Plan Review Details - Permit 16040307
Plan Review Stops For Permit 16040307
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-07-19 Cont ID  
Sent By shill Date 2016-07-19 Time 12:52 Rev Time 0.00
Received By shill Date 2016-07-19 Time 12:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-07-11 Cont ID  
Sent By shill Date 2016-07-11 Time 07:48 Rev Time 0.00
Received By shill Date 2016-07-11 Time 07:48 Sent To  
Notes
2016-07-11 07:50:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. BASED ON OWNER'S MEETINGS WITH MECHANICAL AND
 BUILDING OFFICIAL, AN ALTERNATE DESIGN WAS AGREED UPON
 AND REVISED BUILDING SHEETS ARE REQUIRED. PLEASE REVISE
 PLANS ACCORDINGLY, FBC 107.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-21 Cont ID  
Sent By shill Date 2016-05-21 Time 16:34 Rev Time 0.00
Received By shill Date 2016-05-20 Time 18:13 Sent To  
Notes
2016-05-21 16:35:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 COMMENTS 1, 1A, 1B, 2A, 2B FROM THE PREVIOUS REVIEW
 WERE EITHER NOT ADDRESSED OR NOT ADDRESSED ADEQUATELY.
 RATHER THAN INCLUDE THESE ITEMS, CONSIDER THE FOLLOWING
 LIST IN ADDITION TO THE PREVIOUS LIST.
  
 REVIEW 2 COMMENT #1.) REFER TO PREVIOUS LIST; MANY
 QUESTIONS WERE RAISED IN THAT COMMENT LIST AND NOT
 ANSWERED. A CD WITH HUNDREDS PAGES OF MSDS SHEETS WAS
 PROVIDED. ONE PAGE, NOT SIGNED AND SEALED, NO
 INDICATION OF WHO PREPARED THE INFORMATION, PROVIDED
 THE FOLLOWING ?CHEMICAL DATA?:
  
 IF CHEMICAL IS ACID <250ML
 IF CHEMICAL IS ACETONE <1 LITER
 IF CHEMICAL IS PROPANOL <4 LITER
 IF CHEMICAL IS METHANOL <10 LITER
 IF CHEMICAL IS ACETONITRILE <4 LITER
  
 THIS "CHEMICAL DATA" DOES NOT ADDRESS THE COMMENTS FROM
 PREVIOUS REVIEW. OCCUPANCY CLASSIFICATION OF BUSINESS
 HAS NOT BEEN DEMONSTRATED. THE HAZARD, OR LACK OF
 HAZARD, HAS NOT BEEN DEMONSTRATED WITH THE DOCUMENTS
 PROVIDED. SINCE THE QUANTITIES OF HAZARDOUS MATERIALS
 IS UNCLEAR, COMPLIANCE WITH BUSINESS OCCUPANCY CANNOT
 BE DETERMINED. PREVIOUS REVIEW (ITEM 1B) REQUESTED
 INFORMATION CONSISTENT WITH THE FORMAT OF FBC TABLE
 307.1(1) AND (2). THE QUESTIONS REGARDING THE AMOUNTS
 OF CHEMICALS USED IN EACH CATEGORY, FORM (SOLID,
 LIQUID, GAS), STORAGE, CLOSED OR OPEN SYSTEM, ETC. HAVE
 NOT BEEN ADDRESSED. OCCUPANCY CLASSIFICATION CANNOT BE
 CONFIRMED AS BUSINESS AS HAZARDOUS MATERIALS ARE
 ACKNOWLEDGED TO BE IN STORAGE AND IN USE (VIA THE MSDS
 SHEETS) BUT AMOUNTS OF EACH HAZARD HAS NOT BEEN
 PROVIDED BY THE DESIGN PROFESSIONAL.
  
 EXAMPLES OF HOW THE FORMAT OF THE "CHEMICAL DATA" IS
 GROSSLY INSUFFICIENT AS A RESPONSE TO THE PREVIOUS
 COMMENT LIST:
  
 A. WHAT DOES "IF CHEMICAL IS ACID <250ML" MEAN? AMOUNT
 IN USE, OPEN OR CLOSED, STORED, ALL THREE? 250ML OPEN
 AND CLOSED USE, 250ML STORED, TO EQUAL 750ML? 250ML
 STORED, AND THE CHEMICAL IS NEVER IN USE?
 B. IS THERE MORE THAN ONE ACID USED? 250 ML EACH ACID,
 OR TOTAL OF ALL ACIDS? OF THE 350 PAGES OF DATA
 PROVIDED, HOW MANY ARE ACIDS? ARE ALL OF THESE ACIDS
 CONSIDERED "CORROSIVE" PER THE TABLE, OR ARE ANY ALSO
 "TOXIC" OR "HIGHLY TOXIC"?
 C. HOW HAS ARCHITECT MADE A DETERMINATION OF BUSINESS
 OCCUPANCY WITHOUT THE SPECIFIC INFORMATION REQUESTED
 (QUANTITIES OF HAZARDOUS MATERIALS PER FBC B TABLES
 307.1(1) AND (2)?
 D. IF ARCHITECT HAS THIS INFORMATION, WHY WASN'T IT
 PROVIDED AS REQUESTED?
  
