Plan Review Details - Permit 16040196
Plan Review Stops For Permit 16040196
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-06 Cont ID  
Sent By shill Date 2016-06-06 Time 15:48 Rev Time 0.00
Received By shill Date 2016-06-06 Time 15:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 15:59 Rev Time 0.00
Received By shill Date 2016-05-24 Time 15:52 Sent To  
Notes
2016-05-24 16:00:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB. PLEASE SEND VIA EMAIL IF POSSIBLE.
  
 PLANS ARE SIGNED AND STAMPED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-21 Cont ID  
Sent By jwitmer Date 2016-04-21 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2016-04-21 Time 09:05 Sent To  
Notes
2016-04-21 10:14:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040196
 ADD: 531 SOUTHERN BLVD SUITE # ????
 CONT: ALONSO & ASSOCIATES
 TEL: 561-837-9820
 E-MAIL: AALONSO@ALONSOAND ASSOCIATES.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. APRIL 21/ 2016
 ACTION: DENIED
  
 1) SHEET A-202:
  
 1A) THE RESTROOM WILL NEED TO SHOW THE SIZE OF THE
 LAVATORY TO SHOW COMPLIANCE WITH THE:
  
 2014 FBC-ACCESSIBILITY CODE 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 1B) THE RESTROOM ALSO SHOWS A SHOWER WITH A DEPTH OF 2
 FEET 8 INCHES, PLEASE PROVIDE COMPLIANCE WITH SECTION
 608.2.2 FBC-ACCESS. CODE MINIMUM DEPTH OF 36 INCHES.
  
 1C) THE ACCESSIBLE RESTROOM SHOWER SHOWS A SEAT IN THE
 SHOWER BUT THE WALL EXTENDS PAST THE END OF THE SEAT.
 PLEASE REVIEW 2014 FBC-ACCESSIBILITY CODE FIGURE
 608.2.1 & FIGURE 608.2.2.
  
 2) PLEASE SHOW AN ACCESSIBLE ENTRANCE INTO THE TENANT
 SPACE. 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS
 OF EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 PLEASE NOTE IF THE NEW SWING DOOR IN THE NORTHEAST
 CORNER OF THE BUILDING IS GOING TO BE THE ACCESSIBLE
 ENTRANCE THEN THERE NEEDS TO BE A 5-0 FOOT TURNING
 RADIUS AT THE DOOR. ACCESS. CODE
 405.7.4 CHANGE IN DIRECTION. RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM.
  
 405.7.5 DOORWAYS.
 WHERE DOORWAYS ARE LOCATED ADJACENT TO A RAMP LANDING,
 MANEUVERING CLEARANCES REQUIRED BY 404.2.4 AND 404.3.2
 SHALL BE PERMITTED TO OVERLAP THE REQUIRED LANDING
 AREA. SEE FIGURE 404.2.4.1(H)
 THE TOP OF THE RAMP HAS TO TRANSITION INTO A LEVEL
 LANDING AND HAVE 2-0 FEET BEFORE THE CLOSEST PORTION OF
 THE DOOR.
  
  
 3) DISCREPANCY IN SHEETS A-202 & A-203. SHEET A-202 THE
 TENANT SEPARATION WALL IS SHORTER THAN DEPICTED IN
 A-203. DISCREPANCY, 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) SHEET A-201 IN THE NORTHEAST CORNER OF THE BUILDING
 INDICATES THE REMOVAL OF A OVERHEAD DOOR. SHEET A-202
 SHOWS A NEW EXTERIOR SWING DOOR AND WALL INFILL. THE
 PLANS DO NOT PROVIDE ANY INFORMATION AS TO WHAT
 MATERIALS ARE TO BE USED IN THE INFILL, COLUMNS AND
 BLOCK, STEEL STUDS, ETC?
 107.2.1.3 ADDITIONAL INFORMATION./ 107.3.5.1.1(8)
 BUILDING ENVELOPE, MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS.
  
 5) THE PLANS WILL ALSO NEED TO PROVIDE COMPLIANCE WITH
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 6A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS.
  
