Plan Review Details - Permit 16040396
Plan Review Stops For Permit 16040396
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-04-18 Cont ID  
Sent By cthroop Date 2016-04-18 Time 10:22 Rev Time 0.00
Received By cthroop Date 2016-04-18 Time 10:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-01 Cont ID  
Sent By mvaldes Date 2016-06-01 Time 09:17 Rev Time 0.00
Received By mvaldes Date 2016-06-01 Time 09:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-14 Cont ID  
Sent By mvaldes Date 2016-04-14 Time 14:39 Rev Time 0.00
Received By mvaldes Date 2016-04-14 Time 14:28 Sent To  
Notes
2016-04-14 15:41:591ST REVIEW 4/14/16
 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - PROVIDE MANUFACTURE SPECS ON POOL EQUIPMENT SUCH AS
 LIGHTS, PUMPS, HEATER, CHLORINATER AND ETC, FURTHERMORE
 SHOW ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES. WPBA 107
  
 - ADD A EQUIPOTENTIAL BONDING DETAIL WHICH IS MISSING
 ON DETAIL SHEET. ( MAKE SURE IT TIES IN ALL ELECTRTICAL
 COMPONENTS RELATED TO THE POOL ) NEC 680.26
  
 - IF A NON METALLIC RACEWAY IS BEING USED FOR THE UNDER
 WATER LUMINARE A # 8 AWG INSULATED GROUNDING CONDUCTOR
 SHALL BE ROUTED AND TERMINATED AT THE SHELL , J-BOX,
 TRANSFORMER PLUS A LISTED POTTING COMPOUND WILL PROTECT
 THE CONNECTION FROM POSSIBLE DETERIOATING EFFECT. NEC
 680.23 2B
  
 - GFCI PROTECTION REQUIRED FOR POOL PUMPS NEC 680.21 C
 , RECEPTACLES LOCATED WITHIN 20 FT OF THE INSIDE WALL
 OF THE POOL NEC 680.22 4 , LIGHTING WITHIN AND EXCEPT
 CLEARANCES STATED IN NEC 680.22 B 4

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-04-19 Cont ID  
Sent By tklarge Date 2016-04-19 Time 04:46 Rev Time 0.00
Received By tklarge Date 2016-04-19 Time 04:45 Sent To  
Notes
2016-04-19 04:46:43THERE IS NO GAS HEATER ON THIS POOL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-01 Cont ID  
Sent By mvaldes Date 2016-06-01 Time 09:17 Rev Time 0.00
Received By mvaldes Date 2016-05-26 Time 14:19 Sent To  
Notes
2016-05-26 14:19:35RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-19 Cont ID  
Sent By tklarge Date 2016-04-19 Time 04:46 Rev Time 0.00
Received By tklarge Date 2016-04-07 Time 14:41 Sent To  
Notes
2016-04-07 14:41:45ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-04-19 Cont ID  
Sent By tklarge Date 2016-04-19 Time 04:45 Rev Time 0.00
Received By tklarge Date 2016-04-19 Time 04:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-04-12 Cont ID  
Sent By ajones Date 2016-04-12 Time 16:35 Rev Time 0.00
Received By ajones Date 2016-04-12 Time 16:35 Sent To B
Notes
***NONE***