Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 12:10 Rev Time 0.00
Received By shill Date 2016-05-24 Time 12:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-19 Cont ID  
Sent By shill Date 2016-05-19 Time 17:23 Rev Time 0.00
Received By shill Date 2016-05-19 Time 16:53 Sent To  
Notes
2016-05-19 17:27:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 FROM PREVIOUS LIST:
  
 1) THE STATED VALUE OF THIS PERMIT IS EXTREMLY LOW. W P
 B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. THIS MAY
 BE PROVIDED VIA EMAIL.
  
 2) THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 NO PRODUCT APPROVALS WERE SUBMITTED. ANY PRODUCT
 APPROVALS REQUIRED PER FAC9N-3 SHALL BE SUBMITTED AS A
 REVISION, REVIEWED BY DESIGNER OF RECORD, PRIOR TO
 INSTALLATION. ISSUED AT CONTRACTOR'S RISK.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-18 Cont ID  
Sent By jwitmer Date 2016-04-18 Time 08:02 Rev Time  
Received By jwitmer Date 2016-04-18 Time 06:45 Sent To  
Notes
2016-04-18 08:02:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040429
 ADD: 5505 S. DIXIE HWY. SUITE # 04
 CONT: TBD
 TEL: 561-856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 18/2016
 ACTION: DENIED
  
 1) THE STATED VALUE OF THIS PERMIT IS EXTREMLY LOW. W P
 B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) SHEET A-1 NOTATION # 8 INDICATES THE TENANT
 SEPARATION WALLS ARE TO BE 1 HOUR RATED. THE PLANS DO
 NOT PROVIDE A UL LISTING OR GYPSUM FIRE LISTING NOR
 DETAIL FOR THE INFILE WALL FOR DOOR BEING REMOVED. 2014
 FBC-B 708.3. & 708.4.
  
 3) THE SHEET A-1 INDICATES A CORRIDOR 4FEET WIDE AND 3
 FOOT DOORS SWINGING INTO THE CORRIDOR. PLEASE PROVIDE
 COMPLIANCE WITH
 2014 FBC-B 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED,
 SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7
 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE
 THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
  
 4) SHEET A-1 SHOWS THE DOOR E A EXISTING DOOR IN A 1
 HOUR TENANT SEPARATION WALL, PLEASE PROVIDE THE RATING
 ON THIS DOOR, SEE 2014 FBC-B TABLE 716.5.
  
 5) SHEET A-1 INDICATES THE RESTROOM TO BE 7 FEET IN
 LENGTH. SHEET A2 SHOWS A DETAIL OF THE RESTROOM. THE
 DETAIL ONLY SHOWS 4 FOOT 8 INCHES FROM THE EDGE OF THE
 LAVATORY OVER THE WATER CLOSET TO THE OPPOSITE WALL.
 PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESS. CODE
 SECTION 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET
 SHALL BE 60 INCHES (1525 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES (1420
 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 6) SHEET A2 DETAIL FOR HANDICAPPED FIXTURES AND
 ACCESSORIES SHOWS THE GRAB BARS BEING MEASURED FROM THE
 CENTER LINE TO FINISH FLOOR. PLEASE REVIEW 2014
 FBC-ACCESS. CODE SECTION 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
  
 7) THERE IS NO MENTION IN THE ARCHITECTURAL SHEETS OF
 NEW HOLES CUT IN THE ROOF DECK, NO STRUCTURAL SHEETS,
 SHEET M2 SHOWS
 A NEW ROOF TOP EXHAUST FAN AND ROOF TOP RTU UNIT. SHEET
 M3 SHOWS A CUT SECTION THROUGH EACH OF THESE OPENINGS,
 THERE IS NO MENTION OF ANY BRACING THAT IS NECEASSRY
 FOR THE NEW OPENINGS. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 8) THERE IS NO WIND DESIGN CRITERIA AS TO WHAT WIND
 SPEED, OR EXPOSURE THE ANCHORING SCHEDULE WAS DESIGNED
 FOR?
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS
  
 9) MISSING PRODUCT APPROVALS. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(D)
 ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS, INTAKE
 AND EXHAUST FANS.
  
