Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-09-12 Cont ID  
Sent By jwitmer Date 2016-09-12 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2016-09-12 Time 07:15 Sent To  
Notes
2016-09-12 08:16:24BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040451
 ADD: 2700 BROADWAY
 CONT: BEST MASONRY OF S. FL.
 TEL: 561-436-3732
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. SEPT. 12/2016
 ACTION: BUILDING PROVISO
  
 1)BUILDING PROVISO: THE PROPOSED RESIDENTS ARE CAPABLE
 OF SELF-PRESERVATION AND IF IN THE FUTURE RESIDENCE ARE
 ADDED THAT ARE NOT CAPABLE OF SELF-PRESERVATION THERE
 NEEDS TO BE A PERMIT REQUIRED FOR A CHANGE OF
 OCCUPANCY. 2014 FBC-B 310.6.
  
 2)BUILDING PROVISO: [F] 420.4 AUTOMATIC SPRINKLER
 SYSTEM. GROUP I-1 OCCUPANCIES SHALL BE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.2.6. QUICK RESPONSE OR
 RESIDENTIAL AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.2.
  
 3) SHEET A1:BUILDING PROVISO: NOTE ALL EXTERIOR WINDOW
 & DOORS ARE UNDER A SEPARATE PERMIT.
  
 4) BUILDING PROVISO: 2014 FLORIDA BUILDING CODE [F]
 903.2.6 GROUP I. AN AUTOMATIC SPRINKLER SYSTEM SHALL BE
 PROVIDED THROUGHOUT BUILDINGS WITH A GROUP I FIRE AREA.
 EXCEPTIONS: 1. AN AUTOMATIC SPRINKLER SYSTEM INSTALLED
 IN ACCORDANCE WITH SECTION 903.3.1.2 SHALL BE PERMITTED
 IN GROUP I-1 FACILITIES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-21 Cont ID  
Sent By jwitmer Date 2016-06-21 Time 13:41 Rev Time 0.00
Received By jwitmer Date 2016-06-21 Time 08:08 Sent To  
Notes
2016-06-21 13:41:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040451
 ADD: 2700 BROADWAY
 CONT: BEST MASONRY OF S. FL.
 TEL: 561-436-3732
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 21/2016
 ACTION: DENIED
  
 NOTICE !!!!!!!! THE SUBMITTED PLANS FOR THE 2ND REVIEW
 HAVE NOT BEEN SIGNED NOR SEALED BY THE ENGINEER OF
 RECORD. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS.
 EFFECTIVE DATE 05/06/2009
 (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
  
 1A-B) COMPLIED. R4 OCCUPANCY.
  
 1C)BUILDING PROVISO: THE PROPOSED RESIDENTS ARE CAPABLE
 OF SELF-PRESERVATION AND IF IN THE FUTURE RESIDENCE ARE
 ADDED THAT ARE NOT CAPABLE OF SELF-PRESERVATION THERE
 NEEDS TO BE A PERMIT REQUIRED FOR A CHANGE OF
 OCCUPANCY. 2014 FBC-B 310.6.
  
 1D) NOTICE: 2014 FBC-B 420.1. OCCUPANCIES IN GROUPS
 I-1, R-1, R-2 AND R-3 SHALL COMPLY WITH THE PROVISIONS
 OF SECTIONS 420.1 THROUGH 420.5 AND OTHER APPLICABLE
 PROVISIONS OF THIS CODE.
  
 1E)SEMI-COMPLIED. 420.2 SEPARATION WALLS. WALLS
 SEPARATING DWELLING UNITS IN THE SAME BUILDING, WALLS
 SEPARATING SLEEPING UNITS IN THE SAME BUILDING AND
 WALLS SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER
 OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING
 SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE
 WITH SECTION 708 ( FIRE PARTITIONS). THE PLANS DO
 INDICATE THE USE OF EXISTING PLASTER AND WOOD LATH AND
 THE USE OF 5/8 INCH TYPE X DRYWALL. PLEASE PROVIDE
 COMPLIANCE WITH 1 HOUR SEPARATION BETWEEN SLEEPING
 ROOMS (420.2) AND A 1 HOUR FIRE RATED CORRIDOR (TABLE
 1018.1 (FOOTNOTE C ALLOWS FOR ? HOUR FIRE RATING WHEN
 THE FIRE SPRINKLERS ARE A NFPA 13R, THE PLANS INDICATE
 THE SPRINKLER IS A 13D. THE 13 D IS ALLOWED IN THE R-3
 & R-4 RESIDENCE BUT THE FIRE RATING IS STILL 1 HOUR.
  
 1F) 2ND REQUEST. 420.3 HORIZONTAL SEPARATION. 2ND FLOOR
 BEDROOM #8. FLOOR ASSEMBLIES SEPARATING DWELLING UNITS
 IN THE SAME BUILDINGS, FLOOR ASSEMBLIES SEPARATING
 SLEEPING UNITS IN THE SAME BUILDING AND FLOOR
 ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS FROM
 OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME
 BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES
 IN ACCORDANCE WITH SECTION 711. 2014 FBC-B TABLE
 707.3.10 REQUIRES 2 HOUR FIRE SEPARATION BETWEEN
 OCCUPANCIES.
  
