Plan Review Details - Permit 16040077
Plan Review Stops For Permit 16040077
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-04-12 Cont ID  
Sent By cthroop Date 2016-04-12 Time 13:26 Rev Time 0.00
Received By cthroop Date 2016-04-12 Time 12:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-26 Cont ID  
Sent By albarran Date 2016-04-26 Time 11:26 Rev Time 0.00
Received By albarran Date 2016-04-26 Time 08:16 Sent To I
Notes
2016-04-26 11:28:02IMPORTANT NOTICE TO INSPECTOR CONTRACTOR
 SEPARATE
 ELECTRICAL PERMIT
 REQUIRED
 IMPORTANT NOTICE
 PER FAC RULE 61G4-15.021, A SEPARATE ELECTRICAL PERMIT
 BY A LICENSED ELECTRICAL CONTRACTOR IS REQUIRED FOR THE
 CONNECTION TO THE PREMISES INTEGRAL WIRING OR UTILITY
 SERVICE. SEE MARKING ON APPROVED PLANS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-07 Cont ID  
Sent By albarran Date 2016-04-07 Time 10:24 Rev Time 0.00
Received By albarran Date 2016-04-06 Time 08:25 Sent To B
Notes
2016-04-07 10:25:25ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 1. PER FAC 61G4-15.021(D) THE SCOPE OF A CVC LICENSE
 PROHIBITS THE CONNECTION OF THE PV SYSTEM INTO THE
 INTEGRAL BLDG. WIRING. A LICENSED ELECTRICAL CONTRACTOR
 IS REQUIRED TO SECURE A PERMIT FOR SAME.
 2. ACCORDING TO THE SUBMITTED PLANS, THE PROPOSED AC
 INTERCONNECT CABLE IS TO BE A #10 AWG THWN-2 AND THE
 SPEC SHEET PROVIDED FOR THE CABLE INDICATES IT TO BE A
 #12 AWG THWN-2.
 3. PER NEC 705.12(7) INVERTER OUTPUT CONNECTION, A
 PERMANENT LABEL SHALL BE APPLIED TO THE DISTRIBUTION
 WITH THE FOLLOWING WORDING: WARNING INVERTER OUTPUT
 CONNECTIONS DO NOT RELOCATE THIS OVERCURRENT DEVICE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
2016-04-06 11:15:56I CALLED THE CONTRACTOR TO INQUIRE ON THE TYPE OF CABLE
 BEING PROPOSED TO CONNECT THE INVERTERS TO THE JUNCTION
 BOX. I ALSO HAD HIM CORRECTED THE STATION
 IDENTIFICATION AND COST SAVINGS PARAMETERS TO A LOCAL
 ADDRESS AS OPPOSED TO MIAMI FLORIDA.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-26 Cont ID  
Sent By albarran Date 2016-04-26 Time 11:28 Rev Time 0.00
Received By albarran Date 2016-04-22 Time 14:54 Sent To  
Notes
2016-04-26 11:34:204/26/16 PASSED ELECTRICAL REVIEW WITH EXCEPTIONS NOTED.
 CONTRACTOR NOTIFIED VIA EMAIL. FILE SENT TO SMALL READY
 BIN "P". MA
2016-04-22 14:54:38RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-12 Cont ID  
Sent By cthroop Date 2016-04-12 Time 13:26 Rev Time 0.00
Received By cthroop Date 2016-04-04 Time 14:42 Sent To  
Notes
2016-04-04 14:42:39ROUTED TO ELECTRICAL INBOX