Plan Review Details - Permit 16040630
Plan Review Stops For Permit 16040630
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-13 Cont ID  
Sent By jvalido Date 2016-04-13 Time 14:49 Rev Time 0.00
Received By jvalido Date 2016-04-12 Time 10:53 Sent To  
Notes
2016-04-13 10:53:35MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-14 Cont ID  
Sent By jvalido Date 2016-04-14 Time 15:08 Rev Time 0.00
Received By jvalido Date 2016-04-14 Time 15:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By jvalido Date 2016-04-13 Time 14:49 Rev Time 0.00
Received By jvalido Date 2016-04-13 Time 14:29 Sent To  
Notes
2016-04-13 14:50:10CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 - PROVIDE ON THE PLANS, WHO DREW THE PLANS. IF IT
 IS AN ENGINEER, THE PLANS MUST HAVE THE ENGINEER STAMP
 AND SIGNATURE. IF IT IS THE MECHANICAL CONTRACTOR THE
 PLANS MUST HAVE NAME OF QUALIFIER, NAME OF COMPANY,
 ADDRESS OF COMPANY AND LICENSE NUMBER.
  
 107.2 - PROVIDE CLEAR AND READABLE PLANS. SHOW ALL DUCT
 LOCATIONS, DUCT SIZES, CFM QUANTITIES, GRILL SIZES, AHU
 CLOSET AND CONDENSER LOCATION. PROVIDE CONDENSER TIE
 DOWN DETAIL AS PER FBC 2014 WIND LOAD REQUIREMENTS.
 EQUIPMENT INFORMATION (TO INCLUDE BOTH AHU AND
 CONDENSER - MAKE, MODEL #, TOTAL BTU, KW HEATER SIZE,
 MAX FUSE SIZE )