 6B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 7) SHEET A-202 THE RESTROOM GRAB RAILS ARE MEASURED TO
 THE CENTERLINE OF THE GRAB RAIL. PLEASE BE AWARE OF THE
 CHANGE IN THE 2014 ACCESS. CODE FOR THE HEIGHT OF GRAB
 BARS AND THE MEASURING OF GRAB BARS IS NOW FROM FINISH
 FLOOR TO THE TOP OF THE GRASPING SURFACE OF THE GRAB
 BAR.
 2014 FBC-ACCESS. CODE A609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-13 Cont ID  
Sent By mvaldes Date 2016-06-13 Time 15:26 Rev Time 0.00
Received By mvaldes Date 2016-06-13 Time 15:26 Sent To  
Notes
2016-06-13 15:28:10SENT TO GEORGE PLUMBING

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-05-18 Cont ID  
Sent By mvaldes Date 2016-05-18 Time 14:02 Rev Time 0.00
Received By mvaldes Date 2016-05-16 Time 18:52 Sent To  
Notes
2016-05-18 14:03:58JOB PERMIT NUMBER: 16040196
 JOB ADDRESS: 531 SOUTHERN BLVD.
 WEST PALM BEACH FLORIDA
 DATE: MAY 18 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 THESE ARE COMMENTS TO YOUR RESPONSES!
  
 - 1) NEW SET OF PLANS DON?T SHOW NEC 2011 IN THE
 GENERAL DEMO NOTES AS PREVIOUSLY REQUESTED.
 - 2) THE MANUFACTURE CUT SHEETS FOR THE GENERATOR AND
 ATS EQUIPMENT WEREN?T PROVIDED WITH THE SUBMITTAL.
 GENERATOR PERMITS ARE ISSUED SEPARATELY.
 - 3) THE SITE PLAN WAS RECOGNIZED AND DOES SHOW THE
 LOCATION OF THE GENERATOR. COMPLIED.
 - 4) THE SERVICE RISER DIAGRAM DOESN?T INDICATE A
 GROUNDING DETAIL PER NEC 250.30(6) ALL SEPARATELY
 DERIVED SYSTEM GROUNDING SHALL BE TIED IN WITH A TAP TO
 A COMMON ELECTRODE CONDUCTOR AT THE SAME POINT AT EACH
 SYSTEM.
 - 5) PLEASE ADD NEC 110.15 HIGH LEG MARKING TO THE
 RISER DIAGRAM, NEC 110.16 ARC-FLASH HAZARD WARNING
 LABEL, & NEC 110.24 AVAILABLE FAULT CURRENT MARKINGS.
 FURTHERMORE A PERMANENT PLAQUE SHALL BE INSTALLED TO
 IDENTIFY ALL SERVICES, FEEDERS, AND BRANCH CIRCUITS
 POWERING THE BUILDING. NEC 230.2(E).
 - 6) IT WAS UNDERSTOOD THAT THE GENERATOR ISN?T A
 SEPARATELY DERIVED SYSTEM THEREFORE DOESN?T NEED TO BE
 LISTED AS SERVICE RATED. COMPLIED.
 - 7) IT WAS UNDERSTOOD THAT THE GENERATOR ISN?T A
 SEPARATELY DERIVED SYSTEM THEREFORE DOESN?T NEED TO BE
 LISTED AS SERVICE RATED. JUST FOR CLARIFICATION IN THE
 FUTURE JUST SHOW GROUND ROD AS AN AUXILIARY GROUNDING
 ELECTRODE. COMPLIED.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-14 Cont ID  
Sent By albarran Date 2016-04-14 Time 18:42 Rev Time 0.00
Received By albarran Date 2016-04-14 Time 16:05 Sent To  
Notes
2016-04-14 18:43:36FAILED 1ST ELECTRICAL REVIEW
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 1. GENERAL DEMOLITION NOTES #10 YOU SHALL INDICATE THE
 ACTUAL CODE BY WHICH THE SYSTEM IS DESIGNED. (2011
 EDITION OF THE NEC).
 2. IF THE GENERATOR IS PART OF THE SCOPE OF THIS
 PROJECT, A SEPARATE PERMIT FOR THE GENERATOR WILL BE
 REQUIRED. YOU SHALL PROVIDE MANUFACTURER SPEC SHEETS
 FOR THE GENERATOR.
 3. YOU SHALL ALSO SUBMIT A SITE PLAN REFLECTING THE
 PROPOSED LOCATION OF THE GENERATOR.
 4. SERVICE RISER DIAGRAM FAILS TO INCLUDE THE REQUIRED
 GROUNDING DETAIL. PROVIDE SERVICE GROUNDING FOR EACH
 SERVICE AND CONNECTED THEM AS PER NEC 250.30(6).
 5. PROVIDE PLACARDS AND LABELS AS REQUIRED BY THE
 VARIOUS ARTICLES OF THE NEC: 230.2(E); 110.15; 110.16
 AND 110.24.
 6. SUBMIT MANUFACTURER SPEC FOR THE ATS. IT SHALL BE
 SERVICE RATED.
 7. IF THE INTENT IS TO PROVIDE A SEPARATELY DERIVED
 SERVICE FOR THE GENERATOR, THE ATS SHALL BE CAPABLE OF
 OPENING THE GROUNDED CONDUCTOR, OTHERWISE THE GROUNDING
 ELECTRODE INDICATED ADJACENT TO THE GENERATOR SHALL BE
 REMOVED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
2016-04-13 08:59:39WHEN I WENT TO THE BIN, THE FILE WAS NOT THERE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-13 Cont ID  
Sent By pleduc Date 2016-05-13 Time   Rev Time 0.00
Received By pleduc Date 2016-05-13 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-04-07 Cont ID  
Sent By pleduc Date 2016-04-07 Time   Rev Time 0.00
Received By pleduc Date 2016-04-07 Time 11:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-06-16 Cont ID  
Sent By gjohnson Date 2016-06-16 Time 10:25 Rev Time 0.00
Received By gjohnson Date 2016-06-16 Time 10:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-06-16 Cont ID  
Sent By gjohnson Date 2016-05-12 Time 08:51 Rev Time 0.00
Received By gjohnson Date 2016-05-12 Time 08:51 Sent To  
Notes
2016-05-12 09:05:111ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 (1) THE PRESURE ON THE OUTLET OF THE METER IS UNCLEAR
 IF IT IS .5 LBS. YOU DON'T NEED A LOW PRESURE
 REGULATOR. PLEASE CLARIFY. PER WPBAMEND.TO FBC 107.2.1
  