 10) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 11) PROVIDE COMPLIANCE WITH: 2014 FBC-B 1013.6
 MECHANICAL EQUIPMENT. GUARDS SHALL BE PROVIDED WHERE
 APPLIANCES, EQUIPMENT, FANS, ROOF HATCH OPENINGS OR
 OTHER COMPONENTS THAT REQUIRE SERVICE ARE LOCATED
 WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF
 A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR
 GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN
 DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT.
  
 12) PROVIDE COMPLIANCE WITH: 2014 FBC-B 1013.7 ROOF
 ACCESS. GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH
 OPENING IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF
 EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR
 OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-16 Cont ID  
Sent By vperez Date 2016-05-16 Time 11:16 Rev Time 0.00
Received By vperez Date 2016-05-16 Time 11:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-15 Cont ID  
Sent By vperez Date 2016-04-15 Time 08:59 Rev Time 0.00
Received By vperez Date 2016-04-15 Time 07:29 Sent To  
Notes
2016-04-15 09:02:57INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. SHOW WINDOW RECEPTACLE REQUIRED, SHOW ON FLOOR PLAN
 AND PANEL SCHEDULE NEC 210.62 FBC 107.3.5
 2. PROVIDE A GENERAL NOTE INDICATING LOW VOLTAGE AND
 HOOD SUPPRESSION SYSTEMS TO BE PERMITTED SEPARATELY.
 FBC 107.3.5
 3. SHOW ON FLOOR PLAN THE EXIT LIGHT PER FIRE COMMENTS.
 FBC 107.3.5
 4. NOTE THAT 2ND SET OF PLANS ARE MISSING ELECTRICAL
 SHEETS
 5. PROVIDE NOTES TO INDICATE NEC 230.3 E FOR ID OF
 MULTIPLE SERVICES. LABEL 1 OF 2 AND 2 OF 2 ETC.
 6. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-11 Cont ID  
Sent By pleduc Date 2016-05-11 Time   Rev Time 0.00
Received By pleduc Date 2016-05-11 Time 12:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By pleduc Date 2016-04-11 Time   Rev Time 0.00
Received By pleduc Date 2016-04-11 Time 15:04 Sent To  
Notes
2016-04-11 15:32:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET A 2- INDICATES TWO DOORS OPENING INTO THE EXIT
 CORRIDOR. DOOR 02- TOILET & DOOR 03 - OFFICE.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE PROVIDE FOR THE DOORS TO SWING IN/AWAY FROM THE
 CORRIDOR OR PROVIDE MORE DETAILED INFORMATION
 INDICATING COMPLIANCE WITH THE ABOVE NOTED CODE.
  
 2. SHEET E 1 - PLEASE PROVIDE FOR AN EXIT LIGHT TO BE
 INSTALLED AT THE FRONT AREA OF THE HALL/CORRIDOR
 PROVIDE FOR ILLUMINATION AND DIRECTION FROM EACH
 DIRECTION.
  
 3. SHEET M 2 - PLEASE PROVIDE DETAILS AS TO THE MENU
 ITEMS AND FOOD PREPARATIONS INDICATING THAT GREASE
 LADEN VAPORS ARE NOT BEING PRODUCED AND THE TYPE OF
 HOOD VENTILATION PER NFPA 96.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-03 Cont ID  
Sent By ccole Date 2016-06-03 Time 16:12 Rev Time 0.00
Received By ccole Date 2016-05-09 Time 11:15 Sent To  
Notes
2016-05-09 11:16:04C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-22 Cont ID  
Sent By gjohnson Date 2016-04-22 Time 14:55 Rev Time 0.00
Received By gjohnson Date 2016-04-07 Time 09:12 Sent To  
Notes
2016-04-08 09:12:17C13

