Plan Review Details - Permit 16040566
Plan Review Stops For Permit 16040566
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-28 Cont ID  
Sent By dharvey Date 2016-04-28 Time 09:36 Rev Time 0.00
Received By dharvey Date 2016-04-28 Time 09:34 Sent To  
Notes
2016-04-28 09:35:42PROVISIONAL APPROVAL. THE FOLLOWING NOTES HAVE BEEN
 ATTACHED TO THE PLAN:
  
 THIS IS A PARTIAL PLAN AND DOES NOT INDICATE ALL OF THE
 WORK TO BE PERFORMED. AN AS-BUILT PLAN, INCLUDING FIRE
 STOP DETAILS WILL BE REQUIRED PRIOR TO A FINAL
 INSPECTION. IN ADDITION TO THIS PLAN, ELECTRICAL WORK
 IN THE AREA IS PERMITTED UNDER ELECTRICAL REPAIR PERMIT
 #16030837 ISSUED TO FINE LINE ELECTRIC. THE WORK IN THE
 AREA OF THE NEW CEILINGS NEEDS TO BE INCLUDED IN THE
 AS-BUILT PLAN FOR THIS WORK. ALL WORK AND MODIFICATIONS
 TO THE PLAN ARE SUBJECT TO AND TO BE HANDLED AT THE
 DIRECTION OF THE FIELD INSPECTORS AS NEEDED TO COMPLETE
 THE WORK IN A SAFE AND CODE COMPLIANT MANNER. THIS WORK
 IS A LEVEL 2 ALTERATION AND REQUIRED TO COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF THE FLORIDA BUILDING CODE
 VOLUMES THAT APPLY TO THE PARTICULAR WORK. APPROVAL OF
 THIS PERMIT DOES NOT ELIMINATE THE NEED FOR ADDITIONAL
 PERMITS OR CONTRACTORS AS NEEDED TO COMPLETE BUILDING,
 ELECTRICAL, MECHANICAL, PLUMBING OR GAS WORK, ALL OF
 WHICH IS TO BE PERFORMED BY LICENSED AND INSURED
 CONTRACTORS, LICENSED IN THE ACCORDANCE WITH APPLICABLE
 LAWS AND PERFORMED WITHIN THE SCOPE OF THEIR LICENSE.
  
 THIS NOTE IS MADE A PART OF THIS PERMIT AND NOT TO BE
 REMOVED FROM THE ISSUED PLANS.
  
 DOUG HARVEY
 ASSISTANT BUILDING OFFICIAL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT
  
 SEE ADDITIONAL NOTES FROM PREVIOUS PLAN REVIEW AS WELL
 AND APPLY AS APPLICABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By cthroop Date 2016-04-13 Time 14:49 Rev Time 0.00
Received By cthroop Date 2016-04-13 Time 14:49 Sent To E
Notes
2016-04-13 15:01:441ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. OWNER TO SIGN APPLICATION.
 2. DESIGN PROFESSIONAL TO SIGN DRAWINGS.
 3. IDENTIFY CURRENT GOVERNING CODES ON PLANS.
 4. BUILDING OCCUPANCY IS I-1 INSTITUTIONAL. BUILDING IS
 TYPE IIB SPRINKLERED.
 5. PROVIDE DETAIL ON RE-LOCATION OF FIRE SPRINKLER
 HEADS. DEMONSTRATE HOW REQUIRED COVERAGE WILL BE
 MAINTAINED.
 6, FIRE PERMIT REQUIRED.
 7. PROVIDE DETAIL ON ANY ABOVE CEILING ELECTRICAL WORK.
 8. ELECTRICAL PERMIT REQUIRED.
 9. IDENTIFY AND LABEL ANY WATER LINES AND VALVES ABOVE
 CEILING.
 10. PLUMBING PERMIT REQUIRED.
 11. IDENTIFY AND LABEL ANY HVAC DAMPERS ABOVE CEILING.
 12. HVAC PERMIT REQUIRED.
 13. STENCIL "RATED WALL" ABOVE CEILING PER CODE
 REQUIREMENTS.
 14. PROVIDE DETAIL ON REPAIR OF ANY PENETRATIONS IN
 RATED ASSEMBLIES ABOVE CEILING PRIOR TO CONCEALMENT.
 15. PROVIDE CERTIFICATE OF SURFACE BURNING
 CHARACTERISTICS OF BUILDING MATERIALS FOR PROPOSED
 CEILING TILES PER ASTM E 84-11A.
 16. RE-EVALUATE STATED VALUE ON PERMIT APPLICATION.
 17. DUE TO EXISTING VIOLATIONS, FIELD INSPECTORS MAY
 REQUIRE ADDITIONAL INSPECTIONS.
 18. PROVIDE DETAIL OF DROP CEILING HEIGHT AFF ON PLANS.
 EMERGENCY EXIT LIGHTS MAY HAVE TO BE LOW PROFILE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2016-04-20 Cont ID  
Sent By vperez Date 2016-04-20 Time 08:55 Rev Time 0.00
Received By vperez Date 2016-04-20 Time 08:55 Sent To  
Notes
2016-04-20 08:56:24ELECTRICAL PERMIT ISSUED UNDER SEPERATE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-27 Cont ID  
Sent By pleduc Date 2016-04-27 Time   Rev Time 0.00
Received By pleduc Date 2016-04-27 Time 12:43 Sent To  
Notes
2016-04-27 13:07:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ENSURE FIRE SPRINKLER AND FIRE ALARM DEVICES ARE NOT
 COVERED.
  
