Plan Review Details - Permit 16040440
Plan Review Stops For Permit 16040440
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-05-02 Cont ID  
Sent By cthroop Date 2016-05-02 Time 11:13 Rev Time 0.00
Received By cthroop Date 2016-05-02 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-02 Cont ID  
Sent By mvaldes Date 2016-05-02 Time 11:12 Rev Time 0.00
Received By mvaldes Date 2016-05-02 Time 11:12 Sent To  
Notes
2016-05-02 11:15:42REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 THE FOLLOWING COMMENTS WILL BE ISSUED AS A PROVISO WITH
 THE INTENT OF THE REVISION SUBMITTAL TO ADD THE STATED
 BELOW CORRECTIONS.
  
  
 - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT.
 - ON NEW BATH DOUBLE SINK PROVIDE A SECOND GFCI TO
 COMPLY WITH AN OUTLET WITHIN 3 FT OF THE OUTSIDE EDGE
 OF EACH BASIN NEC 210.52 D
 - IN THE ATTIC ENTRANCE PROVIDE A LIGHTING OUTLET
 NEARBY AHU # 2 FOR SERVICING PURPOSES NEC 210.70 A 3

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By mvaldes Date 2016-04-11 Time 18:34 Rev Time 0.00
Received By mvaldes Date 2016-04-11 Time 18:34 Sent To  
Notes
2016-04-11 18:35:20JOB PERMIT NUMBER: 16040440
 JOB ADDRESS: 239 ARLINGTON RD
 WEST PALM BEACH FLORIDA
 DATE: APRIL 11 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT.
 - ON NEW BATH DOUBLE SINK PROVIDE A SECOND GFCI TO
 COMPLY WITH AN OUTLET WITHIN 3 FT OF THE OUTSIDE EDGE
 OF EACH BASIN NEC 210.52 D
 - IN THE ATTIC ENTRANCE PROVIDE A LIGHTING OUTLET
 NEARBY AHU # 2 FOR SERVICING PURPOSES NEC 210.70 A 3
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-11 Cont ID  
Sent By cthroop Date 2016-05-11 Time 08:32 Rev Time 0.00
Received By cthroop Date 2016-05-11 Time 08:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-03 Cont ID  
Sent By jroach Date 2016-05-03 Time 13:53 Rev Time 0.00
Received By jroach Date 2016-04-08 Time 11:24 Sent To  
Notes
2016-04-08 11:24:19R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-05-11 Cont ID  
Sent By cthroop Date 2016-05-11 Time 08:32 Rev Time 0.00
Received By cthroop Date 2016-05-11 Time 08:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-02 Cont ID  
Sent By cthroop Date 2016-05-02 Time 11:11 Rev Time 0.00
Received By cthroop Date 2016-05-02 Time 11:11 Sent To  
Notes
2016-05-02 11:12:231ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-05-02 Cont ID  
Sent By skennedy Date 2016-05-02 Time 10:14 Rev Time 0.00
Received By jvalido Date 2016-05-02 Time 09:22 Sent To  
Notes
2016-05-02 10:13:27FLORIDA ENERGY CODE
  
 REVISE ENERGY CALCULATIONS TO SHOW ACTUAL UNITS
 EXISTING OR INSTALLED.
 PROVIDE ORIGINAL SIGNATURES OF PREPARED AND OWNER/AGENT
 ON ENERGY CALCULATIONS.
  
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  
 PROVIDE MANUFACTURER SPECIFICATION FOR EQUIPMENT
 INSTALLED AT TIME OF INSPECTION.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-05-02 Cont ID  
Sent By gjohnson Date 2016-04-29 Time   Rev Time  
Received By gjohnson Date 2016-04-29 Time   Sent To  
Notes
2016-05-02 09:31:11PROVISO: RED LINED PLAN ELIMINATING DRY VENT
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
2016-04-29 12:45:56PLUMBING COMMENTS 1. DRY VENT UP STREAM NOT REQUIRED -
 NEED TO REMOVE VENT
  
  
  
 GEORGE EARL PLAN REVIEW EMAIL GEARL @WPB.ORG

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-05-02 Cont ID  
Sent By cthroop Date 2016-05-02 Time 11:13 Rev Time 0.00
Received By cthroop Date 2016-05-02 Time 11:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-05-03 Cont ID  
Sent By jroach Date 2016-05-03 Time 13:52 Rev Time 0.00
Received By jroach Date 2016-05-03 Time 13:52 Sent To PC
Notes
2016-05-03 13:52:49ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.03.2016
 PERMIT NO.: 16040440
 ADDRESS: 239 ARLINGTON ROAD
 CONTRACTOR/CONTACT: GAIDA ZIRKELBACH
 TELEPHONE NO.: 561.676.3801
 SCOPE OF REVIEW: NEW ADDITION TO EXISTING SINGLE FAMILY
 RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PURSUANT TO SECTION 94-441 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), BECAUSE THE
 PROPOSED SCOPE OF WORK EXCEEDS 50 PERCENT OF THE VALUE
 OF THE EXISTING STRUCTURE, THE SITE SHALL BE BROUGHT
 INTO COMPLIANCE WITH ARTICLE XIV (LANDSCAPING) OF THE
 ZLDRS. PLANS SHALL BE SUBMITTED INDICATING SUCH. IF
 EXISTING MATERIAL IS SHOWN ON THE PLANS AND ALL
 PROVISIONS OF ARTICLE XIV HAVE BEEN MET, THEN NO
 ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF THE
 EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL OF
 THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A LANDSCAPE PERMIT. PLEASE NOTE THAT
 PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO, THE
 FOLLOWING:
  
 A. THE LOCATION OF ALL EXISTING AND PROPOSED
 STRUCTURES, IMPROVEMENTS, ETC.
  
 B. THE LOCATION OF ALL EXISTING AND PROPOSED TREES,
 SHRUBS, GROUND COVERS, ETC.
  
 C. THE LOCATION OF UTILITY AND DRAINAGE EASEMENTS,
 OVERHEAD LINES, WATER METERS, TRANSFORMERS, CHECK
 VALVES, CLEAN OUTS, FIRE HYDRANTS, LIGHT POLES, ETC.
 THAT MAY IMPACT LANDSCAPING.
  
 D. TABULATION TABLE INDICATING HOW THE EXISTING AND
 PROPOSED PLANT MATERIAL COMPLIES WITH ARTICLE XIV.
  
 E. SPECIES, QUANTITY, HEIGHT, SPREAD, SPACING, AND
 LOCATION OF THE EXISTING AND PROPOSED PLANT MATERIAL.
  
 F. STATEMENT THAT ALL LANDSCAPE AREAS WILL BE PROVIDED
 WITH A PERMANENT AUTOMATIC IRRIGATION SYSTEM, INCLUDING
 THE ADJACENT RIGHT-OF-WAY (PLEASE NOTE THAT ANY NEW
 IRRIGATION SHALL BE DONE UNDER A SEPARATE PERMIT).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved