| 2016-04-12 12:35:34 | ELECTRICAL REVIEW COMMENTS |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 2010 FLORIDA BLDG. CODES; 2008 NEC |
| | |
| | CORRECTIONS REQUIRED FOR THE SUBMITTED AS-BUILT |
| | DRAWINGS AS INDICATED BELOW. WHERE THREE AND FOUR WAY |
| | SWITCHING IS MENTIONED PLEASE NOTE THAT THIS IS ONLY A |
| | SUGGESTION IN THE INTEREST OF ENERGY CONSERVATION, LIFE |
| | SAFETY AND USER CONVENIENCE AND THEY DO NOT HAVE TO BE |
| | INSTALLED. |
| | 1. NEC 250.94 MISSING THE INTER SYSTEM BONDING TERMINAL |
| | REQUIRED. |
| | 2. NEC 110.12 & NEC 408.4 THE AS-BUILT DRAWINGS PANEL |
| | SCHEDULES SHOULD INDICATE THE PANEL?S MANUFACTURER NAME |
| | BRAND. |
| | 3. NEC 220 PART III ADJUST THE LOADS AND CALCS AS |
| | INSTRUCTED BY NEC. I WORKED THE LOAD CALCS AND CAME UP |
| | WITH A MUCH LOWER NUMBER. |
| | 4. REVISE THE SWITCH SYMBOL ON THE DRAWINGS TO MATCH |
| | THE LEGEND |
| | 5. NEC 210.70(A)(1) PROVIDE A WALL SWITCH FOR THE LIGHT |
| | IN ROOM 100. |
| | 6. NEC 210.70(A)(1) PROVIDE THE REQUIRED LIGHT AND WALL |
| | SWITCH IN ROOMS 113, 105 & 109. |
| | 7. NEC 210.52(A)(1) OUTLET SPACING IN ROOM 213 IS NOT |
| | TO CODE. |
| | 8. NEC 210.70(A)(1) THERE SHALL BE A LIGHT CONTROLLED |
| | BY A WALL SWITCH IN THE ROOM BETWEEN ROOMS 211 & 213. |
| | PREFERABLY THIS LIGHT SHOULD HAVE A 3 WAY SWITCH. |
| | 9. ADD AN ADDITIONAL SWITCH FOR THE HALL 201 AND |
| | VESTIBULE 211 AS IT EXITS INTO ROOM 213. THIS WOULD BE |
| | A 4 WAY SWITCH. |
| | 10. NEC 210.52(E)(3) A GFI PROTECTED OUTLET IS REQUIRED |
| | IN THE BALCONY OUTSIDE OF ROOM 202. |
| | 11. A 3 WAY SWITCH TO CONTROL HALL WAY 207 LIGHTS AS IT |
| | EXITS INTO ROOM 209 IS SUGGESTED. |
| | 12. NEC 406.8 ALL RECEPTACLES IN DAMP OR WET LOCATIONS |
| | SHALL BE LISTED WEATHER-RESISTANT IN ADDITION TO HAVING |
| | AN IN-USE TYPE COVER. |
| | 13. FBC-E SECTION 404.1 A MINIMUM OF 50% OF THE LAMPS |
| | IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |