| 2016-04-07 10:25:25 | ELECTRICAL REVIEW COMMENTS |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 |
| | EDITION |
| | |
| | CORRECTIONS REQUIRED: |
| | 1. PER FAC 61G4-15.021(D) THE SCOPE OF A CVC LICENSE |
| | PROHIBITS THE CONNECTION OF THE PV SYSTEM INTO THE |
| | INTEGRAL BLDG. WIRING. A LICENSED ELECTRICAL CONTRACTOR |
| | IS REQUIRED TO SECURE A PERMIT FOR SAME. |
| | 2. ACCORDING TO THE SUBMITTED PLANS, THE PROPOSED AC |
| | INTERCONNECT CABLE IS TO BE A #10 AWG THWN-2 AND THE |
| | SPEC SHEET PROVIDED FOR THE CABLE INDICATES IT TO BE A |
| | #12 AWG THWN-2. |
| | 3. PER NEC 705.12(7) INVERTER OUTPUT CONNECTION, A |
| | PERMANENT LABEL SHALL BE APPLIED TO THE DISTRIBUTION |
| | WITH THE FOLLOWING WORDING: WARNING INVERTER OUTPUT |
| | CONNECTIONS DO NOT RELOCATE THIS OVERCURRENT DEVICE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |
| 2016-04-06 11:15:56 | I CALLED THE CONTRACTOR TO INQUIRE ON THE TYPE OF CABLE |
| | BEING PROPOSED TO CONNECT THE INVERTERS TO THE JUNCTION |
| | BOX. I ALSO HAD HIM CORRECTED THE STATION |
| | IDENTIFICATION AND COST SAVINGS PARAMETERS TO A LOCAL |
| | ADDRESS AS OPPOSED TO MIAMI FLORIDA. |