 ONLY A DESIGN PROFESSIONAL (ARCHITECT, ENGINEER) CAN
 DESIGN A COMMERCIAL BUILDING PER FS 471, 481. THE
 BUILDING CLASSIFICATION IS PROVIDED BY THE ARCHITECT,
 BUT THE INFORMATION TO SUPPORT THAT CLASSIFICATION IS
 NOT SIGNED AND SEALED, DOES NOT INCLUDE A TITLE BLOCK
 OR ANY OTHER INFORMATION REGARDING WHO IS PROVIDING THE
 INFORMATION.
  
 REVIEW 2 COMMENT #2.) SEE FBC BUILDING 414.1.3
 INFORMATION REQUIRED. A REPORT SHALL BE SUBMITTED TO
 THE BUILDING OFFICIAL IDENTIFYING THE MAXIMUM EXPECTED
 QUANTITIES OF HAZARDOUS MATERIALS TO BE STORED, USED IN
 A CLOSED SYSTEM AND USED IN AN OPEN SYSTEM, AND
 SUBDIVIDED TO SEPARATELY ADDRESS HAZARDOUS MATERIAL
 CLASSIFICATION CATEGORIES BASED ON TABLES 307.1(1) AND
 307.1(2). THE METHODS OF PROTECTION FROM SUCH HAZARDS,
 INCLUDING BUT NOT LIMITED TO CONTROL AREAS, FIRE
 PROTECTION SYSTEMS AND GROUP H OCCUPANCIES SHALL BE
 INDICATED IN THE REPORT AND ON THE CONSTRUCTION
 DOCUMENTS. THE OPINION AND REPORT SHALL BE PREPARED BY
 A QUALIFIED PERSON, FIRM OR CORPORATION APPROVED BY THE
 BUILDING OFFICIAL AND PROVIDED WITHOUT CHARGE TO THE
 ENFORCING AGENCY.
  
 PRIOR TO RESUBMITTAL, PROVIDE A RESUME OF PERTINENT
 EDUCATION AND EXPERIENCE OF THE PERSON, FIRM OR
 CORPORATION PROPOSED TO PROVIDE THE REPORT FOR BUILDING
 OFFICIAL APPROVAL. THE RESUME SHOULD BE SUBMITTED VIA
 EMAIL FOR APPROVAL PRIOR TO RESUBMITTAL.
  
 REVIEW 2 COMMENT #3.) SEE ALSO FBC BUILDING 414.1.2,
 WHICH STATES THAT THE SAFE DESIGN OF HAZARDOUS MATERIAL
 OCCUPANCIES IS MATERIAL DEPENDENT. THE HAZARD, OR LACK
 OF HAZARD, IS STILL NOT CLEAR AS THE REQUESTED (AND
 REQUIRED) INFORMATION WAS NOT PROVIDED. IT IS CLEAR
 THAT HAZARDOUS MATERIALS WILL BE IN USE AND WILL BE
 STORED AT THIS LABORATORY, BUT QUANTITIES AND
 COMPLIANCE WITH ALL REQUIREMENTS OF FBC BUILDING 307
 AND 414 ARE NOT CLEAR. THIS SHOULD BE ADDRESSED BY THE
 REPORT.
  
 REVIEW 2 COMMENT #4.) ARCHITECT'S RESPONSE REGARDING
 THE NITROGEN GENERATOR (1B) INSTRUCTS THE PLAN REVIEWER
 TO NOTE THAT NITROGEN IS AN INERT GAS, NA PER FBC TABLE
 307.1(1) AND ALSO REFERS TO ATTACHED EQUIPMENT
 SPECIFICATIONS. THERE ARE A FEW ISSUES WITH THIS
 STATEMENT:
  
 A. WHERE ARE THE EQUIPMENT SPECS LOCATED? NONE OF THE
 15 PDFS PROVIDED ON CD (TOTALING ALMOST 350 PAGES) WAS
 TITLED IN A MANNER WHICH WOULD INDICATE IT INCLUDED
 GENERATOR SPECS. IF INFORMATION REQUESTED IN PLAN
 REVIEW IS CONTAINED SOMEWHERE WITHIN HUNDREDS OF PAGES
 ON A CD, PLEASE PROVIDE FILE NAME AND PAGE. NONE OF THE
 HAZARDOUS MATERIALS ARE REFERENCED ON THE ARCHITECT'S
 PLANS.
  
 B. RESPONSE TO CONCERNS REGARDING THE NITROGEN
 GENERATOR WAS TO ADVISE THE REVIEWER TO NOTE THAT
 NITROGEN IS AN INERT GAS, AND THE AMOUNT ALLOWED BY THE
 TABLE IS NA AND THERE IS NO MAXIMUM CONCENTRATION
 LISTED. THE RELEVANCE OF THE RESPONSE THAT NITROGEN IS
 AN INERT GAS IS NOT CLEAR. ALTHOUGH THE AMOUNT ALLOWED
 PER CONTROL AREA IS NOT LIMITED, IT IS CONSIDERED A
 HAZARDOUS MATERIAL, AND ANY AMOUNT IS A RISK TO BE
 CONSIDERED.
  