 1G) [F] 420.4 AUTOMATIC SPRINKLER SYSTEM. GROUP R
 OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.2.8. GROUP I-1 OCCUPANCIES SHALL BE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.2.6. QUICK RESPONSE OR
 RESIDENTIAL AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.2.
  
 1H)2ND REQUEST. BEDROOM # 7 SHOWS THE REMOVAL OF A
 NON-BEARING WALL, WITH A NOTE TO PROVIDE TEMPORARY
 SUPPORT OF EXISTING ROOF SYSTEM WHILE CONDUCTING
 STRUCTURAL MODIFICATIONS, IF THE WALL IS NON-BEARING
 WHY THE STRUCTURAL SUPPORT REQUIRED? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1I) NEW COMMENT. THE SLEEPING ROOM # 6 DOES NOT HAVE
 EMERGENCY ESCAPE AND RESCUE WINDOWS THAT OPEN DIRECTLY
 INTO A PUBLIC WAY, OR TO A YARD OR COURT THAT OPENS TO
 A PUBLIC WAY. 2014 FBC-B 1029.1.
  
  
  
 1J) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE 223.2 HOSPITALS, REHABILITATION FACILITIES,
 PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES.
 HOSPITALS, REHABILITATION FACILITIES, PSYCHIATRIC
 FACILITIES AND DETOXIFICATION FACILITIES SHALL COMPLY
 WITH 223.2.
  
 ACCESS. CODE 223.2.1 FACILITIES NOT SPECIALIZING IN
 TREATING CONDITIONS THAT AFFECT MOBILITY.
 IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER
 THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE
 PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY.
  
 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY.
 IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT
 AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING
 ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH
 805.
  
 ADVISORY 223.2.2 FACILITIES SPECIALIZING IN TREATING
 CONDITIONS THAT AFFECT MOBILITY.
 CONDITIONS THAT AFFECT MOBILITY INCLUDE CONDITIONS
 REQUIRING THE USE OR ASSISTANCE OF A BRACE, CANE,
 CRUTCH, PROSTHETIC DEVICE, WHEELCHAIR, OR POWERED
 MOBILITY AID; ARTHRITIC, NEUROLOGICAL, OR ORTHOPEDIC
 CONDITIONS THAT SEVERELY LIMIT ONE?S ABILITY TO WALK;
 RESPIRATORY DISEASES AND OTHER CONDITIONS WHICH MAY
 REQUIRE THE USE OF PORTABLE OXYGEN; AND CARDIAC
 CONDITIONS THAT IMPOSE SIGNIFICANT FUNCTIONAL
 LIMITATIONS. FACILITIES THAT MAY PROVIDE TREATMENT FOR,
 BUT THAT DO NOT SPECIALIZE IN TREATMENT OF SUCH
 CONDITIONS, SUCH AS GENERAL REHABILITATION HOSPITALS,
 ARE NOT SUBJECT TO THIS REQUIREMENT BUT ARE SUBJECT TO
 SECTION 223.2.1.
  
 1K)(1) COMPLIED. 9805.2 TURNING SPACE. TURNING SPACE
 COMPLYING WITH 304 SHALL BE PROVIDED WITHIN THE ROOM.
  
 1K)(2) 2ND REQUEST. 805.3 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 SHALL BE
 PROVIDED ON EACH SIDE OF THE BED. THE CLEAR FLOOR SPACE
 SHALL BE POSITIONED FOR PARALLEL APPROACH TO THE SIDE
 OF THE BED.
  
 1K)(3) 2ND REQUEST. THE NARRATIVE RESPONSE INDICATES
 THE RESTROOMS WERE CODE COMPLIANT WHEN LAST REMODELED.
 BOTH OF THE ACCESSIBLE RESTROOMS INDICATE NEW WALL TILE
 OM THE WALLS, NEW ACCESSIBLE SHOWER, NEW PLUMBING
 FIXTURES. THE PLANS INDICATE THE USE OF GREEN BOARD AS
 TILE BACKER BOARD IN THE SHOWERS.
 PLEASE REVIEW SECTION 2509.2 BASE FOR TILE. GLASS MAT
 WATER-RESISTANT GYPSUM BACKING PANELS, DISCRETE
 NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE SHEETS OR
 NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER
 UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR C 1325
 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
  
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
  
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
  
 805.4 TOILET AND BATHING ROOMS. TOILET AND BATHING
 ROOMS THAT ARE PROVIDED AS PART OF A PATIENT OR
 RESIDENT SLEEPING ROOM SHALL COMPLY WITH 603. WHERE
 PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY,
 AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF 603 THROUGH 610.
  
 1L) 2ND REQUEST. PLEASE SHOW HOW COMPLIANCE WITH
 202.4.1 DISPROPORTIONATE COST WILL BE MET. THE VALUE OF
 THE JOB AS INDICATED, $145,000.00 X .20%= $29,000.00
 DOLLARS ARE TO BE SPENT IN ACCESSIBLE UPGRADES AND IN
 THIS ORDER:
 2014 FBC-ACCESS. CODE. 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 PLEASE PROVIDE AN ITEMIZED LIST IN THE ORDER LISTED
 ABOVE OF WHERE THE FUNDS WILL BE SPENT IN MAKING
 ACCESSIBLE UPGRADES. PLEASE HAVE THE ACCESSIBLE UPGRADE
 LIST ON EITHER THE CONTRACTORS OR THE DESIGNER OF
 RECORD LETTERHEAD TAKING OWNERSHIP OF THE DOCUMENT.
  