 (2) IF IT IS REQUIRED TO HAVE A METER YOU NEED A VALVE
 UPSTEAM OF METER AND A SEDIMIT TRAP UP STEAM OF THE
 REGULATOR AND SHALL COMPLY WITH.
  
 2014 FBC GAS SEC.
  
 410.2 MP REGULATORS. MP PRESSURE REGULATORS SHALL
 COMPLY WITH THE FOLLOWING:
  
 1. THE MP REGULATOR SHALL BE APPROVED AND SHALL BE
 SUITABLE FOR THE INLET AND OUTLET GAS PRESSURES FOR THE
 APPLICATION.
  
 2. THE MP REGULATOR SHALL MAINTAIN A REDUCED OUTLET
 PRESSURE UNDER LOCKUP (NO-FLOW) CONDITIONS.
  
 3. THE CAPACITY OF THE MP REGULATOR, DETERMINED BY
 PUBLISHED RATINGS OF ITS MANUFACTURER, SHALL BE
 ADEQUATE TO SUPPLY THE APPLIANCES SERVED.
  
 4. THE MP PRESSURE REGULATOR SHALL BE PROVIDED WITH
 ACCESS. WHERE LOCATED INDOORS, THE REGULATOR SHALL BE
 VENTED TO THE OUTDOORS OR SHALL BE EQUIPPED WITH A
 LEAK-LIMITING DEVICE, IN EITHER CASE COMPLYING WITH
 SECTION 410.3.
  
 5. A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED BETWEEN THE MP REGULATOR AND ITS
 UPSTREAM SHUTOFF VALVE. SUCH TEE FITTING SHALL BE
 POSITIONED TO ALLOW CONNECTION OF A PRESSURE-MEASURING
 INSTRUMENT AND TO SERVE AS A SEDIMENT TRAP.
  
 6. A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED NOT LESS THAN 10 PIPE DIAMETERS
 DOWNSTREAM OF THE MP REGULATOR OUTLET. SUCH TEE FITTING
 SHALL BE POSITIONED TO ALLOW CONNECTION OF A
 PRESSURE-MEASURING INSTRUMENT.
  