 C. SINCE NITROGEN IS AN INERT GAS AS STATED, DOES THIS
 MEAN THAT INERT GASES DO NOT PRESENT A HAZARD? EVEN
 WHEN IN COMPRESSED FORM? (SEE FFPC PER FBC B 414.1.2).
 ISN'T NITROGEN A POSSIBLE HEALTH HAZARD? EVEN IF THE
 TABLE STATES "NA" AND THE QUANTITY PER CONTROL AREA IS
 NOT LIMITED, AM I MISINTREPRETING THE CODE TO THINK
 THAT ALL OF THE HAZARDOUS CHEMICALS, INCLUDING INERT
 GASES, INERT PRESSURIZED GASES, OR INERT LIQUIDS BE
 CONSIDERED WHEN PERFORMING A HAZARD ANALYSIS OF A
 FACILITY? ALTHOUGH I AM NOT KNOWLEDGEABLE ABOUT
 HAZARDOUS CHEMICALS, IT WOULD APPEAR THAT THE FACT THAT
 IT IS INERT DOES NOT ELIMINATE RISKS ASSOCIATED WITH
 THE HAZARD, WHICH IS WHY IT IS INCLUDED ON A TABLE OF
 "HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD". THE
 PREVIOUS LIST QUESTIONED THE HAZARD OF NITROGEN AS
 RELATED TO OXYGEN DEPLETION. IS THIS FACT NOT STILL
 APPLICABLE, EVEN THOUGH IT IS "INERT"? AS MOST PLAN
 REVIEWERS, INCLUDING MYSELF, DO NOT HAVE EXTENSIVE
 EDUCATION IN CHEMISTRY, AND THE FBC CANNOT POSSIBLY
 ADDRESS EVERY CHEMICAL AND HAZARD WHICH EXISTS AT THE
 TIME OF THE WRITING OF THE CODE AND ALL CHEMICALS
 INTRODUCED TO THE MARKET AFTER ADOPTION OF THE CODE,
 THE FBC REQUIRES THAT A HAZARD ANALYSIS BE PERFORMED BY
 AN EXPERT (FBC B 414.1.3). IT IS NOT CLEAR WHO HAS
 PROVIDED THE HAZARD RELATED INFORMATION AND WHO HAS
 PERFORMED THE REQUIRED HAZARD ANALYSIS. UPON WHAT
 INFORMATION HAS THE BUSINESS OCCUPANCY BEEN DETERMINED?
 IT IS NOT CLEAR HOW THIS COULD BE CLASSIFIED AS
 BUSINESS WITHOUT THE INFORMATION REQUIRED BY THE
 PREVIOUS LIST AND BY FBC B 414.1.3.
  
 D. THE ARCHITECT'S RESPONSE TO QUESTIONS REGARDING THE
 NITROGEN GENERATOR REFERRED TO THE EQUIPMENT
 SPECIFICATIONS "ATTACHED". THESE QUESTIONS SHOULD BE
 ANSWERED BY THE HAZARD ANALYSIS REPORT OR BY THE DESIGN
 PROFESSIONAL BY INCORPORATING INFORMATION INTO THE
 PLAN. I HAVE SPENT HOURS SEARCHING THE "ATTACHED" FOR
 ANSWERS TO THE CODE RELATED QUESTIONS FROM THE PREVIOUS
 REVIEW, AND IT APPEARS THAT THE ANSWERS ARE NOT
 "ATTACHED"; EITHER NOT INCLUDED (AS IN THE CASE OF THE
 NITROGEN GENERATOR) OR THE DATA NOT PRESENTED IN THE
 CORRECT FORMAT (OVER 300 PAGES OF MSDS SHEETS). ALL
 ISSUES REGARDING THE HAZARDS OF THE FACILITY SHOULD BE
 ADDRESSED IN THE REPORT OR INCORPORATED INTO THE PLAN
 BY THE DESIGN PROFESSIONAL. IT IS NOT REASONABLE TO
 EXPECT FOR A NON EXPERT TO LOCATE ANSWERS IN A LENGTHY
 MANUFACTURER SPECIFICATION BOOK OR ATTEMPT TO CLASSIFY
 EACH CHEMICAL AND ADD THE AMOUNTS, ESPECIALLY WHEN THE
 AMOUNTS ARE NOT CLEAR. THESE QUESTIONS WERE RAISED BOTH
 TO ASSIST THE DESIGN PROFESSIONAL IN PROVIDING ADEQUATE
 INFORMATION TO DEMONSTRATE THAT HAZARDS WERE ADDRESSED
 AS WELL AS TO CONFIRM THE BUSINESS OCCUPANCY
 CLASSIFICATION.
  