 1M) SHEET A1: PROVISO: NOTE ALL EXTERIOR WINDOW & DOORS
 ARE UNDER A SEPARATE PERMIT.
  
 2) THE COVERSHEET ALSO LIST THE BUILDING TYPE AS A
 BUILDING TYPE V THE PLANS DO NOT INDICATE IF THE
 BUILDING IS A TYPE VA OR VB. CLASSIFY BUILDING TYPE AS
 TO 2014 FBC-B TABLE 503 & TABLE 601.
  
 3)2ND REQUEST. THE COVERSHEET INDICATES THIS STRUCTURE
 IS FIRE SPRINKLERED BUT DOES NOT INDICATE AS TO WHAT
 TYPE OF SYSTEM IS INSTALLED IN THIS STRUCTURE NOR IS
 THERE AN EXISTING FIRE SPRINKLER PLAN LAYOUT OR
 PROPOSED CHANGES TO THE EXISTING FIRE SPRINKLER PLAN.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FLOOR PLAN FOR FIRE SPRINKLERS
  
 4) 2ND REQUEST. THE RESPONSE IS IN THE NARRATIVE BUT
 NOT INDICATED IN THE PLANS, ADD THE ALTERATION LEVEL TO
 THE PLANS. THE DESIGNER OF RECORD HAS NOT INDICATED TO
 WHAT CODE THE PLANS WERE DESIGNED TOO? 2014 FBC/ 5TH
 EDITION WAS ADOPTED STATE WIDE ON JUNE 30/ 2015. PLEASE
 NOTE THE DESIGNER OF RECORD HAS NOT INDICATED TO WHICH
 METHOD OF COMPLIANCE WAS CHOSEN FOR CODE COMPLIANCE
 UNDER THE 2014 FBC-EXISTING BUILDING CODE? 2014
 FBC-EXISTING BUILDING CODE 301.1. THE REPAIR,
 ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR RELOCATION
 OF ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE
 METHODS LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS
 SELECTED BY THE APPLICANT.
  
 5) 2ND REQUEST. SHEET A1 INDICATES THE FRONT ENTRY
 STEPS THE REMOVAL OF AN EXISTING STEEL PIPE HANDRAIL
 AND REPLACEMENT WITH A NEW WROUGHT IRON HANDRAIL PER
 THE REQUIREMENTS OF THE 2014 FBC. PLEASE NOTE THE
 DESIGNER OF RECORD WILL NEED TO PROVIDE THE DESIGN FOR
 THE HANDRAIL AND NOT JUST QUOTE CODE COMPLIANCE TO BE
 ACHIEVED.
  
 SHEET A1 SHOWS A SECTION THROUGH THE FRONT STAIRS,
 SECTION B, IT DOES NOT INDICATE WHERE THIS SECTION B.
 SHEET A2 DOES SHOW A ENTRY STAIR AND HAND RAIL. PLEASE
 NOTE THIS SECTION IS SO OLD IT REFERENCES 100 PSF LIVE
 LOAD, PER SBCCI CHAPTER 16. PLEASE UPDATE THE CODE TO
 THE 2014 FBC-B.
  
 THIS SAME SECTION SHOWS A HANDRAIL SYSTEM PLEASE SHOW
 COMPLIANCE WITH 2014 FBC-B 1012.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT OR RAMP RUN. WHERE HANDRAILS ARE
 NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND
 THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF
 ONE TREAD BEYOND THE BOTTOM RISER.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION?
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-03 Cont ID  
Sent By jwitmer Date 2016-05-03 Time 08:48 Rev Time 0.00
Received By jwitmer Date 2016-05-02 Time 17:16 Sent To  
Notes
2016-05-03 08:48:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040451
 ADD: 2700 BROADWAY
 CONT: BEST MASONRY OF S. FL.
 TEL: 561-436-3732
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 03/2016
 ACTION: DENIED
  
 1A) THE COVERSHEET A1 UNDER THE HEADING OF GENERAL
 INFORMATION INDICATES THE OCCUPANCY AS A R4 AND AS A
 I-1 TYPE OF OCCUPANCY, WITH LESS THAN 16 BEDS . PLEASE
 UPDATE PLANS TO THE TYPE OF OCCUPANCY. THE OCCUPATIONAL
 LICENSE FOR THIS SITE IS FOR 12 BEDS THAT WOULD
 CLASSIFY THE OCCUPANCY AS A TYPE R4 OCCUPANCY.
 2014 FBC-B 310.6. GROUP R-4 OCCUPANCIES SHALL MEET THE
 REQUIREMENTS FOR CONSTRUCTION AS DEFINED FOR GROUP R-3,
 EXCEPT AS OTHERWISE PROVIDED FOR IN THIS CODE.
 2014FBC-B
 1B) PLEASE INDICATE IN EACH OF THE BEDROOMS HOW MANY
 OCCUPANTS WILL OCCUPY EACH OF THE BEDROOMS, SHOW THE
 BEDS FOR EACH OF THE BEDROOMS.
  
