Plan Review Details - Permit 16040171
| Plan Review Stops For Permit 16040171 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-05-03 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-05-03 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-05-03 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-04-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-04-12 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-04-12 |
Time |
14:33 |
Sent To |
E |
|
| Notes |
| 2016-04-12 14:51:21 | 1ST REVIEW: FBC 2014 5TH ED | | | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | 1. VALUE APPEARS LOW. | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY | | | DELAY THE APPLICATION PROCESS. | | | | | | 2. DESIGNER TO SIGN DRAWINGS. | | | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | 3. DRAWINGS INELIGIBLE. | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | | RECORDS MANAGEMENT. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-05-03 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-05-03 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-05-03 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-04-13 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-04-13 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-04-13 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2016-04-13 14:11:34 | 1ST REVIEW 4/13/16 | | | 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | | | | | | | | | | -107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | | | | - PLANS ARE SKETCHED WITH PENCIL WHICH IS NON PERMANET | | | , THERES A HOME DEPOT SEAL STATING NOT TO COPYWRITE | | | THERE PLANS. | | | - ADD GENERAL ELECTRICAL NOTES NEC 406.11 TAMPER | | | RESISTANT RECEPTACLES , FBC-ER 404.1.1 / 402.4.4 | | | RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT AS WELL AS | | | IC RATED AND SEALED TO NOT COMPROMISE BUILDING THERMAL | | | ENVELOPE. ( 2CFM ), SMOKE ALARMS PER RESIDENTIAL CODE | | | SECTIONS 314 & 315. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-04-13 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-04-13 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-04-05 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2016-04-11 13:49:34 | BLDG MISC 2 |
|
|
|