| 2016-06-08 11:10:11 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040733 |
| | ADD: 3110 45TH ST. SUITE: E |
| | CONT: BERNARD SIMPSON |
| | TEL: 561-296-5858 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 08/2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A WRITTEN DESCRIPTION OF THE WORK TO |
| | BE COMPLETED UNDER THIS PERMIT. IF THIS PERMIT REQUEST |
| | IS THE RESULT OF A ANNUAL FIRE SITE INSPECTION, PLEASE |
| | PROVIDE THE FIRE INSPECTION REPORT OF DEFICIENCIES THAT |
| | NEED TO BE CORRECTED. THERE ARE NUMEROUS CODE |
| | VIOLATIONS FOUND IN THE SUBMITTED PLANS. IT APPEARS |
| | THERE IS A LOT OF UNPERMITTED WORK THAT HAS OCCURRED |
| | OVER THE YEARS. THE LAST SET OF PLANS FOR PERMITTED |
| | WORK WAS UNDER PERMIT: 97003468 UNDER THIS ADDRESS, |
| | THERE WAS NO SECOND FLOORS OR MEZZANINES IN THAT SCOPE |
| | OF WORK. |
| | |
| | 2) PLEASE INDICATE IF THE SUBMITTED PLAN IS FOR THE |
| | ENTIRE BUILDING OR FOR ONLY THIS TENANT SPACE? THE |
| | PROPERTY APPRAISERS INDICATES THE TOTAL SQ. FOOTAGE FOR |
| | THIS BUILDING TO BE 7500 SQ. FT. WHERE AS THE PLANS |
| | SUBMITTED SCALE OFF TO BE 5022 SQ. FT. THE SAME HOLD |
| | TRUE FOR THE 2ND FLOOR OR MEZZANINE. ADDITIONAL |
| | INFORMATION REQUIRED? 107.2.1.3/ DISCREPANCY IN PLANS. |
| | |
| | 3) THE DESIGNER OF RECORD LIST THE BUILDING |
| | CONSTRUCTION TYPE AS BUILDING TYPE IB. THE MINIMUM |
| | BUILDING TYPE FOR A VB/ F1 IS 8500 SQ. FT., FOR A VB/ |
| | S1 IS 9000 SQ. FT. AND FOR A VB/B IS ALSO 9000SQ.FT. |
| | DOES THIS BUILDING HAVE 2 HOUR FIRE RATING FOR THE |
| | PRIMARY STRUCTURAL FRAME, EXTERIOR WALLS INTERIOR |
| | BEARING WALLS (MEZZANINE/ 2ND FLOOR AREAS TO BE |
| | DETERMINED) AND 1 FOUR ROOF FRAMING MEMBERS AND ROOF |
| | CONSTRUCTION? |
| | |
| | 4) THE PLANS ARE NOT CLEAR TO WHERE THE MEZZANINE OR |
| | 2ND FLOOR STARTS AND ENDS. A CUT SECTION THROUGH THE |
| | NORTH/ SOUTH ACCESS WILL HELP US TO DETERMINE IF THERE |
| | IS A TRUE MEZZANINE OR MEZZANINES OR IF WE ARE DEALING |
| | WITH A 2ND STORY. THE TERM ATTIC IS USED ON A PORTION |
| | OF THE 2ND STORY. IS THE ATTIC AREA ACTUALLY HAVE A |
| | FLOOR CEILING ASSEMBLY, FROM THE 1ST FLOOR THAT ALLOWS |
| | FOR THE USE OF A 2ND STORY IN THIS AREA BUT NOT IN USE? |
| | ON BOTH ENDS OF THE ATTIC AREA THERE ARE DOORWAYS |
| | LEADING INTO THIS AREA? |
| | |
| | 5) THE REQUIREMENTS FOR ENCLOSED STAIRS CANNOT BE |
| | DETERMINED UNTIL THE MEZZANINE/ 2ND FLOOR CAN BE |
| | DETERMINED? 107.2.1.3. FBC-B 505 MEZZANINES, 1009.3/ |
| | 1016.3.1 EXIT ACCESS STAIRS. |
| | |
| | 6) THE PLANS APPEARS TO DEPICT A SINGLE TENANCY. PLEASE |
| | PROVIDE THE TYPE OF OCCUPANCY OR IF THIS IS A MIXED USE |
| | OCCUPANCY? IS THE INTENT TO HAVE OCCUPANCY SEPARATION |
| | PER 2014 FBC-B TABLE 508.4 OR NON-SEPARATED PER SECTION |
| | 508.3. |
| | |
| | 7) OTHER ISSUES AS HANDRAILS, GUARDRAILS AND |
| | ACCESSIBILITY WILL NEED TO BE ADDRESSED ONCE A |
| | UNDERSTANDING OF THE ABOVE COMMENTS ARE SATISFIED. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| 2016-06-03 18:36:00 | THE BUILDING REVIEW OF 5/2/16 IS RESCINDED THIS DATE. |
| | SAK |