 (3) A SEDIMET TRAP IS REQUIRED AT THE APPLIANCE.PER FBC
 GAS SEC. 408.4 SEDIMENT TRAP.
 WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT
 TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED
 NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE
 BOTTOMMOST OPENING OF THE TEE AS ILLUSTRATED IN FIGURE
 408.4 OR OTHER DEVICE APPROVED AS AN EFFECTIVE SEDIMENT
 TRAP. ILLUMINATING APPLIANCES, RANGES, CLOTHES DRYERS,
 DECORATIVE VENTED APPLIANCES FOR INSTALLATION IN VENTED
 FIREPLACES, GAS FIREPLACES, AND OUTDOOR GRILLS NEED NOT
 BE SO EQUIPPED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-16 Cont ID  
Sent By gjohnson Date 2016-06-16 Time 10:26 Rev Time 0.00
Received By gjohnson Date 2016-06-03 Time 14:31 Sent To  
Notes
2016-06-03 14:31:22C33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-24 Cont ID  
Sent By shill Date 2016-05-24 Time 16:00 Rev Time 0.00
Received By shill Date 2016-05-10 Time 15:35 Sent To  
Notes
2016-05-10 15:35:46C33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-27 Cont ID  
Sent By jwitmer Date 2016-04-27 Time 09:15 Rev Time 0.00
Received By gjohnson Date 2016-04-05 Time 14:22 Sent To  
Notes
2016-04-05 14:22:48C06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-04-21 Cont ID  
Sent By jwitmer Date 2016-04-21 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2016-04-21 Time 10:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-04-06 Cont ID  
Sent By jvalido Date 2016-04-06 Time 12:49 Rev Time 0.00
Received By jvalido Date 2016-04-06 Time 10:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-06-13 Cont ID  
Sent By gearl Date 2016-06-13 Time 13:55 Rev Time 0.00
Received By gearl Date 2016-06-13 Time 13:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-05-12 Cont ID  
Sent By gjohnson Date 2016-05-12 Time 08:29 Rev Time 0.00
Received By gjohnson Date 2016-05-12 Time 08:29 Sent To  
Notes
2016-05-12 08:36:592ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.TWO BATHROOMS ARE REQUIRED. PER FBC PL SEC. 403.2
 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 EXCEPTIONS:
  
 1. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR
 DWELLING UNITS AND SLEEPING UNITS.
  
 2. SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 STRUCTURES OR TENANT SPACES WITH A TOTAL OCCUPANT LOAD,
 INCLUDING BOTH EMPLOYEES AND CUSTOMERS, OF 15 OR FEWER.
  
 3. SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 MERCANTILE OCCUPANCIES IN WHICH THE MAXIMUM OCCUPANT
 LOAD IS 100 OR FEWER.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-26 Cont ID  
Sent By gjohnson Date 2016-04-26 Time 10:30 Rev Time 0.00
Received By gjohnson Date 2016-04-26 Time 10:30 Sent To  
Notes
2016-04-26 13:36:33 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. TWO DRINKING FOUNTAINS REQUIRED. PER FBC ACC. SEC.
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 2. SHT.A-202
 (A) DETAIL #2 SHOWS LAVATORY ENCROACHING ON CLEAR
 FLOORSPACE FOR TOILET IT SHALL COMPLY TO FBC ACC. SEC.
 604.3.1
  
 (B) DETAIL #3 SHOW COMPLIANCE WITH FBC ACC. SEC.
  
 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES (150 MM)
 MAXIMUM FROM ADJACENT WALLS.
 .
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 610.3 SHOWER COMPARTMENT SEATS.
 WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS,
 AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT
 IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN
 TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE
 BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
  
 610.3.2 L-SHAPED SEATS.
 THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 2 1/2 INCHES
 (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES (380 MM)
 MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM THE SEAT
 WALL. THE REAR EDGE OF THE ?L? PORTION OF THE SEAT
 SHALL BE 11/2 INCHES (38 MM) MAXIMUM FROM THE WALL AND
 THE FRONT EDGE SHALL BE 14 INCHES (355 MM) MINIMUM AND
 15 INCHES (380 MM) MAXIMUM FROM THE WALL. THE END OF
 THE ?L? SHALL BE 22 INCHES (560 MM) MINIMUM AND 23
 INCHES MAXIMUM (585 MM) FROM THE MAIN SEAT WALL.
  
 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL.
  
 (C) DETAIL # 4 SHOW COMPLIANCE WITH MIN. AND MAX. PER
 FBC ACC. SEC.
  
 609.4 POSITION OF GRAB BARS. MEASURED TO TOP OF
 GRIPPING SURFACE
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
  
 3. PROVIDE MANUFACTURE SPECS FOR WATER HEATER. PER WPB
 AMEND. TO FBC SEC. 107.2.1
  
 4. PROVIDE BACK FLOW FOR HUMIDIFIER PER FBC PL SEC.
 608.3
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  