Plan Review Details - Permit 16040854
Plan Review Stops For Permit 16040854
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-23 Cont ID  
Sent By shill Date 2016-05-23 Time 13:30 Rev Time 0.00
Received By shill Date 2016-05-23 Time 13:30 Sent To  
Notes
2016-05-23 13:30:555/26/15 CONFIRMED VIA EMAIL THAT UNITY OF TITLE
 APPLICATION WAS SUBMITTED THROUGH ENGINEERING
 DEPARTMENT PER VINCE NOEL
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By jwitmer Date 2016-05-05 Time 07:19 Rev Time 0.00
Received By jwitmer Date 2016-05-05 Time 06:26 Sent To  
Notes
2016-05-05 07:19:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040854
 ADD: 1200 S. FLAGLER DR. 1703 & 1704
 CONT: CAMBRIDGE
 TEL: 561-248-5266
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 05/2016
 ACTION: DENIED
  
 1) SHEET A-1 INDICATES WORK IS BEING COMPLETED NOT IN
 ONE UNIT BUT IN (2) UNITS COMBINING THE TWO UNITS INTO
 ONE UNIT. A UNITY OF TITLE IS REQUIRED. THE PROPOSED
 BUILDING STRUCTURE TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM 'THE SITE'. A
 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF
 TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 2) SHEET A2 INDICATES NEW EXTERIOR SLIDING GLASS DOORS
 ARE TO BE INSTALLED. PLEASE SHOW COMPLIANCE WITH: 2014
 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) COMPONENTS & CLADDING. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 4) FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.6)
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By mvaldes Date 2016-06-01 Time 13:17 Rev Time 0.00
Received By mvaldes Date 2016-06-01 Time 13:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-21 Cont ID  
Sent By mvaldes Date 2016-04-21 Time 18:41 Rev Time 0.00
Received By mvaldes Date 2016-04-21 Time 18:05 Sent To  
Notes
2016-04-21 18:43:22JOB PERMIT NUMBER: 16040854
 JOB ADDRESS: 1200 S FLAGLER DRIVE
 WEST PALM BEACH FLORIDA
 DATE: APRIL 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 - NEC 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT,
 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
 - NEC 404.2C SWITCHES CONTROLLING LIGHTING LOADS
 SUPPLIED BY A GROUNDED GENERAL PURPOSE BRANCH CIRCUIT,
 THE GROUNDED CIRCUIT CONDUCTOR FOR THE CONTROLLED
 LIGHTING CIRCUIT SHALL BE PROVIDED AT THE SWITCH
 LOCATION.
 - NEC 210.52(E)(3) BALCONIES GREATER THAN 20 SQ. FT.
 SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET INSTALLED
 WITHIN THE PERIMETER OF THE BALCONY.
 - MISSING SMOKE DETECTORS IN NEW LIVING ROOM , NEW
 DINING ROOM , NEW DEN , NEW OFFICE , ALL ALARMS MUST BE
 INTERCONNECTED PER RESIDENTIAL CODE SECTIONS 314 & 315
 PLUS NFPA 72 CHAPTER 29.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-20 Cont ID  
Sent By pleduc Date 2016-05-20 Time   Rev Time 0.00
Received By pleduc Date 2016-05-19 Time 17:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-27 Cont ID  
Sent By pleduc Date 2016-04-27 Time   Rev Time 0.00
Received By pleduc Date 2016-04-27 Time 10:15 Sent To  
Notes
2016-04-27 12:04:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NOT INDICATION OF COMPLIANCE WITH ANY FIRE
 CODE NOTED ON ANY PLAN SHEET. PLEASE PROVIDE NOTE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) THERE IS NO INDICATION OF EXISTING FIRE ALARM OR
 FIRE SPRINKLER SYSTEMS. PLEASE PROVIDE NOTE.
  
 IF EITHER SYSTEM IS EXISTING.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRE AN EVALUATION BY A CERTIFIED LIFE SAFTEY
 CONTRACTOR.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 3) THERE IS NO INDICATION OR LOCATION OF ANY EXISTING
 OR NEW SMOKE DETECTION/ALARMS. PLEASE PROVIDE
 INCOMPLIANCE WITH THE ABOVE NOTED CODES.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2016-05-17 Time 14:46 Sent To  
Notes
2016-05-17 14:47:01B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-17 Cont ID  
Sent By lmarchan Date 2016-05-17 Time 14:46 Rev Time 0.00
Received By lmarchan Date 2016-04-19 Time 12:50 Sent To  
Notes
2016-04-20 12:51:06B09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-05 Cont ID  
Sent By jwitmer Date 2016-05-05 Time 07:19 Rev Time 0.00
Received By jwitmer Date 2016-05-05 Time 06:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-05-24 Cont ID  
Sent By ccole Date 2016-05-24 Time 09:31 Rev Time 0.00
Received By ccole Date 2016-05-24 Time 09:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-22 Cont ID  
Sent By ccole Date 2016-04-22 Time 08:11 Rev Time 0.00
Received By ccole Date 2016-04-22 Time 08:10 Sent To  
Notes
2016-04-22 08:13:001ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040854
 4/22/16
  
 1) PROVIDE MECHANICAL PLANS INDICATING ALL REQUIRED
 ALTERATIONS TO THE EXISTING HVAC SYSTEMS TO ACCOMODATE
 THE JOINING OF THE TWO UNITS INTO ONE.
 2) PROVIDE AC CHANGE OUT FORMS FOR THE THE REPLACED
 SYSTEM I N UNIT #1703.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-23 Cont ID  
Sent By gjohnson Date 2016-05-23 Time 09:11 Rev Time 0.00
Received By gjohnson Date 2016-05-23 Time 09:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-29 Cont ID  
Sent By tklarge Date 2016-04-29 Time 06:06 Rev Time 0.00
Received By tklarge Date 2016-04-29 Time 05:55 Sent To  
Notes
***NONE***