Plan Review Details - Permit 16040608
Plan Review Stops For Permit 16040608
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-12 Cont ID  
Sent By shill Date 2016-05-12 Time 09:32 Rev Time 0.00
Received By shill Date 2016-05-12 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-04 Cont ID  
Sent By shill Date 2016-05-04 Time 11:18 Rev Time 0.00
Received By shill Date 2016-05-04 Time 11:18 Sent To  
Notes
2016-05-04 11:26:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO INCLUDE ROOM DESIGNATIONS, FBC
 1008.1.10. PANIC HARDWARE IS SHOWN ON SOME DOORS BUT
 NOT ALL. NOT ENOUGH INFORMATION PROVIDED TO DEMONSTRATE
 CODE COMPLIANCE.
  
 2. FBC 2014 ACCESSIBILITY 303, THRESHOLD HEIGHT NOT
 CLEAR. IF ADA THRESHOLD OPTION IS APPLICABLE FOR ALL
 DOORS, REVISE PLAN TO INCLUDE THAT INFORMATION (A
 STATEMENT IS SUFFICIENT). IF NOT, REVISE PLAN TO SHOW
 WHICH DOORS WILL COMPLY WITH FBC 2014 ACCESSIBILITY AND
 REVISE PLAN TO SHOW EXEMPTIONS FOR DOORS WHICH WILL NOT
 BE ACCESSIBLE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-12 Cont ID  
Sent By shill Date 2016-05-12 Time 09:32 Rev Time 0.00
Received By shill Date 2016-05-09 Time 09:45 Sent To  
Notes
2016-05-10 09:46:04RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-04 Cont ID  
Sent By shill Date 2016-05-04 Time 11:26 Rev Time 0.00
Received By shill Date 2016-04-12 Time 10:51 Sent To  
Notes
2016-04-13 10:52:10ROUTED TO BLDG MISC 1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved