Plan Review Details - Permit 16040576
Plan Review Stops For Permit 16040576
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-04 Cont ID  
Sent By jwitmer Date 2016-05-04 Time 17:45 Rev Time  
Received By jwitmer Date 2016-05-04 Time 17:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-12 Cont ID  
Sent By mvaldes Date 2016-05-12 Time 11:23 Rev Time 0.00
Received By mvaldes Date 2016-05-12 Time 11:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-04-21 Cont ID  
Sent By mvaldes Date 2016-04-21 Time 16:59 Rev Time 0.00
Received By mvaldes Date 2016-04-21 Time 16:10 Sent To  
Notes
2016-04-21 17:00:20REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 NEC 404.2C SWITCH CONNECTIONS
 SWITCHES CONTROLLING LIGHTING LOADS SUPPLIED BY A
 GROUNDED GENERAL PURPOSE BRANCH CIRCUIT, THE GROUNDED
 CIRCUIT CONDUCTOR FOR THE CONTROLLED LIGHTING CIRCUIT
 SHALL BE PROVIDED AT THE SWITCH LOCATION.
  
 FBC-ER 404.1.1 / 402.4.4
 RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT
 AS WELL AS IC RATED AND SEALED TO NOT COMPROMISE
 BUILDING THERMAL ENVELOPE. ( 2 CFM )
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-11 Cont ID  
Sent By pleduc Date 2016-05-11 Time   Rev Time 0.00
Received By pleduc Date 2016-05-11 Time 12:05 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-27 Cont ID  
Sent By pleduc Date 2016-04-27 Time   Rev Time 0.00
Received By pleduc Date 2016-04-27 Time 13:26 Sent To  
Notes
2016-04-27 13:37:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NOT INDICATION OF COMPLIANCE WITH CERTAIN
 FIRE CODES NOTED ON ANY PLAN SHEET. PLEASE PROVIDE
 NOTE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) THERE IS NO INDICATION OF EXISTING FIRE ALARM OR
 FIRE SPRINKLER SYSTEMS. PLEASE PROVIDE NOTE.
  
 IF EITHER SYSTEM IS EXISTING.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRE AN EVALUATION BY A CERTIFIED LIFE SAFTEY
 CONTRACTOR.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 3) THERE IS NO INDICATION OR LOCATION OF ANY EXISTING
 OR NEW SMOKE DETECTION/ALARMS. PLEASE PROVIDE
 INCOMPLIANCE WITH THE ABOVE NOTED CODES.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-12 Cont ID  
Sent By skennedy Date 2016-05-12 Time 11:36 Rev Time 0.00
Received By skennedy Date 2016-05-09 Time 10:33 Sent To  
Notes
2016-05-10 10:34:09RESUB ROUTED TO PLEDUC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-04 Cont ID  
Sent By   Date 2016-05-04 Time   Rev Time 0.00
Received By lmarchan Date 2016-04-18 Time 10:18 Sent To  
Notes
2016-04-19 10:19:17B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-04 Cont ID  
Sent By jwitmer Date 2016-05-04 Time   Rev Time  
Received By jwitmer Date 2016-05-04 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-29 Cont ID  
Sent By tklarge Date 2016-04-29 Time 05:54 Rev Time 0.00
Received By tklarge Date 2016-04-29 Time 05:45 Sent To  
Notes
***NONE***