 1C) THE PLANS WILL NEED TO INDICATE THAT ALL OF THE
 PROPOSED RESIDENTS ARE CAPABLE OF SELF-PRESERVATION AND
 IF IN THE FUTURE RESIDENCE ARE ADDED THAT ARE NOT
 CAPABLE OF SELF-PRESERVATION THERE NEEDS TO BE A PERMIT
 REQUIRED FOR A CHANGE OF OCCUPANCY. 2014 FBC-B 310.6.
  
 1D)2014 FBC-B 420.1. OCCUPANCIES IN GROUPS I-1, R-1,
 R-2 AND R-3 SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 420.1 THROUGH 420.5 AND OTHER APPLICABLE
 PROVISIONS OF THIS CODE.
  
 1E) 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING
 UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING
 UNITS IN THE SAME BUILDING AND WALLS SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH
 SECTION 708.
  
 1F) 420.3 HORIZONTAL SEPARATION. 2ND FLOOR BEDROOM #8.
 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH
 SECTION 711.
  
 1G) [F] 420.4 AUTOMATIC SPRINKLER SYSTEM. GROUP R
 OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.2.8. GROUP I-1 OCCUPANCIES SHALL BE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.2.6. QUICK RESPONSE OR
 RESIDENTIAL AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.2.
  
 1H) BEDROOM # 7 SHOWS THE REMOVAL OF A NON-BEARING
 WALL, WITH A NOTE TO PROVIDE TEMPORARY SUPPORT OF
 EXISTING ROOF SYSTEM WHILE CONDUCTING STRUCTURAL
 MODIFICATIONS, IF THE WALL IS NON-BEARING WHY THE
 STRUCTURAL SUPPORT REQUIRED? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1I) BEDROOM #8 IS ON THE 2ND FLOOR AND WILL NEED TO
 COMPLY WITH:
  
 BLDG TYPE: TYPE V FLOOR INSULATION (FBC-B 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 1I)(A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1I)(B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1I)(C) TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 1J) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE 223.2 HOSPITALS, REHABILITATION FACILITIES,
 PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES.
 HOSPITALS, REHABILITATION FACILITIES, PSYCHIATRIC
 FACILITIES AND DETOXIFICATION FACILITIES SHALL COMPLY
 WITH 223.2.
  
 ACCESS. CODE 223.2.1 FACILITIES NOT SPECIALIZING IN
 TREATING CONDITIONS THAT AFFECT MOBILITY.
 IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER
 THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE
 PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY.
  
 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY.
 IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT
 AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING
 ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH
 805.
  
 ADVISORY 223.2.2 FACILITIES SPECIALIZING IN TREATING
 CONDITIONS THAT AFFECT MOBILITY.
 CONDITIONS THAT AFFECT MOBILITY INCLUDE CONDITIONS
 REQUIRING THE USE OR ASSISTANCE OF A BRACE, CANE,
 CRUTCH, PROSTHETIC DEVICE, WHEELCHAIR, OR POWERED
 MOBILITY AID; ARTHRITIC, NEUROLOGICAL, OR ORTHOPEDIC
 CONDITIONS THAT SEVERELY LIMIT ONE?S ABILITY TO WALK;
 RESPIRATORY DISEASES AND OTHER CONDITIONS WHICH MAY
 REQUIRE THE USE OF PORTABLE OXYGEN; AND CARDIAC
 CONDITIONS THAT IMPOSE SIGNIFICANT FUNCTIONAL
 LIMITATIONS. FACILITIES THAT MAY PROVIDE TREATMENT FOR,
 BUT THAT DO NOT SPECIALIZE IN TREATMENT OF SUCH
 CONDITIONS, SUCH AS GENERAL REHABILITATION HOSPITALS,
 ARE NOT SUBJECT TO THIS REQUIREMENT BUT ARE SUBJECT TO
 SECTION 223.2.1.
  
 1K) 2014 FBC-ACCESS. CODE. 805 MEDICAL CARE AND
 LONG-TERM CARE FACILITIES 805.1 MEDICAL CARE FACILITY
 AND LONG-TERM CARE FACILITY PATIENT OR RESIDENT
 SLEEPING ROOMS REQUIRED TO PROVIDE MOBILITY FEATURES
 SHALL COMPLY WITH 805.
  
 1K)(1) 9805.2 TURNING SPACE. TURNING SPACE COMPLYING
 WITH 304 SHALL BE PROVIDED WITHIN THE ROOM.
  
 1K)(2) 805.3 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 SHALL BE PROVIDED ON EACH SIDE
 OF THE BED. THE CLEAR FLOOR SPACE SHALL BE POSITIONED
 FOR PARALLEL APPROACH TO THE SIDE OF THE BED.
  
 1K)(3) 805.4 TOILET AND BATHING ROOMS. TOILET AND
 BATHING ROOMS THAT ARE PROVIDED AS PART OF A PATIENT OR
 RESIDENT SLEEPING ROOM SHALL COMPLY WITH 603. WHERE
 PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY,
 AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF 603 THROUGH 610.
  
