| Plan Review Stops For Permit 16040736 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-06-30 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-06-30 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2016-06-30 13:33:58 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER ? PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | ACTION: PASSED | | | DATE: 6/30/16 | | | | | | 1. METROPOLITAN DADE COUNTY PRODUCT CONTROL NOTICE OF | | | ACCEPTANCE RECEIVED FOR WINDOWS TO BE RELOCATED. | | | 2. PRODUCT APPROVALS FOR WINDOWS AND DOORS SUBJECT TO | | | WIND LOAD REVIEWED AND APPROVED. | | | 3. PROVISO - PLEASE BE ADVISED THE INSPECTOR MAY | | | REQUIRE PREVIOUSLY COMPLETED WORK TO BE MADE ACCESSIBLE | | | AND OPEN FOR INSPECTION OR REQUIRE ADDITIONAL | | | DOCUMENTATION FOR ALL CONCEALED WORK PREVIOUSLY | | | COMPLETED PURSUANT TO FBC 110 & FBC 117. FBC 110.1 | | | GENERAL. CONSTRUCTION OR WORK FOR WHICH A PERMIT IS | | | REQUIRED SHALL BE SUBJECT TO INSPECTION BY THE BUILDING | | | OFFICIAL AND SUCH CONSTRUCTION OR WORK SHALL REMAIN | | | ACCESSIBLE AND EXPOSED FOR INSPECTION PURPOSES UNTIL | | | APPROVED. | | | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR | | | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE | | | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN | | | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-05-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-05-11 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-05-11 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2016-05-11 10:32:19 | 1ST REVIEW: FBC 2014 5TH ED | | | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-7918 | | | [email protected] | | | | | | 1. PROVIDE SCOPE OF WORK DESCRIBING WHAT ELEMENTS ARE | | | EXISTING -VS- WHAT ELEMENTS ARE PROPOSED. | | | 2. MECH., ELECTRICAL & PLUMBING PERMITS REQUIRED. | | | 3. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS | | | SUBJECT TO WIND LOAD. | | | 4. PALM BEACH COUNTY IMPACT FEES MAY APPLY. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY | | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, | | | WINDOW, AND DOOR SUBMITTALS. | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND | | | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED | | | WITH A COPY OF RECEIPT AS APPLICABLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-07-11 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-07-11 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-07-11 |
Time |
09:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-04-18 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-04-18 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-04-18 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2016-04-18 10:12:41 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE SHOW LIGHTING OUTLETS PER FBC RES E3903.3 | | | EGRESS OF DOORS OUTSIDE. | | | 2. SHOW THE DRYER OUTLET ON FLOOR PLAN FBC 107.3.5 | | | 3. LABEL THE LIGHTING OUTLET ABOVE SHOWER TO BE | | | RECESSED FIXTURE, VAPOR PROOF RATED. E4003.9 | | | 4. CLARIFY ELECTRICAL KEYNOTES AS SOME ARE NOT | | | APPLICABLE TO SCOPE OF WORK. DELETE N/A TO SCOPE. | | | 5. PLEASE SHOW AND ADD A WP WR RESISTANT RECEPTACLE ON | | | THE EXTERIOR OF DETACHED GARAGE. FBC E3901.7 | | | 6. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-08-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-08-05 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-08-05 |
Time |
08:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-08-04 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-08-04 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-08-02 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2016-08-03 10:15:15 | RESUB ROUTED TO JVALIDO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-07-22 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-07-22 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-06-29 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-05-23 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-04-14 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2016-05-11 10:37:13 | R02 | | 2016-04-15 09:28:52 | ROUTED TO ELECTRICAL INBOX |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2016-08-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-08-05 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-08-05 |
Time |
08:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2016-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-07-06 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-07-06 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2016-07-06 09:11:42 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER ? PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | DATE: 7/6/16 | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-05-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-05-11 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-05-11 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2016-05-11 10:33:52 | 1ST REVIEW: FBC 2014 5TH ED | | | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-7918 | | | [email protected] | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND | | | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED | | | WITH A COPY OF RECEIPT AS APPLICABLE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2016-08-03 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-08-03 |
Time |
18:18 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-08-03 |
Time |
18:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-07-21 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-07-21 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-07-21 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2016-07-21 17:31:25 | FLORIDA ENERGY CODE FBC 2014 | | | | | | FORM R405-2014 MUST BE SIGNED BY "PREPARED BY" AND | | | "OWNER/AGENT" | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-05-23 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-05-23 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-05-23 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2016-05-23 13:55:56 | FLORIDA BUILDING CODE 5TH EDITION (2014) ENERGY | | | CONSERVATION | | | | | | R101.4.4 CHANGE IN OCCUPANCY OR USE & R101.4.5 CHANGE | | | IN SPACE CONDITIONING | | | | | | PROVIE ENERGY AND HEAT LOAD CALCULATIONS. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-07-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-07-20 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-07-20 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-05-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-05-13 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-05-13 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2016-05-13 11:16:47 | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHOW DIMENSION OF VANITY SINK NEXT TO TOILET 15IN | | | REQUIRED FOR CLEARANCE ON SIDE OF TOILET. WPB AMEND TO | | | FBC SEC.107.2.1 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-07-22 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-07-22 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-07-22 |
Time |
09:31 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2016-05-17 |
|
|
Cont ID |
|
| Sent By |
nwiar |
Date |
2016-05-17 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-05-17 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|