 REVIEW 2 COMMENT #5.) THE ISSUES RAISED IN THIS REVIEW
 FOCUS ON ONLY ONE OF THE HAZARDOUS CHEMICALS IN THIS
 LABORATORY. THIS IS AN EXAMPLE OF HOW THE RESPONSE TO
 THE REQUEST FOR ADDITIONAL INFORMATION WAS INSUFFICIENT
 AND GIVES SOME OF THE ITEMS WHICH SHOULD BE CONSIDERED
 WHEN THE EXPERT PREPARES THE HAZARD ANALYSIS. IT IS
 ANTICIPATED THAT THE HAZARD ANALYSIS SHOULD ADDRESS
 MANY THINGS OF WHICH I AM ENTIRELY UNAWARE AS A HAZARD.
 THE PLAN SUBMITTED DOES NOT ACKNOWLEDGE THE EXISTENCE
 OF ANY HAZARDOUS CHEMICALS, YET IT APPEARS THAT AN
 ANALYSIS OF THE CHEMICALS PROPOSED FOR USE SHOULD HAVE
 A SIGNIFICANT IMPACT ON THE DESIGN OF THE SITE
 (STARTING WITH OCCUPANCY CLASSIFICATION), AS WELL AS
 DOCUMENTING THE ARCHITECT?S AND ENGINEER?S FAMILIARITY
 AND KNOWLEDGE OF THE HAZARDS. THE INFORMATION REQUESTED
 IN FIRST REVIEW REGARDING QUANTITIES TO DEMONSTRATE
 THAT THIS IS BUSINESS AND NOT HAZARDOUS OCCUPANCY
 SHOULD HAVE BEEN INCORPORATED INTO THE PLAN, OR A
 REFERENCE THAT THE REQUIRED HAZARD ANALYSIS REPORT HAS
 BEEN REVIEWED BY DORS IF THE ANALYSIS WAS DELEGATED
 (AND THE HAZARD REPORT PROVIDED FOR REVIEW).
  
 REVIEW 2 COMMENT #6.) WHEN RESUBMITTING, REVIEW THE
 PREVIOUS LIST, ITEMS 1 AND 2, AND ADDRESS ALL ITEMS AS
 WELL AS THE ITEMS ON THIS LIST VIA THE HAZARD ANALYSIS
 REPORT, INCORPORATING RESPONSES INTO THE PLAN AS
 APPROPRIATE, AND ADDITIONAL DATA OR SPEC SHEETS AS
 NEEDED. ALL INFORMATION SHOULD BE EASILY LOCATED AND IF
 IT IS NOT, ESPECIALLY AS THE DOR SHOULD BE FAMILIAR
 WITH THESE SPECS ALREADY, PLEASE ADVISE AS TO THE
 LOCATION, IN PARTICULAR IF THE INFORMATION IS CONTAINED
 WITHIN A LARGE DOCUMENT. THE ISSUES AND QUESTIONS
 PRESENTED IN THIS REVIEW AND PREVIOUS REVIEW SHOULD BE
 ADDRESSED IN THE REPORT REQUIRED BY FBC B 414.1.3. THIS
 LIST IS NOT COMPREHENSIVE. THE REPORT SHOULD BE
 COMPREHENSIVE AS AN EXPERT IN THE FIELD SHOULD BE AWARE
 OF ALL POTENTIAL RISKS AND SHOULD KNOW HOW TO PROVIDE
 EVIDENCE OF WHICH HAZARDOUS CHEMICALS (IN PARTICULAR,
 THE CHEMICALS INCLUDED IN THE TABLES) DO NOT PRESENT A
 HAZARD IN THIS APPLICATION, OR HOW THE HAZARD HAS BEEN
 MITIGATED, AND SHOULD PROVIDE THE QUANTITIES AS
 REQUIRED. IT WOULD BE HELPFUL IF AN EXCEL SPREADSHEET
 IS PROVIDED SO THAT MATHEMATICAL FORMULAS CAN BE
 CONFIRMED IF THE LIST OF CHEMICALS IS EXTENSIVE.
  
 IT IS NOT NECESSARY TO PROVIDE A RESPONSE LETTER WITH
 ANSWERS TO THE NUMEROUS ISSUES RAISED IN THE PREVIOUS
 AND THIS REVIEW AS THE REPORT SHOULD CLARIFY ALL ISSUES
 REGARDING ALL HAZARDS, HAZARDOUS MATERIALS (EACH
 CHEMICAL INDIVIDUALLY, POSSIBLE INTERACTIONS, ALL OTHER
 POTENTIAL HAZARDS), ETC. ALL REQUIREMENTS OF FBC B 414,
 307, AND FFPC ARE TO BE CLEARLY ADDRESSED IN THE
 REPORT.
  
 REVIEW 2 COMMENT #7.) SEE FLORIDA STATUTE 553.80(2)(B).
 A FOUR TIMES PLAN REVIEW FEE WILL BE ASSESSED IF THIS
 COMMENT IS NOT ADDRESSED CORRECTLY A THIRD TIME, AS
 REQUIRED BY THE FLORIDA STATUTE.
  