 1L) PLEASE SHOW HOW COMPLIANCE WITH 202.4.1
 DISPROPORTIONATE COST WILL BE MET. THE VALUE OF THE JOB
 AS INDICATED, $145,000.00 X .20%= $29,000.00 DOLLARS
 ARE TO BE SPENT IN ACCESSIBLE UPGRADES AND IN THIS
 ORDER:
 2014 FBC-ACCESS. CODE. 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 PLEASE PROVIDE AN ITEMIZED LIST IN THE ORDER LISTED
 ABOVE OF WHERE THE FUNDS WILL BE SPENT IN MAKING
 ACCESSIBLE UPGRADES. PLEASE HAVE THE ACCESSIBLE UPGRADE
 LIST ON EITHER THE CONTRACTORS OR THE DESIGNER OF
 RECORD LETTERHEAD TAKING OWNERSHIP OF THE DOCUMENT.
  
 1M) SHEET A1: PROVISO: NOTE ALL EXTERIOR WINDOW & DOORS
 ARE UNDER A SEPARATE PERMIT.
  
 2) THE COVERSHEET ALSO LIST THE BUILDING TYPE AS A
 BUILDING TYPE V THE PLANS DO NOT INDICATE IF THE
 BUILDING IS A TYPE VA OR VB. CLASSIFY BUILDING TYPE AS
 TO 2014 FBC-B TABLE 503 & TABLE 601.
  
 3) THE COVERSHEET INDICATES THIS STRUCTURE IS FIRE
 SPRINKLERED BUT DOES NOT INDICATE AS TO WHAT TYPE OF
 SYSTEM IS INSTALLED IN THIS STRUCTURE NOR IS THERE AN
 EXISTING FIRE SPRINKLER PLAN LAYOUT OR PROPOSED CHANGES
 TO THE EXISTING FIRE SPRINKLER PLAN.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FLOOR PLAN FOR FIRE SPRINKLERS
  
 4) THE DESIGNER OF RECORD HAS NOT INDICATED TO WHAT
 CODE THE PLANS WERE DESIGNED TOO? 2014 FBC/ 5TH EDITION
 WAS ADOPTED STATE WIDE ON JUNE 30/ 2015. PLEASE NOTE
 THE DESIGNER OF RECORD HAS NOT INDICATED TO WHICH
 METHOD OF COMPLIANCE WAS CHOSEN FOR CODE COMPLIANCE
 UNDER THE 2014 FBC-EXISTING BUILDING CODE? 2014
 FBC-EXISTING BUILDING CODE 301.1. THE REPAIR,
 ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR RELOCATION
 OF ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE
 METHODS LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS
 SELECTED BY THE APPLICANT.
  