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-06-03 Cont ID  
Sent By ccole Date 2016-06-03 Time 16:24 Rev Time 0.00
Received By ccole Date 2016-06-03 Time 16:12 Sent To  
Notes
2016-06-03 16:26:47MECHANICAL PROVISO
 PERMIT #16040429
 6/3/16
  
 1) A REVISION IS REQUIRED FOR COMPLETE ENGINEERED TIE
 DOWN DETAILS FOR ANCHORING THE RTU AND CURB TO THE ROOF
 STRUCTURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-05-16 Cont ID  
Sent By ccole Date 2016-05-16 Time 14:08 Rev Time 0.00
Received By ccole Date 2016-05-16 Time 13:30 Sent To  
Notes
2016-05-16 14:31:202ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040429
 5/16/16
  
 1) M2: REFER TO SECTION C403.2.4.4 AND ADD MOTORZED
 OUTDOOR AIR DAMPERS TO THE ENERGY COMPLIANCE TABLE.
 2) SHEET M2.1 & S1.0: THE PLANS APPEAR TO SHOW THE NEW
 RTU ABUTTED TO THE PARAPET WALL WHICH CLOSE OFF THE
 REQUIRED MANUFACTURER'S CLEARANCE SPACE ON ONE SIDE OF
 THE UNIT.
 3) M2.1 & S1.0: THERE ARE CONFLICTING DETAILS FOR
 ATTACHING THE RTU AND RTU CURB ON THESE SHEETS. PLEASE
 PROVIDE CONSISTENT DETAILS ON THE PLANS, AND INCLUDE
 THE EXTERIOR DUCTWORK SUPPORT AND ANCHORAGE.
 4) THE PLAN DOESN'T INDICATE HOW AIR WILL BE RETURNED
 FROM THE OFFICE TO THE RTU- SEE SECTION 601.5.
 5) PROVIDE AN AIR DEVICE SCHEDULE
 6) THE RESPONSE FROM THE ARCHITECT TO COMMENT #5 FROM
 THE 1ST REVIEW STATES THAT THE MAKE UP AIR QUANTITY IS
 LESS THAN THE HVAC QUANTITY OF THE 5-TON SYSTEM,
 HOWEVER IT IS THE ADDED HEAT LOAD FROM THE MAKEUP AIR
 THAT MAY IMPACT THE SYSTEM. PLEASE REVISE THE AC
 CALCULATIONS TO SHOW THIS ADDITIONAL HEAT LOAD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By ccole Date 2016-04-13 Time 12:16 Rev Time 0.00
Received By ccole Date 2016-04-13 Time 12:16 Sent To  
Notes
2016-04-13 12:17:511ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040429
 4/13/16
  