 A SET HAS BEEN RETAINED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-13 Cont ID  
Sent By jwitmer Date 2016-04-13 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2016-04-13 Time 07:59 Sent To  
Notes
2016-04-13 09:43:28BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040307
 ADD: 901 NORTHPOINT PARKWAY SUITES: 119-120
 CONT: CAPITAL CONSTRUCTION & DEVELOPMENT
 TEL: 561-876-2994
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 13/2016
 ACTION: DENIED
  
 1) SHEET A-01 UNDER THE HEADING OF USE AND OCCUPANCY
 LIST THIS TENANT SPACE AS A BUSINESS OCCUPANCY.
  
 1A) IT WOULD APPEAR THE USE OF THIS TENANT SPACE WOULD
 BE A LABORATORY OR TEACHING FACILITY WITH THE TYPE OF
 EQUIPMENT THAT IS ILLUSTRATED ON A2.1A THE EQUIPMENT
 SHEET & ELECTRICAL SHEETS. PLEASE DEFINE THE TYPE OF
 USAGE UNDER THE BUSINESS OCCUPANCY? 2014 FBC-B 304.1.
  
 1B) THE PLANS SHOW THE INSTALLATION OF A NITROGEN
 GENERATOR, HPLC INSTRUMENT, MASS SPECTROMETER.
 WILL THERE BE LC/MS TOXICOLOGY ANALYZER FOR CLINICAL
 RESEARCH & FOR FORENSIC TOXICOLOGY APPLICATIONS, AND A
 AU400 UNIT USED FOR CHEMISTRY ANALYZER? ADDITIONAL
 INFORMATION WILL BE REQUIRED TO DETERMINE IF THIS USAGE
 WILL REMAIN A BUSINESS OCCUPANCY, OR POSSIBLY A
 BUSINESS OCCUPANCY WITH CONTROLLED (1 HR. SEPARATION)
 AREAS, OR CONSIDERED A HAZARDOUS OCCUPANCY. PLEASE ALSO
 SUPPLY A LIST OF ALL CHEMICALS TO BE USED IN THE
 VARIOUS APPLICATIONS, THE CHEMICAL NAME, IF SOLID,
 LIQUID OR GAS, THE AMOUNTS IN EITHER POUNDS, LIQUIDS OR
 IF GAS CUBIC FEET TO BE STORED AT THE SITE .THE PLAN
 INDICATES THE USE OF A STORAGE CABINET, PLEASE PROVIDE
 THE MANUFACTURERS SPEC ON THIS CABINET, IS IT A 1 HOUR
 FIRE RATED CABINET? THE CHEMICALS TO BE STORED, IN A
 CLOSED SYSTEM. WHAT ARE THE AMOUNTS OF THE CHEMICALS TO
 BE USED DAILY NOT IN THE ENCLOSED STORAGE CABINET?
 PLEASE REFER TO THE 2014 FBC-B TABLE 307.1(1). MAXIMUM
 ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS
 MATERIALS POSING A PHYSICAL HAZARD.
  
 1C) FOR THE CHEMICALS TO BE STORED AND OR USED ON SITE
 PLEASE PROVIDE THEIR MSDS SHEETS (MATERIAL SAFETY DATA
 SHEETS), THESE DOCUMENTS WILL HELP TO CLASSIFY THE
 CHEMICALS AS IF HAZARDOUS AND TO IF THIS REMAINS A
 BUSINESS OCCUPANCY, A BUSINESS OCCUPANCY W/ CONTROL
 AREAS AND OR AS A HAZARDOUS OCCUPANCY.
  
 2A) SHEET A2.1A INDICATES THE USE OF A NITROGEN
 GENERATOR. PLEASE PROVIDE HOW MUCH NITROGEN WILL THIS
 SYSTEM, GENERATE, WILL IT BE STORED ON SITE AND TO WHAT
 QUANTITIES, AND IN WHAT TYPE OF CONTAINERS, AND TO WHAT
 PRESSURE WILL THE NITROGEN BE STORED. 2014 FBC-B TABLE
 307.1(1).
  
 2B) NOT HAVING ANY LITERATURE ON THE NITROGEN GENERATOR
 NOR AS TO WHAT PRESSURE THE SYSTEM WILL OPERATE, (NOT
 SHOWN ON PLANS, NO PIPING, VALVES, BACK FLOW PREVENTION
 NOR CROSS OVER PREVENTION) WHAT SAFETY EQUIPMENT OR
 DEVICES WILL BE PROVIDED TO NOTIFY THE OCCUPANTS OF AN
 OXYGEN-DEFICIENT ATMOSPHERE? 2014 FBC-B TABLE 307.1(1).
 MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF
 HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD.
  
 3) LIFE SAFETY SHEET A2.0 HAS DOORS THAT WILL NEED TO
 COMPLY WITH THE 2014 FBC-ACCESSIBILITY CODE;
 3A) EXISTING OFFICE # 1 ENTRY DOOR ,ACCESS. CODE
 404.2.4 MANEUVERING CLEARANCES MISSING THE 18 INCHES
 LATCH SIDE OF THE DOOR.
 3B) EXISTING OFFICE # 3 ENTRY DOOR, ACCESS. CODE
 404.2.4 MANEUVERING CLEARANCES MISSING THE 18 INCHES
 LATCH SIDE OF THE DOOR.
 3C) DOOR 101C NOTE HARDWARE SCHEDULE INDICATES CLOSURE
 TYPE HINGES WILL NEED TO COMPLY WITH, ACCESS. CODE
 404.2.4 MANEUVERING CLEARANCES MISSING THE 12 INCHES
 LATCH SIDE OF THE DOOR SEE FIGURE
 404.2.4.1( C ).
  
