Plan Review Details - Permit 16040741
Plan Review Stops For Permit 16040741
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-26 Cont ID  
Sent By lmarchan Date 2017-01-26 Time 09:48 Rev Time 0.00
Received By lmarchan Date 2017-01-17 Time 13:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-15 Cont ID  
Sent By lmarchan Date 2016-12-15 Time 09:41 Rev Time 0.00
Received By lmarchan Date 2016-11-29 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-01 Cont ID  
Sent By lmarchan Date 2016-08-01 Time 16:15 Rev Time 0.00
Received By lmarchan Date 2016-06-27 Time 09:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-01-26 Cont ID  
Sent By tklarge Date 2017-01-26 Time 06:44 Rev Time 0.00
Received By tklarge Date 2017-01-26 Time 05:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-12-15 Cont ID  
Sent By tklarge Date 2016-12-15 Time 09:27 Rev Time 0.00
Received By tklarge Date 2016-12-15 Time 03:58 Sent To  
Notes
2016-12-15 09:24:56 
 1) SUBMIT MSDS DATA FOR THE CHEMICALS USED FOR THE ACID
 INJECTION SYSTEM FOR THE IRRIGATION SYSTEM.FBC 107.2.1.
 2) SHT. IR1.00 - THE NOTES ON THIS SHEET ARE ILLEGIBLE.
 SUBMIT A SHEET WITH CLEAR AND LEGIBLE DETAILS AND
 NOTES. WPB AMEND. TO FBC SEC. 107.2.1.
 3) PROVIDE MATCH LINES ON SHEETS IR1.06, IR1.07,
 IR1.08, IR1.11 & IR1.12.
 4) SHT. IR1.10 REFERS TO CIVIL DRAWINGS FOR
 INFORMATION/LOCATION ON THE LAKE AUTOMATIC VALVE.
 SUBMIT THIS CIVIL SHEET FOR REFERENCE. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By gjohnson Date 2016-07-26 Time 17:08 Rev Time 0.00
Received By gjohnson Date 2016-07-26 Time 17:08 Sent To  
Notes
2016-07-26 17:33:151ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENT:
  
 1. SHEETS 1.02/1.06/1.11/1.12 EACH CONTROLLER IS
 REQUIRED TO HAVE A RAIN SENSOR. PER FAC
 40C-2.042(2)(A)5.
  
 2.SHT. IR 1.02 HAS A NOTE CONNECT TO POTABLE WATER
 SYSTEM FOR AGILITY FIELD IRR YOU SHALL PROVIDE A
 BACKFLOW FOR ANY CONNECTIONS TO POTABLE WATER SYSTEM.
 PER FBC PL 608.16.5 CONNECTIONS TO LAWN IRRIGATION
 SYSTEMS.
 THE POTABLE WATER SUPPLY TO LAWN IRRIGATION SYSTEMS
 SHALL BE PROTECTED AGAINST BACKFLOW BY AN ATMOSPHERIC
 VACUUM BREAKER, A PRESSURE VACUUM BREAKER ASSEMBLY OR A
 REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION
 ASSEMBLY. VALVES SHALL NOT BE INSTALLED DOWNSTREAM FROM
 AN ATMOSPHERIC VACUUM BREAKER. WHERE CHEMICALS ARE
 INTRODUCED INTO THE SYSTEM, THE POTABLE WATER SUPPLY
 SHALL BE PROTECTED AGAINST BACKFLOW BY A REDUCED
 PRESSURE PRINCIPLE BACKFLOW PREVENTION ASSEMBLY.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-01-26 Cont ID  
Sent By tklarge Date 2017-01-26 Time 06:45 Rev Time 0.00
Received By tklarge Date 2017-01-26 Time 06:45 Sent To  
Notes
2017-01-26 06:45:47SIGNATURE VERIFIED.