 5) SHEET A1 INDICATES THE FRONT ENTRY STEPS THE REMOVAL
 OF AN EXISTING STEEL PIPE HANDRAIL AND REPLACEMENT WITH
 A NEW WROUGHT IRON HANDRAIL PER THE REQUIREMENTS OF THE
 2014 FBC. PLEASE NOTE THE DESIGNER OF RECORD WILL NEED
 TO PROVIDE THE DESIGN FOR THE HANDRAIL AND NOT JUST
 QUOTE CODE COMPLIANCE TO BE ACHIEVED.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION?
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO VIEW COMMENTS FROM ALL DISCIPLINES SEE: HTTP://ONEST
 OPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STATUS.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-10-03 Cont ID  
Sent By mvaldes Date 2016-10-03 Time 14:53 Rev Time 0.00
Received By mvaldes Date 2016-10-03 Time 14:53 Sent To  
Notes
2016-10-03 14:54:16ROUTED TO CC.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-08 Cont ID  
Sent By mvaldes Date 2016-09-08 Time 17:25 Rev Time 0.00
Received By mvaldes Date 2016-09-08 Time 16:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-27 Cont ID  
Sent By mvaldes Date 2016-06-27 Time 13:01 Rev Time 0.00
Received By mvaldes Date 2016-06-27 Time 11:23 Sent To  
Notes
2016-06-27 13:04:52REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PASSED WITH PREVIOUS ADRESSED COMMENTS. SUBJECT TO
 NEW COMMENTS IF ANY OCCUPANCY CHANGE PER BUILDING
 REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-21 Cont ID  
Sent By mvaldes Date 2016-04-21 Time 11:10 Rev Time 0.00
Received By mvaldes Date 2016-04-21 Time 08:41 Sent To  
Notes
2016-04-21 11:13:22JOB PERMIT NUMBER: 16040451
 JOB ADDRESS: 2700 BROADWAY
 WEST PALM BEACH 33407
 DATE: APRIL 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - DEFINE ALTERATION LEVEL EITHER 1 , 2 OR 3 THEN IN
 DETAIL DESCRIBE THE EXTENT OF THE SCOPE OF WORK WBPA
 107
 - WBPA- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 - NEC 517 ALL PATIENT CARE BED AREAS MUST HAVE AN
 ISOLATED EQUIPMENT GROUNDING CONDUCTOR FOR ALL
 RECEPTACLES AND LIGHTING WITHIN 7 ?? FEET FROM FLOOR
 GRADE. WIRING METHODS MUST BE EMT , HOSPITAL GRADE MC
 OR AC CABLE WITH GREEN EXTERIOR METAL CLAD , THEREFORE
 NM CABLE ( PROPER TERMINOLOGY FOR ROMEX WHICH IS A
 BRAND NAME. ) ISN?T ACCEPTABLE IN PATIENT AREAS.
 FURTHERMORE TAMPER RESISTANT RECEPTACLES SHALL BE
 INSTALLED IN OTHER AREAS NOT CLASSIFIED AS CARE AREA.
 - FBC- 450 NURSING HOMES SHALL HAVE THE FOLLOWING
 ESSENTIAL ELECTRICAL SYSTEMS, FIRST A EMERGENCY SYSTEM
 WITH CRITICAL BRANCH CIRCUITS VIA A GENERATOR OR OTHER
 POWER SOURCE, SECOND A LIGHTNING PROTECTION SYSTEM WITH
 EQUIPOTENTIAL BONDING TO THE BUILDING GROUND, THIRD AND
 LAST A SURGE PROTECTION SYSTEM AT THE SERVICE EQUIPMENT
 AND PANEL BOARDS.
 - A SMOKE DETECTOR IS MISSING IN FRONT OF THE FIRE
 ALARM PANEL IN THE NEW PANTRY ROOM PER NFPA 72. NEC 760
 THE FIRE ALARM CIRCUIT SHALL BE A 20 AMP DEDICATED
 CIRCUIT IDENTIFIED WITH RED MARKING IN PANEL BOARD
 IDENTIFICATION LABELING. ( MECHANICAL PROTECTION
 REQUIRED. )
 - FBC- 450 A READING NIGHT LAMP SHALL BE PROVIDED IN
 ALL BEDROOMS WITH A SWITCH ACCESSIBLE NEARBY THE LIGHT.
 PANELS LOCATED IN SPACES SUBJECT TO STORAGE SHALL BE
 MARKED ? ELECTRICAL ? NOT FOR STORAGE?. ( PROPER
 WORKING CLEARANCE MUST BE MAINTAINED AT ALL TIMES. )
 - SECOND FLOOR HAS A EXTERIOR DOOR NOT LEADING TO A
 BALCONY OR MEANS OF EGRESS STAIRWAY PLEASE CLARIFY ?
 ALL EXTERIOR LIGHTING MUST HAVE A MINIMUM OF 1 FT
 CANDLE ILLUMINATION FOR MEANS OF EGRESS UNTIL PUBLIC
 WAY IS SAFELY REACHED.
 - NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY.
 - THE CURRENT APPLICABLE CODES ARE: FLORIDA FIRE
 PREVENTION CODE: 2012, NFPA 1: 2012, NFPA 70, (NEC):
 2011, NFPA 72: 2010, NFPA 101: 2012, FBC- 5TH EDITION:
 2014.
 -
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-09-07 Cont ID  
Sent By pleduc Date 2016-09-07 Time   Rev Time 0.00
Received By pleduc Date 2016-09-07 Time 11:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-06-23 Cont ID  
Sent By J.Walker Date 2016-06-23 Time   Rev Time 0.30
Received By   Date 2016-06-23 Time   Sent To  
Notes
2016-06-23 16:34:16WILL REQUIRE K EXTINGUISHER IN KITCHEN
 WILL REQUIRE SUB-PERMIT FOR FIRE ALARM SYSTEM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-12 Cont ID  
Sent By J.Walker Date 2016-04-12 Time   Rev Time 0.45
Received By   Date 2016-04-11 Time   Sent To  
Notes
2016-04-12 08:06:24FIRE EXTINGUISHER REQUIRED ON SECOND FLOOR
 INSTALL EMERGENCY LIGHT IN STAIR WELL
 HOOD SUPPRESSION SYSTEM IN KITCHEN REQUIRED
 FIRE ALARM PERMIT ( SCOPE OF WORK )

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-06-17 Cont ID  
Sent By gjohnson Date 2016-06-17 Time 15:36 Rev Time 0.00
Received By gjohnson Date 2016-06-17 Time 15:36 Sent To  
Notes
2016-06-17 15:39:20GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-09-01 Cont ID  
Sent By fmittner Date 2016-09-01 Time 13:25 Rev Time 0.00
Received By fmittner Date 2016-09-01 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-10-21 Cont ID  
Sent By ccole Date 2016-10-21 Time 14:33 Rev Time 0.00
Received By ccole Date 2016-10-20 Time 11:50 Sent To  
Notes
2016-10-21 11:51:10RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-10-13 Cont ID  
Sent By ccole Date 2016-10-13 Time 16:17 Rev Time 0.00
Received By ccole Date 2016-09-28 Time 12:54 Sent To  
Notes
2016-09-29 12:54:29RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-15 Cont ID  
Sent By gjohnson Date 2016-09-15 Time 12:38 Rev Time 0.00
Received By gjohnson Date 2016-08-19 Time 15:55 Sent To  
Notes
2016-08-19 15:55:21B21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-27 Cont ID  
Sent By mvaldes Date 2016-06-27 Time 13:25 Rev Time 0.00
Received By mvaldes Date 2016-06-03 Time 11:14 Sent To  
Notes
2016-06-06 11:14:28B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-03 Cont ID  
Sent By jwitmer Date 2016-05-03 Time 08:49 Rev Time 0.00
Received By jwitmer Date 2016-04-08 Time 11:14 Sent To  
Notes
2016-04-08 11:14:32B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-05-03 Cont ID  
Sent By jwitmer Date 2016-05-03 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2016-05-03 Time 08:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-10-21 Cont ID  
Sent By ccole Date 2016-10-21 Time 14:33 Rev Time 0.00
Received By ccole Date 2016-10-21 Time 14:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-10-13 Cont ID  
Sent By ccole Date 2016-10-13 Time 15:49 Rev Time 0.00
Received By ccole Date 2016-10-13 Time 15:49 Sent To  
Notes
2016-10-13 15:50:483RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16040451
 10/13/16
  
