Plan Review Details - Permit 16040620
Plan Review Stops For Permit 16040620
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-26 Cont ID  
Sent By spalmer Date 2016-04-26 Time 12:27 Rev Time 0.00
Received By spalmer Date 2016-04-26 Time 12:27 Sent To  
Notes
2016-04-26 12:29:55PASSED PER JULIO WHO PASSED THE I STOP INSTEAD OF
 ADDING BUILDING STOP. JULIO CALLED CUSTOMER AND
 INFORMED THEM PERMIT WAS READY FOR PICK UP AS HIS NOTE
 ON FRONT SCREEN IS NOTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-20 Cont ID  
Sent By jgomez Date 2016-04-19 Time 18:26 Rev Time 0.00
Received By jgomez Date 2016-04-19 Time 17:47 Sent To  
Notes
2016-04-19 18:27:25RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 1- ENGINEER CALCULATIONS ITEM #1 SHOW 4'X4'X1.5"
 INSULATION BOARD FASTENED WITH (12) FASTENERS FOR MAX.
 DESIGN PRESSURES OF -82.5PSF. THE FASTENER PATTERN
 SHOWN ON ITEM #3 SPECIFIES (6) FASTENERS FOR THE FIELD
 AREA, (10) FASTENERS FOR THE PERIMETER AREA AND (16)
 FASTENERS FOR THE CORNER AREA. ACCORDING TO SEC. 8.1 OF
 RAS 117 THE PRODUCT APPROVAL MAXIMUM DESIGN PRESSURES
 SHOWN ON THE SELECTED ASSEMBLY APPLY TO THE FIELD AREA
 OF THE ROOF . THEREFORE, THE NUMBER OF FASTENERS CAN
 NOT BE REDUCED. ENGINEER NEEDS TO REVISE THE FASTENER
 PATTERN TO COMPLY WITH RAS 117 SEC. 8.1.
  
 2- ENGINEER PROVIDES NOTE THAT "FASTENER PATTERNS SHALL
 BE AS SPECIFIED IN RAS NO. 117, FIG. 2". PROVIDE COPY
 OF FIG. 2 FOR CONTRACTOR AND INSPECTOR REFERENCE. NOTE:
 FIGURE 2 DOESN'T SHOW FASTENER PATTERN FOR 16
 FASTENERS. ENGINEER TO PROVIDE FIGURE SHOWING PATTERN
 TO INSTALL ALL FASTENERS SPECIFIED INCLUDING 16
 FASTENERS AS SPECIFIED TO RESIST THE CALCULATED DESIGN
 PRESSURES. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-04-13 Cont ID  
Sent By destabro Date 2016-04-13 Time 15:19 Rev Time 0.00
Received By destabro Date 2016-04-13 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2016-04-25 Cont ID  
Sent By jgomez Date 2016-04-25 Time 13:39 Rev Time 0.00
Received By jgomez Date 2016-04-25 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-19 Cont ID  
Sent By jgomez Date 2016-04-19 Time 18:27 Rev Time 0.00
Received By jgomez Date 2016-04-12 Time 16:30 Sent To  
Notes
2016-04-12 16:31:28ROUTED TO HISTORIC VIA ZONING INBOX