 3D) DOOR 103, ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES MISSING THE 18 INCHES LATCH SIDE OF THE
 DOOR.
  
 3E) 2 OF THE 4 DOORS LISTED ABOVE ARE EXISTING AND WILL
 NEED TO BE CORRECTED UNDER THE DISPROPORTIONATE COST
 SECTION OF THE 2014 ACCESSIBILITY CODE, SECTION
 202.4.1. CONTRACT VALUE OF $46,200.00 X 20%= $ 9,240.00
 DOLLARS. SEE THE ORDER OF HOW THE FUNDS ARE TO BE
 SPENT, LISTED BELOW. IF ALL CORRECTIONS HAVE BEEN MADE
 BEFORE ALL OF THE FUNDS WERE USED, THEN COMPLIANCE HAS
 BEEN ACHIEVED. 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 4) THERE ARE NO DETAILS ON THE BREAK ROOM SINK, PLEASE
 SHOW COMPLIANCE WITH 2014 FBC-ACCESS. CODE 606.3
 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 5) THE WORK STATIONS THROUGHOUT THE SUITE DO NOT SHOW
 COMPLIANCE WITH: 2014 FBC-ACCESS. CODE 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) SHEET A2.5 SHOWS THE GRAB BARS MEASURED FROM THE
 CENTERLINE OF THE GRAB BAR. IF THE CONTRACTOR PUTS THE
 BAR AT THE MAXIMUM HEIGHT OF 36 INCHES THEN THE GRAB
 BARS ARE TO HIGH. IN THE 2014 FBC-ACCESS. CODE THE GRAB
 BARS ARE MEASURED FROM THE TOP OF THE GRASPING SURFACE,
 NOT CENTERLINED. 20104 FBC- ACCESS. CODE 609.4.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-07-15 Cont ID  
Sent By vperez Date 2016-07-15 Time 08:05 Rev Time 0.00
Received By vperez Date 2016-07-15 Time 08:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-22 Cont ID  
Sent By vperez Date 2016-06-22 Time 15:24 Rev Time 0.00
Received By vperez Date 2016-06-22 Time 14:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-05-14 Cont ID  
Sent By vperez Date 2016-05-14 Time 07:11 Rev Time 0.00
Received By vperez Date 2016-05-13 Time 12:23 Sent To  
Notes
2016-05-14 08:39:202ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PREVIOUS COMMENT #4 NOT ADDRESSED REGARDING SPECS
 FOR EQUIPMENT. FBC 107.3.5
 2. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By vperez Date 2016-04-11 Time 09:19 Rev Time 0.00
Received By vperez Date 2016-04-11 Time 06:18 Sent To  
Notes
2016-04-11 09:20:18APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE
 PERMITS FOR THE LOW VOLTAGE SYSTEMS. FBC 107.3
 2. CLARIFY BUS AMP RATING OF THE 42 SPACE PANEL BOARDS
 SHOWN AT 100AMP BUT NOT MANUFACTURED IN MORE THAN A
 30/40 SPACE DESIGN.
 3. THE ABOVE COMMENT IMPACTS THE BREAKER SIZE,
 EQUIPMENT GROUNDING CONDUCTOR SHOWN AS EXISTING ETC.
 PLEASE CLARIFY AND CORRELATE.
 4. PROVIDE SPECS SHEET FOR ALL EQUIPMENT TO INCLUDE THE
 NITROGEN GENERATOR, FORE PUMPS ETC. FBC 107.3.5
 5. PROVIDE A NOTE AT THE SERVICE TO LABEL AND ID PER
 NEC 230.2E. A NOTE WILL SUFFICE
 6. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-07-18 Cont ID  
Sent By pleduc Date 2016-07-18 Time   Rev Time 0.00
Received By pleduc Date 2016-07-18 Time 15:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-06-24 Cont ID  
Sent By pleduc Date 2016-06-24 Time   Rev Time 0.00
Received By pleduc Date 2016-06-24 Time 14:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-05-23 Cont ID  
Sent By scaldero Date 2016-05-23 Time 14:21 Rev Time 0.00
Received By scaldero Date 2016-05-23 Time 14:17 Sent To  
Notes
2016-05-23 14:21:32DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-11 Cont ID  
Sent By scaldero Date 2016-04-11 Time 13:28 Rev Time 0.00
Received By scaldero Date 2016-04-11 Time 13:27 Sent To  
Notes
2016-04-11 13:28:29PERMIT # 16040307
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-07-19 Cont ID  
Sent By shill Date 2016-07-19 Time 12:52 Rev Time 0.00
Received By shill Date 2016-07-13 Time 13:08 Sent To  
Notes
2016-07-13 13:08:28B32

