Plan Review Details - Permit 16040741
| Plan Review Stops For Permit 16040741 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-01-26 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-01-26 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-01-17 |
Time |
13:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-12-15 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-11-29 |
Time |
08:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-08-01 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-08-01 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-06-27 |
Time |
09:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-01-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-01-26 |
Time |
06:44 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-01-26 |
Time |
05:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-12-15 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-12-15 |
Time |
03:58 |
Sent To |
|
|
| Notes |
| 2016-12-15 09:24:56 | | | | 1) SUBMIT MSDS DATA FOR THE CHEMICALS USED FOR THE ACID | | | INJECTION SYSTEM FOR THE IRRIGATION SYSTEM.FBC 107.2.1. | | | 2) SHT. IR1.00 - THE NOTES ON THIS SHEET ARE ILLEGIBLE. | | | SUBMIT A SHEET WITH CLEAR AND LEGIBLE DETAILS AND | | | NOTES. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) PROVIDE MATCH LINES ON SHEETS IR1.06, IR1.07, | | | IR1.08, IR1.11 & IR1.12. | | | 4) SHT. IR1.10 REFERS TO CIVIL DRAWINGS FOR | | | INFORMATION/LOCATION ON THE LAKE AUTOMATIC VALVE. | | | SUBMIT THIS CIVIL SHEET FOR REFERENCE. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-07-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-07-26 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-07-26 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2016-07-26 17:33:15 | 1ST REVIEW | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENT: | | | | | | 1. SHEETS 1.02/1.06/1.11/1.12 EACH CONTROLLER IS | | | REQUIRED TO HAVE A RAIN SENSOR. PER FAC | | | 40C-2.042(2)(A)5. | | | | | | 2.SHT. IR 1.02 HAS A NOTE CONNECT TO POTABLE WATER | | | SYSTEM FOR AGILITY FIELD IRR YOU SHALL PROVIDE A | | | BACKFLOW FOR ANY CONNECTIONS TO POTABLE WATER SYSTEM. | | | PER FBC PL 608.16.5 CONNECTIONS TO LAWN IRRIGATION | | | SYSTEMS. | | | THE POTABLE WATER SUPPLY TO LAWN IRRIGATION SYSTEMS | | | SHALL BE PROTECTED AGAINST BACKFLOW BY AN ATMOSPHERIC | | | VACUUM BREAKER, A PRESSURE VACUUM BREAKER ASSEMBLY OR A | | | REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION | | | ASSEMBLY. VALVES SHALL NOT BE INSTALLED DOWNSTREAM FROM | | | AN ATMOSPHERIC VACUUM BREAKER. WHERE CHEMICALS ARE | | | INTRODUCED INTO THE SYSTEM, THE POTABLE WATER SUPPLY | | | SHALL BE PROTECTED AGAINST BACKFLOW BY A REDUCED | | | PRESSURE PRINCIPLE BACKFLOW PREVENTION ASSEMBLY. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2017-01-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-01-26 |
Time |
06:45 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-01-26 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2017-01-26 06:45:47 | SIGNATURE VERIFIED. |
|
|
|