Plan Review Details - Permit 16040708
Plan Review Stops For Permit 16040708
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-12 Cont ID  
Sent By jwitmer Date 2016-05-12 Time 11:33 Rev Time 0.00
Received By jwitmer Date 2016-05-12 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-04-25 Cont ID  
Sent By mvaldes Date 2016-04-25 Time 15:06 Rev Time 0.00
Received By mvaldes Date 2016-04-25 Time 13:46 Sent To  
Notes
2016-04-25 15:14:25REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 PASSED WITH A PROVISO
  
 NOTICE TO ELECTRICAL CONTRACTOR
 ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED
 STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE
 RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE
 SEALING MATERIAL.
  
 NEC 110.24 AVAILABLE FAULT CURRENT, NEC 110.16 ARC
 FLASH HAZARD
 A ? FIELD MARKING, SHALL INCLUDE DATE AND BE SUITABLE
 TO WITHSTAND ENVIRONMENT INVOLVED.
 B ? MODIFICATIONS, RECALCULATIONS NECESSARY TO ENSURE
 SUFFICIENT AT LINE TERMINALS OF EQUIPMENT.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-18 Cont ID  
Sent By pleduc Date 2016-04-18 Time   Rev Time 0.00
Received By pleduc Date 2016-04-18 Time 15:48 Sent To  
Notes
2016-04-18 16:18:14THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET CD - THERE ARE INCORRECT REFERENCES TO THE
 FIRE CODE INDICATED. PLEASE UPDATE YOUR RECORDS AND
 REFERENCES AS FUTURE SUBMITTALS WITH THE SAME INCORRECT
 REFERENCES WIL BE DENIED.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 IT DOES NOT APPEAR TO NEGATIVELY AFFECT YOUR PROPOSED
 PREJECT; HOWEVER, A MORE DETAILED REVIEW BY YOUR
 DESIGNERS MAY BE WARRANTED.
  
 ALL FIRE INSPECTIONS SHALL BE CONDUCTED FOR COMPLIANCE
 WITH THE CURRENT FIRE CODES.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-27 Cont ID  
Sent By lmarchan Date 2016-05-27 Time 10:00 Rev Time 0.00
Received By lmarchan Date 2016-05-24 Time 12:39 Sent To  
Notes
2016-05-25 12:39:55RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-18 Cont ID  
Sent By cpuell Date 2016-05-18 Time 11:35 Rev Time 0.00
Received By cpuell Date 2016-05-17 Time 16:05 Sent To  
Notes
2016-05-17 16:05:26RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-27 Cont ID  
Sent By lmarchan Date 2016-05-27 Time 10:00 Rev Time 0.00
Received By lmarchan Date 2016-04-14 Time 13:19 Sent To  
Notes
2016-04-14 13:19:12C18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-12 Cont ID  
Sent By jwitmer Date 2016-05-12 Time 11:13 Rev Time 0.00
Received By jwitmer Date 2016-05-12 Time 11:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-05-26 Cont ID  
Sent By jvalido Date 2016-05-26 Time 16:10 Rev Time 0.00
Received By jvalido Date 2016-05-26 Time 16:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-05-17 Cont ID  
Sent By jvalido Date 2016-05-17 Time 17:24 Rev Time 0.00
Received By jvalido Date 2016-05-17 Time 17:19 Sent To  
Notes
2016-05-17 17:22:43CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 AS ASKED FOR IN THE LAST REVIEW. PROVIDE EQUIPMENT
 SCHEDULE FOR ALL VAV BOXES ON PLANS. PROVIDE
 SPECIFICATIONS ON ALL VAV EQUIPMENT (TO INCLUDE) BRAND,
 MODEL #, TOTAL CFM, HEAT KW (IF APPLICABLE).

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-19 Cont ID  
Sent By jvalido Date 2016-04-19 Time 17:25 Rev Time 0.00
Received By jvalido Date 2016-04-19 Time 16:28 Sent To  
Notes
2016-04-19 17:12:45CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.2.1
 IDENTIFY ALL VAV EQUIPMENT SO IT BE SPECIFIC TO EACH
 DEVICE (EXAMPLE: VAV #1 - VAV #2 AND SO ON). PROVIDE
 SPECIFICATIONS ON ALL VAV EQUIPMENT (TO INCLUDE) BRAND,
 MODEL #, TOTAL CFM, HEAT KW (IF APPLICABLE).

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-29 Cont ID  
Sent By gjohnson Date 2016-04-29 Time 16:51 Rev Time 0.00
Received By gjohnson Date 2016-04-29 Time 16:40 Sent To  
Notes
***NONE***