 1) 2ND REQUEST FOR FIRE DAMPERS FOR DUCT PENETRATING
 FIRE-RATED CORRIDOR WALLS. PLEASE REFER TO TABLE 1018.1
 FBC-14 FOR REQUIRED FIRE-RESISTNCE RATING OF CORRIDORS
 IN THE R4 OCCUPANCY. PLEASE NOTE THAT PER SECTION
 607.5.3 EXCEPTION 1, FIRE DAMPERS CAN BE ELIMINATED IN
 THE DUCTS IF APPROVED THROUGH-PENETRATION FIRE-STOPPING
 IS USED TO PROTECT THE ANNULAR SPACE AROUND THE DUCT-
 SEE SECTION 714.1.1 FBC-14 BUILDING. PLEASE INDICATE
 ONE MEANS OF PROTECTION OR THE OTHER ON THE PLANS.
  
 2) ONE SET OF PLANS IS MISSING SHEET M0.1 AND THE OTHER
 IS MISSING M1.1.
  
 3) 2ND REQUEST FOR THE ENERGYGAUGE CALCULATION
 SUBMITTAL TO BE SIGNED BY THE OWNER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-09 Cont ID  
Sent By ccole Date 2016-09-09 Time 09:11 Rev Time 0.00
Received By ccole Date 2016-09-09 Time 09:10 Sent To  
Notes
2016-09-09 09:24:522ND REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16040451
 9/9/16
  
 1) FIRE DAMPERS MISSING FOR DUCTS PENETRATING THE RATED
 CORRIDOR/BEDROOM WALLS, AT THE 30/20 RA GRILL AT THE
 MECHANICAL CLOSET, AND AT THE 12/10 RA GRILL AT THE
 BEDROOM/LOUNGE WALL.
  
 2) THE NEW CORRIDOR CANNOT BE USED TO CONVEY RETURN AIR
 VIA THE TRANSFERS FROM THE BEDROOMS- SECTION 601.2.
  
 3) THE PROJECT IS BEING REVIEWED AS A CHANGE OF
 OCCUPANCY PER SECTION 202 FBC-14 EXISTING BUILDING
 CODES. EXISTING CORRIDOR AND OTHER WALLS PREVIOUSLY
 NON-RATED MAY NOW BE REQUIRED TO BE FIRE-RATED (SEE
 BUILDING REVIEW COMMENTS). PLEASE PROVIDE A COMPLETE
 DUCT LAYOUT PLAN SHOWING LOCATIONS OF ALL REQUIRED FIRE
 DAMPERS (NEW OR EXISTING) IN DUCTS PENETRATING
 FIRE-RATED WALLS.
  
 4) PROVIDE DETAILS FOR THE CONTROLS OPERATION AND
 SUPERVISION OF THE RETURN AIR SMOKE DETECTOR AT AHU-1-
 SECTIONS 606.4 AND 606.4.1.
  
 5) PROVIDE FIRE DAMPER INSTALLATION DETAILS.
  
 6) M5.1: PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 COMPLETE DETAILS FOR INSTALLATION OF THE GROUND AND
 WALL-MOUNTED CU'S. SUBMIT A FL. PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE WALL BRACKET.
  
 7) THE OWNER/AGENT MUST SIGN AND DATE THE SUBMITTED
 ENERGY COMPLIANCE FORM R405-2014.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-06-10 Cont ID  
Sent By ccole Date 2016-06-10 Time 14:36 Rev Time 0.00
Received By ccole Date 2016-06-10 Time 14:36 Sent To  
Notes
2016-06-10 14:51:121ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040451
 6/10/16
  
 1) SUBMIT MECHANICAL PLANS SHOWING ALL REQUIRED
 ALTERATIONS TO THE EXISTING SYSTEMS. PLEASE INCLUDE A
 SCOPE OF WORK NARRATIVE ON THE PLAN.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ALTERED ROOMS AND SPACES PER TABLE 403.3 FBC-14
 MECHANICAL.
  