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-11 Cont ID  
Sent By shill Date 2016-07-11 Time 07:50 Rev Time 0.00
Received By shill Date 2016-06-15 Time 14:00 Sent To  
Notes
2016-06-16 14:00:25B31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-23 Cont ID  
Sent By shill Date 2016-05-23 Time 17:27 Rev Time 0.00
Received By shill Date 2016-05-05 Time 14:24 Sent To  
Notes
2016-05-05 14:24:38B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-29 Cont ID  
Sent By cpuell Date 2016-04-29 Time 08:09 Rev Time 0.00
Received By cpuell Date 2016-04-05 Time 10:05 Sent To  
Notes
2016-04-06 10:05:26B14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-04-13 Cont ID  
Sent By jwitmer Date 2016-04-13 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2016-04-13 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-07-19 Cont ID  
Sent By hmoser Date 2016-07-19 Time 10:10 Rev Time 0.00
Received By hmoser Date 2016-07-19 Time 09:45 Sent To  
Notes
2016-07-19 10:10:23PASS PROVISO
 REFER TO SECTION 607.5.3 FIRE PARTITIONS
 DUCTS AND TRANSFER OPENINGS THAT PENETRATE FIRE
 PARTITIONS
 SHALL BE PROTECTED WITH LISTED FIRE DAMPERS INSTALLED
 IN
 ACCORDANCE WITH THERE LISTING.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 516-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-07-08 Cont ID  
Sent By ccole Date 2016-07-08 Time 10:46 Rev Time 0.00
Received By ccole Date 2016-06-17 Time 10:45 Sent To B
Notes
2016-07-08 10:53:303RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040307
 7/8/16
  
 1) THE SUBMITTED ALTERNATE DESIGN METHOD FOR THE
 MECHANICAL VENTILATION WAS NOT APPROVED BY BUILDING
 OFFICIAL ROBERT BROWN. THE ENGINEER OF RECORD BEN ELLIS
 P.E. HAS AGREED TO RESUBMIT BOTH CORRECTED PLANS AND A
 REVISED LETTER REQUEST FOR ALTERNATE DESIGN APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-05-12 Cont ID  
Sent By ccole Date 2016-05-12 Time 10:20 Rev Time 0.00
Received By ccole Date 2016-05-12 Time 10:20 Sent To  
Notes
2016-05-12 10:32:482ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040307
 5/12/16
  
 1) THE RE-SUBMITTED PLANS DO NOT INDICATE THAT COMMENTS
 #1, 2, & 3 HAVE BEEN ADDRESSED COMPLETELY. I AM
 RE-PRINTING THOSE COMMENTS BELOW FOR REVIEW BY THE
 DESIGN PROFESSIONALS.
  
 1) REFER TO SECTIONS 809.1 AND 809.2 FBC-14 EXISTING
 BUILDING AND PROVIDE MINIMUM VENTILATION CALCULATIONS
 FOR ALL ROOMS AND SPACES OF THE NEW OCCUPANCY IN
 ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL. PLEASE
 NOTE THAT PER SECTION 403.3 THE NEW LAB MUST BE
 VENTILATED PER THE RATES INDICATED FOR SCIENCE
 LABORATORIES INCLUDING A .7 CFM PER SQ. FT. EXHAUST
 RATE.
 **PLEASE NOTE THAT IN RESPONSE TO THIS COMMENT ABOVE
 THE DESIGN PROFESSIONAL HAS PROVIDED THE REQUIRED O/A
 CALCULATIONS, HOWEVER THE REQUESTED EXHAUST VENTILATION
 SYSTEM AND CALCULATIONS FOR THE LAB AREA ARE NOT SHOWN
 ON THE PLAN.**
  
 2) REFER TO SECTION 414.1.3 FBC-14 BUILDING AND SHOW
 COMPLIANCE FOR CHEMICAL STORAGE IN THE NEW OCCUPANCY.
 [F] 414.1.3 INFORMATION REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
 FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP
 H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING
 THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO
 AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF
 EVERY BUILDING AND STRUCTURE.
  
 3) PROVIDE MANUFACTURER'S SPECIFCATIONS AND DATA SHEETS
 FOR THE FORE PUMP AND EXHAUST SYSTEM, AND ALL OTHER
 EQUIPMENT THAT REQUIRE EXHAUST SYSTEMS SUCH AS THE
 NIOTROGEN GENERATOR. PROVIDE ON THE PLANS EXHAUST
 SYSTEM DIAGRAMS INDICATING THE TYPES AND SIZES OF
 EXHAUST PIPES AND DUCTS, EXHAUST RUN LENGTHS, AND
 TERMINATION LOCATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-07 Cont ID  
Sent By ccole Date 2016-04-07 Time 16:26 Rev Time 0.00
Received By ccole Date 2016-04-07 Time 16:26 Sent To  
Notes
2016-04-07 17:06:121ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040307
 4/7/16
  