 1) SHEET M1: THE VENTILATION FAN SCHEDULE INDICATES 560
 CFM CAPACITIES FOR TEF-1, AND EF-1: PLEASE CORRECT, AND
 INCLUDE THE CFM CAPACITY OF THE TEF-1 INTO THE AIR
 BALANCE CALCULATION AND SCHEDULE.
 2 ) PROVIDE A MECHANICAL ROOF PLAN INDICATING EQUIPMENT
 LOCATIONS, AND CLEARANCE DISTANCE MEASUREMENTS FOR AIR
 INTAKES AS REQUIRED IN SECTION 401.6, AND EXHAUST
 OUTLET TERMINATIONS AS REQUIRED IN SECTIONS 501.3.1 AND
 506.4.2 (TYPE II TERMINATIONS). PLEASE NOTE THAT THE
 HOOD EXHAUST OUTLET SHALL TERMINATE NOT LESS THAN 30
 INCHES ABOVE THE ROOF SURFACE (TO BE ADDRESSED UNDER
 HOOD PERMIT PLANS).
 3) REFER TO SECTIONS 304.11 FOR REQUIRED GUARDS AT ROOF
 EDGE IF NECESSARY, AND SECTION 306.5 FOR PERMANENT ROOF
 LADDER REQUIERMENTS IF NECESSARY AND NO COMPLIANT MEANS
 OF ACCESS EXISTS.
 3) SEPARATE PERMITS ARE REQUIRED FOR THE HOOD AND THE
 WALK-IN COOLER. PLEASE PLACE A NOTE ON THE PLANS TO
 CLARIFY AND PROVIDE DIRECTION.
 4) SHEET M3: PROVIDE THE WIND LOAD DESIGN CRITERIA ON
 THE PLANS FOR ANCHORAGE OF THE RTU, CURBS, AND FANS TO
 THE ROOF STRUCTURE- SEE SECTIONS 301.15 FBC-14
 MECHANCIAL, AND SECTION 1609 FBC-14 BUILDING. PLEASE
 PROVIDE COMPLETE DETAILS FOR INSTALLATION OF THE ROOF
 TOP FANS INCLUDING THE TYPE AND SIZE OF FASTENERS FOR
 MOUNTING THE CURBS TO THE STRUCTURE, AND THE FANS TO
 THE CURBS,
 5) REFER TO SECTION 508.1.1 AND INDICATE COMPLIANCE FOR
 MAKEUP AIR TEMPERATURE FOR THE PROPOSED HOOD SYSTEM (TO
 BE ADDRESSED UNDER HOOD PERMIT PLANS).
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
 6) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW RTU-
 TYPE AND SIZE OF CONDENSATE PIPING, PIPING RUN AND
 DISCHARGE LOCATION, PIPING PRIOTECTION FROM UV
 DEGRADATION- SEE SECTION 307.
 7) THE $15,000 JOB VALUE LISTED ON THE APPLICATION
 APPEARS TOO LOW FOR THE SCOPE OF THE PROJECT. PLEASE
 PROVIDE AN ACCURATE VALUE BASED ON COSTS FOR LABOR,
 MATERIALS, EQUIPMENT, FIXTURES, AND DESIGN FEES-
 SECTION 109.3 WPB AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-11 Cont ID  
Sent By gjohnson Date 2016-05-11 Time 16:45 Rev Time 0.00
Received By gjohnson Date 2016-05-11 Time 16:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-22 Cont ID  
Sent By gjohnson Date 2016-04-22 Time 14:12 Rev Time 0.00
Received By gjohnson Date 2016-04-22 Time 12:18 Sent To  
Notes
2016-04-22 14:51:31PLUMBING COMMENTS:
  
 1. GRAB BARS ARE TO BE MEASURED FROM THE TOP OF THE
 GRIPING SURFACE AT MIN 33IN 36IN MAX .
 PER FBC ACC. SEC. 609.4
  
 2. TOILET TO BE MEASURED FROM SIDE WALL 16IN MIN 18IN
 MAX.
 PER FBC ACC. SEC. 604.2
  
 3. PER FBC SEC. 306.2 THIS OCCUPANCY USE IS F-1 WHICH
 REQUIRES SEPARATE PLUMBING FACILITIES FOR MEN AND WOMEN
 PER FBC PL SEC. 403.2 THE EXCEPTION #3 DOES NOT APPLY
 BECAUSE THE PRIMARY USE IS F-1.
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE
 403.1
  
 5. PLEASE PROVIDE GREASE TRAP CALCULATIONS FROM SCHIER
 YOU CAN CONNECT LEE SCHNEEWEIS AT 800-538-4792.
 PER WPB AMEND. TO FBC 107.2.1
  
 6. SHOW LOCATION OF TOILET PAPER DISPENSER TO COMPLY
 WITH FBC ACC. SEC. 604.7
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-26 Cont ID  
Sent By ajones Date 2016-05-26 Time 15:54 Rev Time 0.00
Received By ajones Date 2016-05-26 Time 15:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-04-11 Cont ID  
Sent By ajones Date 2016-04-11 Time 14:10 Rev Time 0.00
Received By ajones Date 2016-04-11 Time 14:10 Sent To  
Notes
***NONE***