Plan Review Details - Permit 16040652
Plan Review Stops For Permit 16040652
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-02-10 Cont ID  
Sent By cthroop Date 2017-02-10 Time 09:26 Rev Time 0.00
Received By cthroop Date 2017-02-09 Time 15:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-30 Cont ID  
Sent By cthroop Date 2017-01-30 Time 10:16 Rev Time 0.00
Received By cthroop Date 2017-01-30 Time 10:16 Sent To  
Notes
2017-01-30 10:31:50BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE INCREASED BY $4,800 (PYLON SIGNAGE INSTALL).
 2. DESCREPENCY OF DEMENSIONS (WIDTH) FOR AUGER DRILLED
 PIERS BETWEEN ROBERT W. WALL, P.E. (3'-0") AND JOHN F.
 DOUGHERTY, P.E. (1'-6"). PLEASE CLARIFY.
 3. DESCREPENCY OF DESIGN WIND LOADS FOR PYLON SIGN
 BETWEEN ROBERT W. WALL, P.E. (ASCE 7-10 - EXPOSURE C -
 175 MPH) AND JOHN F. DOUGHERTY, P.E. (FL BLDG. CODE,
 5TH ED 2014 - VULT - 170 MPH, EXPOSURE B). PLEASE
 CLARIFY.
 4. PROVIDE CONNECTION DETAIL FOR PYLON SIGN DISPLAY
 CABINET TO ALUMINUM ANGLE FRAMING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By shill Date 2016-05-04 Time 15:46 Rev Time 0.00
Received By shill Date 2016-05-04 Time 15:46 Sent To E
Notes
2016-05-04 15:47:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS
 PROJECT. THIS SHOULD INCLUDE ALL SIGNS, INCLUDING
 PERMITS WHICH HAVE ALREADY PASSED PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-02-09 Cont ID  
Sent By albarran Date 2017-02-09 Time 17:08 Rev Time 0.00
Received By albarran Date 2017-02-09 Time 16:08 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-11 Cont ID  
Sent By mvaldes Date 2017-01-11 Time 18:31 Rev Time 0.00
Received By mvaldes Date 2017-01-11 Time 18:02 Sent To B
Notes
2017-01-11 18:32:09ROUTED TO SH.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-05-05 Cont ID  
Sent By mvaldes Date 2016-05-05 Time 11:50 Rev Time 0.00
Received By mvaldes Date 2016-05-05 Time 11:33 Sent To  
Notes
2016-05-05 11:59:42REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - NEC 600.5 A DEDICATED 20 AMP BRANCH CIRCUIT REQUIRED
 FOR SIGN OUTLET.
  
 - C405.2.4 EXTERIOR LIGHTING CONTROLS
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS..
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-10 Cont ID  
Sent By cthroop Date 2017-02-10 Time 09:26 Rev Time 0.00
Received By cthroop Date 2017-02-07 Time 12:38 Sent To  
Notes
2017-02-08 12:38:42RESUB ROUTED TO LLOUIE VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-30 Cont ID  
Sent By cthroop Date 2017-01-30 Time 10:16 Rev Time 0.00
Received By cthroop Date 2017-01-10 Time 13:29 Sent To  
Notes
2017-01-10 13:29:34RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-05 Cont ID  
Sent By mvaldes Date 2016-05-05 Time 12:00 Rev Time 0.00
Received By mvaldes Date 2016-04-12 Time 10:19 Sent To  
Notes
2016-05-04 15:48:055/4 TO ELEC BOX
  
2016-04-13 10:21:18ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-02-09 Cont ID  
Sent By llouie Date 2017-02-09 Time   Rev Time 0.00
Received By llouie Date 2017-02-09 Time   Sent To E
Notes
2017-02-08 16:44:59ROUTED TO LINDA LOUIE

Review Stop Z ZONING
Rev No 1 Status P Date 2016-04-15 Cont ID  
Sent By llouie Date 2017-01-03 Time 15:57 Rev Time 0.00
Received By llouie Date 2017-01-03 Time 15:57 Sent To B
Notes
2016-04-15 16:00:29** PASSED ON 1/3/2017 **
  
 PER THE APPROVED PERMIT PLAN:
  
 - NO SIGNAGE PERMITTED ON OR BETWEEN POLE COVERS.
  
 CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
  
 ** FAILED ** (4/17/2016)
  
 1.) PER ORDINANCE NO. 4572-15, NO BUILDING PERMIT FOR
 ANY LAND CONSTRUCTION RELATING TO THE DEVELOPMENT OF
 THE BW-AUSTRALIAN & BELVEDERE CPD WILL BE APPROVED
 UNTIL ALL CONDITIONS OUTLINED IN THE ORDINANCE HAVE
 BEEN ADDRESSED.
  
 CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  