 1) REFER TO SECTIONS 809.1 AND 809.2 FBC-14 EXISTING
 BUILDING AND PROVIDE MINIMUM VENTILATION CALCULATIONS
 FOR ALL ROOMS AND SPACES OF THE NEW OCCUPANCY IN
 ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL. PLEASE
 NOTE THAT PER SECTION 403.3 THE NEW LAB MUST BE
 VENTILATED PER THE RATES INDICATED FOR SCIENCE
 LABORATORIES INCLUDING A .7 CFM PER SQ. FT. EXHAUST
 RATE.
 2) REFER TO SECTION 414.1.3 FBC-14 BUILDING AND SHOW
 COMPLIANCE FOR CHEMICAL STORAGE IN THE NEW OCCUPANCY.
 [F] 414.1.3 INFORMATION REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
 FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP
 H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING
 THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO
 AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF
 EVERY BUILDING AND STRUCTURE.
 3) PROVIDE MANUFACTURER'S SPECIFCATIONS AND DATA SHEETS
 FOR THE FORE PUMP AND EXHAUST SYSTEM, AND ALL OTHER
 EQUIPMENT THAT REQUIRE EXHAUST SYSTEMS SUCH AS THE
 NIOTROGEN GENERATOR. PROVIDE ON THE PLANS EXHAUST
 SYSTEM DIAGRAMS INDICATING THE TYPES AND SIZES OF
 EXHAUST PIPES AND DUCTS, EXHAUST RUN LENGTHS, AND
 TERMINATION LOCATIONS.
 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FOR EXHAUST OUTLETS TO
 MECHANICAL AND GRAVITY AIR INTAKES.
 5) PROVIDE CONTROLS OPERATION AND SUPERVISION DETAILS
 FOR THE NEW DUCT SMOKE DETECTORS. CLARIFY IF ALL AC
 SYSTEMS WILL BE LINKED TOGETHER FOR FAN SHUT DOWN IF
 ONE SYSTEM DETECTOR ACTIVATES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-06-24 Cont ID  
Sent By gearl Date 2016-06-24 Time 08:38 Rev Time 0.00
Received By gearl Date 2016-06-24 Time 08:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-05-13 Cont ID  
Sent By gjohnson Date 2016-05-13 Time 10:03 Rev Time 0.00
Received By gjohnson Date 2016-05-13 Time 10:03 Sent To  
Notes
2016-05-13 10:16:382ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. WE STILL NEED A COMPLETE LIST OF CHEMICALS WITH THE
 STATE THEY ARE BEING STORED IN THE AMOUNTS AND WHAT
 TYPE OF CONTAINER. PLEASE PROVIDE ON PLAN. PER WPB
 AMEND TO FBC SEC.107.2.1
  
 2. PLEASE PROVIDE DIMENSIONS OF THE SINK YOUR USING FOR
 SERVICE SINK IT SHOULD BE BIG ENOUGH TO RECEIVE 5-7 GAL
 OF WATER DUMPED IN IT AND NOT OVER FLOW. PER WPB AMEND
 TO FBC SEC. 107.2.1
  
 3. PLEASE PROVIDE A RISER DIAGRAM WITH SIZES AND
 LENGTHS FOR THE VENT SYSTEM ON FORE PUMP, SOLVENT VENT
 AND PROTECTOR HOOD ALSO DETAILS OF WHAT TYPE OF PIPING
 IS BEING USED. PER WPB AMEND. TO FBC SEC.107.2.1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-20 Cont ID  
Sent By gjohnson Date 2016-04-20 Time 15:17 Rev Time 0.00
Received By gjohnson Date 2016-04-20 Time 12:45 Sent To  
Notes
2016-04-20 16:05:571ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. A2.1A + SHT. P-2 EQUIPMENT LIST L14 + L15 DO
 NOT SHOW ANY PLUMBING REQUIREMENTS THEY ARE SHOWN ON
 PLUMBING DOES ANY OTHER EQUIPMENT REQUIRE PLUMBING.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 2. TOILET PAPER HOLER SHALL COMPLY WITH ALL DEMINSIONS
 OF FBC ACCC.SEC 604.7
  
 3. SHT. P2 EQUIPMENT LIST SHOWS A 2IN. DRAIN FOR L5 IT
 IS NOT SHOWN ON SANITARY RISER.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 4. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 5. SHT. A1.0 THE NOTE ON THE PLAN INDICATES 2 ADA
 UNISEX BATHROOMS SEPARATE FACILITIES ARE REQUIRED PER
 FBC PL SEC. 403.2
 PLEASE INDICATE ON ALL SHEETS MEN'S OR WOMEN'S BATHROOM
 WPB AMEND. TO FBC SEC. 107.2.1
  
 6. WHERE ARE THE CHEMICALS USED IN THIS LAB BING
 DISPOSED OF.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 7. PLEASE PROVIDE MSDS SHEETS ON ALL CHEMICALS USED AND
 A REPORT CONTAINING A LISTING OF ALL CHEMICALS, THE
 AMOUNTS , THE STATE, WHAT TYPE OF CONTAINER THEY ARE
 STORED IN.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
  
  
  