 2) ANY FIRE SPRINKLER OR FIRE ALARM WORK SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-29 Cont ID  
Sent By cpuell Date 2016-04-29 Time 08:22 Rev Time 0.00
Received By cpuell Date 2016-04-11 Time 11:09 Sent To  
Notes
2016-04-20 09:23:04B05
2016-04-12 11:10:29BLDG <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-04-28 Cont ID  
Sent By dharvey Date 2016-04-28 Time 09:37 Rev Time 0.00
Received By dharvey Date 2016-04-28 Time 09:37 Sent To  
Notes
2016-04-28 09:37:21PROVISIONAL APPROVAL. THE FOLLOWING NOTES HAVE BEEN
 ATTACHED TO THE PLAN:
  
 THIS IS A PARTIAL PLAN AND DOES NOT INDICATE ALL OF THE
 WORK TO BE PERFORMED. AN AS-BUILT PLAN, INCLUDING FIRE
 STOP DETAILS WILL BE REQUIRED PRIOR TO A FINAL
 INSPECTION. IN ADDITION TO THIS PLAN, ELECTRICAL WORK
 IN THE AREA IS PERMITTED UNDER ELECTRICAL REPAIR PERMIT
 #16030837 ISSUED TO FINE LINE ELECTRIC. THE WORK IN THE
 AREA OF THE NEW CEILINGS NEEDS TO BE INCLUDED IN THE
 AS-BUILT PLAN FOR THIS WORK. ALL WORK AND MODIFICATIONS
 TO THE PLAN ARE SUBJECT TO AND TO BE HANDLED AT THE
 DIRECTION OF THE FIELD INSPECTORS AS NEEDED TO COMPLETE
 THE WORK IN A SAFE AND CODE COMPLIANT MANNER. THIS WORK
 IS A LEVEL 2 ALTERATION AND REQUIRED TO COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF THE FLORIDA BUILDING CODE
 VOLUMES THAT APPLY TO THE PARTICULAR WORK. APPROVAL OF
 THIS PERMIT DOES NOT ELIMINATE THE NEED FOR ADDITIONAL
 PERMITS OR CONTRACTORS AS NEEDED TO COMPLETE BUILDING,
 ELECTRICAL, MECHANICAL, PLUMBING OR GAS WORK, ALL OF
 WHICH IS TO BE PERFORMED BY LICENSED AND INSURED
 CONTRACTORS, LICENSED IN THE ACCORDANCE WITH APPLICABLE
 LAWS AND PERFORMED WITHIN THE SCOPE OF THEIR LICENSE.
  
 THIS NOTE IS MADE A PART OF THIS PERMIT AND NOT TO BE
 REMOVED FROM THE ISSUED PLANS.
  
 DOUG HARVEY
 ASSISTANT BUILDING OFFICIAL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT
  
 SEE ADDITIONAL NOTES FROM PREVIOUS PLAN REVIEW AS WELL
 AND APPLY AS APPLICABLE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-22 Cont ID  
Sent By ccole Date 2016-04-22 Time 10:24 Rev Time 0.00
Received By ccole Date 2016-04-22 Time 10:24 Sent To  
Notes
2016-04-22 10:45:241ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16040566
 4/22/16
  
 1) PLEASE PROVIDE THE LEVEL OF ALTERATION ON THE PLAN-
 REFER TO SECTION 501.1 FBC-14 EXISTING BUILDING.
 2) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT.
 3) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 ON THE PLAN WITH CORRESPONDING DRAWINGS, DETAILS, AND
 SPECIFICATIONS. SHOW ALL EXISTING EQUIPMENT AND
 COMPONENTS TO BE REMOVED, RE-LOCATED, OR REPLACED
 INCLUDING THE CORRIDORS WHERE IT APPEARS A NEW
 SUSPENDED CEILING WILL BE INSTALLED. REFER TO SECTIONS
 601.2 AND 607 FBC-14 MECHANICAL FOR CODE COMPLIANCE
 INFORMATION.
 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND
 TABLE 403.3 MECHANCIAL AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS IN ALL ROOMS AND SPACES WHERE MECHANICAL
 ALTERATIONS ARE PROPOSED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  