 3) AN KITCHEN EXHAUST HOOD IS REQUIRED OVER THE NEW
 8-BURNER STOVE- REFER TO SECTION 507.2 AND PROVIDE A
 SEPARATE PERMIT APPLICATION AND PLANS FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-09-15 Cont ID  
Sent By gjohnson Date 2016-09-15 Time 12:38 Rev Time 0.00
Received By gjohnson Date 2016-09-13 Time 16:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-06-17 Cont ID  
Sent By gjohnson Date 2016-06-17 Time 15:40 Rev Time 0.00
Received By gjohnson Date 2016-06-17 Time 15:40 Sent To  
Notes
2016-06-17 16:26:592NDT REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHT. A3 FIRST FLOOR REPLACEMENT PIPE TNE NOTE
 DOWNSTREAM OF CLEAN OUT CONNECT EXISTING 2IN PVC AND
 ABOVE IT SAYS CONNECT 4IN PVC IT IS UNCLEAR WHAT YOU
 DOING THERE IF THERE IS A BRANCH LINE THERE SHOW IT ON
 RISER AND PUT NOTE ON IT. PER WPB AMEND.TO FBC SEC.
 107.2.1
  
 2. FIRST FLOOR RISER BATH #5 THE VENT NEEDS TO CONNECT
 TO LAVATORY NOT THE WATER CLOSET. COMPLY WITH FBC RES.
 P3101.1
  
 3. FIRST FLOOR RISER BATH #3 THE VENT NEEDS TO CONNECT
 TO LAVATORY NOT THE WATER CLOSET. COMPLY WITH FBC RES.
 P3101.1
  
 4. SHOW HEIGHT OF HANDICAP LAV. TO COMPLY WITH FBC ACC.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5. SHOW HEIGHT OF TOILET. TO COMPLY WITH FBC ACC.604.4
 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 6. TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 7. MIRROR SHALL COMPLY WITH FBC ACC. 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 8. REAR GRAB BAR SHALL COMPLY WITH FBC ACC 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 9. PROVIDE DIMENSIONS OF ACCESSIBLE SHOWERS AND SHOWER
 VALVES. PER WPB AMEND.TO FBC SEC. 107.2.1
  
 10. SHOW NEW SHOWER ON SECOND FLOW RISER DIAGRAM. PER
 WPB AMEND.TO FBC SEC. 107.2.1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-29 Cont ID  
Sent By gearl Date 2016-04-29 Time 12:59 Rev Time 0.00
Received By gearl Date 2016-04-29 Time 12:59 Sent To  
Notes
2016-04-29 13:10:35 
  
 1. NEED TO SHOW CLEAN-OUT AT BASE OF STACK . FPC
 708.3.4
  
 2. NEED PLUMBING DIAGRAM TO SHOW 2ND FLOOR BATHROOM .
 CWPB TO WPB SECTION 107.2.1
  
 GEORGE EARL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2016-08-23 Cont ID  
Sent By llouie Date 2016-08-23 Time 09:39 Rev Time 0.00
Received By llouie Date 2016-08-22 Time 16:32 Sent To HIST
Notes
2016-08-23 09:46:58NOTES:
  
 1.) PER 12/15/15 SETTLEMENT AGREEMENT (ATTACHED WITH
 PERMIT SETS), A MAXIMUM OF 15 BEDS FOR A RESIDENTIAL
 DETOXIFICATION SUBSTANCE ABUSE TREATMENT SERVICES
 PERMITTED ON PROPERTY.
  
 2.) SEPARATE PERMIT APPLICATION AND REVIEW REQUIRED
 FOR: HAVC AND RESURFACE/RESTRIPE OF THE PARKING LOT
 AREA, PER THE REQUIRED SITE IMPROVEMENTS LISTED ON PAGE
 2-3 OF 7 OF THE SETTLEMENT AGREEMENT.
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-06-14 Cont ID  
Sent By llouie Date 2016-06-14 Time 09:52 Rev Time 0.00
Received By llouie Date 2016-06-14 Time 09:52 Sent To  
Notes
2016-06-14 09:54:58** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT FROM 4/22/16: CLARIFICATION IS
 NEEDED ON THE NUMBER OF BEDS PROVIDED/EXISTING. THE
 BUSINESS TAX APPLICATION NOTE INDICATES A MAXIMUM OF
 TWELVE (12) BEDS PERMITTED. THE PLANS SEEM TO INDICATE
 SIXTEEN (16) BEDS ARE PROVIDED. PLEASE DOCUMENT/NOTATE
 ON THE PLANS HOW MANY BEDS ARE BEING PROVIDED FOR THE
 USE (I.E. HOW MANY BEDS PER ROOM, ETC.).
  
 [PER PROJECT ENGINEER'S RESPONSE TO ZONING'S COMMENTS,
 "OWNER OF THE PROPERTY WILL NEED TO ADDRESS THIS
 COMMENT." THERE HAS BEEN NO CORRESPONDENCE WITH THE
 PROPERTY OWNER, NOR HAVE THE NUMBER OF BEDS BEEN
 CLARIFIED IN THE PLANS.]
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-04-22 Cont ID  
Sent By llouie Date 2016-04-22 Time   Rev Time 0.00
Received By llouie Date 2016-04-22 Time   Sent To  
Notes
2016-04-22 12:04:36** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING OR ON
 THE PLANS WHERE APPLICABLE:
  
 CLARIFICATION IS NEEDED ON THE NUMBER OF BEDS
 PROVIDED/EXISTING. THE BUSINESS TAX APPLICATION
 INDICATES A MAXIMUM OF TWELVE (12) BEDS PERMITTED. THE
 PLANS SEEM TO INDICATE SIXTEEN (16) BEDS ARE PROVIDED.
 PLEASE DOCUMENT/NOTATE ON THE PLANS HOW MANY BEDS ARE
 BEING PROVIDED FOR THE USE (I.E. HOW MANY BEDS PER
 ROOM, ETC.).
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  