 2016-06-06 Time 12:41 Sent To  
Notes
2016-06-06 14:06:27PLAN DENIED
 1) REFER TO SECTION M1602.3 BALANCED RETURN AIR.
 2014 RESIDENTIAL CODE
 2) PROVIDE AHRI SHEETS FOR FINAL INSPECTION.
 3) EQUIPMENT ON PLAN AND SIZING CALCULATION
 DO NOT MATCH . 107 FBC 2014
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-01-13 Cont ID  
Sent By gjohnson Date 2017-01-13 Time 17:27 Rev Time 0.00
Received By gjohnson Date 2017-01-13 Time 17:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-11-04 Cont ID  
Sent By gjohnson Date 2016-11-04 Time 13:49 Rev Time 0.00
Received By gjohnson Date 2016-11-04 Time 13:49 Sent To  
Notes
2016-11-04 13:53:431ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 1. CLEAN OUT REQUIRED AT THE BASE OF THE STACKS. PER
 FBC RES P3005.2.6 BASE OF STACKS.
 A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE
 OR SOIL STACK.
  
 2. SHOW LOCATION OF WATER HEATER. PER WPB AMEND TO FBC
 107.2.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By tklarge Date 2016-05-04 Time 12:38 Rev Time  
Received By gearl Date 2016-05-04 Time   Sent To  
Notes
2016-05-04 12:40:13 
  
  
 1. NEED TO SUBMIT PLUMBING RISER DIAGRAM 107.3.5.1
 MINIMUN PLAN REVIEW / PLUMBING
  
  
 GEORGE EAL PLUMBING PLANS REVIEWER 0013B

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-11-03 Cont ID  
Sent By jgomez Date 2016-11-03 Time 17:44 Rev Time 0.00
Received By jgomez Date 2016-11-03 Time 17:44 Sent To  
Notes
2016-11-03 17:45:45THE ADDITION WAS DISCARDED. NO ROOFING PERMIT REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-05-27 Cont ID  
Sent By jgomez Date 2016-05-27 Time 13:50 Rev Time 0.00
Received By jgomez Date 2016-05-27 Time 13:50 Sent To B
Notes
2016-05-27 13:52:411- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ROOFING TO
 BE INSTALLED.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING,
 NOT SIGNING AND SEALING PRODUCT APPROVAL.

Review Stop Z ZONING
Rev No 3 Status P Date 2017-01-18 Cont ID  
Sent By destabro Date 2017-01-18 Time 08:31 Rev Time 0.00
Received By destabro Date 2017-01-18 Time 08:31 Sent To B
Notes
2017-01-17 09:43:47ROUTED TO DESIREE ESTABROOK
2016-12-27 16:53:23NEW REVISED PLANS AND PRODUCT APPROVALS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-28 Cont ID  
Sent By destabro Date 2016-10-28 Time 13:06 Rev Time 0.00
Received By destabro Date 2016-10-28 Time 13:06 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-25 Cont ID  
Sent By fmittner Date 2016-05-25 Time 15:30 Rev Time 0.00
Received By destabro Date 2016-05-25 Time 15:30 Sent To  
Notes
***NONE***