Plan Review Details - Permit 16040042
Plan Review Stops For Permit 16040042
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-12 Cont ID  
Sent By jwitmer Date 2016-08-12 Time 10:33 Rev Time 0.00
Received By jwitmer Date 2016-08-12 Time 07:44 Sent To  
Notes
2016-08-12 10:33:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040042
 ADD: 1865 N. TAMARIND AVE.
 CONT: T. H. MOTTLEY
 TEL: 561-644-4081
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. AUGUST 12/2016
 ACTION: DENIED
  
 NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) PLEASE NOTE NO NARRATIVE SUBMITTED. ) WHEN
 RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1A) 2ND REQUEST. SHEET 2OF 6 THE CODE DATA INDICATES
 THE OCCUPANCY AS A A-2 OCCUPANCY BUT THE OCCUPANCY LOAD
 IS STATED AT 15. WITH THE OCCUPANT LOAD LESS THAN 50
 OCCUPANTS THIS OCCUPANCY IS CLASSIFIED AS A BUSINESS
 OCCUPANCY. THE PLANS SUBMITTED INDICATE THE KITCHEN 278
 SQ. FT./ 300= 1 NET. FBC-B TABLE 1004.1,2, COMMERCIAL
 KITCHENS ARE TO BE TAKEN AT 200 SQ. FT./ OCCUPANT. THE
 A-2 ASSEMBLY AREA IS 577 SQ. FT./ 15= 39 OCCUPANTS. 39
 +2= 41 OCCUPANTS.
  
 THIS REVIEW A SITE PLAN WAS SUBMITTED SHOW A DECK, 2
 PERGOLAS BUT AGAIN NO OUTSIDE SEASONAL SEATING THAT MAY
 MAKE THIS AN A2 OCCUPANCY.
 SEE 2014 FBC-B 303.1.1 SMALL BUILDINGS AND TENANT
 SPACES. A BUILDING OR TENANT SPACE USED FOR ASSEMBLY
 PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS
 SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY.
  
 1B) NEW COMMENT THE PERMIT APPLICATION INDICATES UNDER
 THE DESCRIPTION OF WORK, PERGOLAS, WATER FOUNTAIN AND
 LANDSCAPING. UNDER THIS REVIEW SHEET 5OF 6 A SITE PLAN
 DOES INDICATE THESE ELEMENTS IN THE CONCEPT DRAWINGS.
 PLEASE NOTE NO ADDITIONAL PLANS HAVE BEEN SUBMITTED FOR
 ANY OF THESE ELEMENTS. EACH OF THESE ELEMENTS WILL
 REQUIRE A SEPARATE PERMIT AND PLANS. THIS FOR
 INSPECTION TRACKING PURPOSES AS WELL AS RECORD KEEPING.
 107.2.1.4 QUALITY OF BUILDING PLANS. . THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
  
  
  
 2)2ND REQUEST. SHEET 2 OF 6 INDICATES THIS BUILDING
 TYPE AS A BUILDING TYPE III-B. PLEASE PROVIDE A SURVEY
 FOR THE DISTANCE FROM THE PROPERTY LINES CAN BE
 ESTABLISHED AND CODE COMPLIANCE WITH:
 2014 FBC-B TABLE 602 & TABLE 705.8.
  
 3) 2ND REQUEST. PLEASE NOTE FIELD VERIFY THAT THE FRONT
 ENTRY IS AT GRADE. GOOGLE EARTH SHOWS SHUTTERS ACROSS
 THE FRONT DOOR, A SITE VISIT WILL BE REQUIRED. SHEET 4
 OF 6 SHOWS THE FRONT ENTRY AT GRADE. PLEASE VISIT THE
 SITE FOR VERIFICATION WITH THE FRONT ENTRY IS AN
 ACCESSIBLE ENTRY, THAT THE ENTRY IS FLUSH WITH THE
 EXTERIOR AND THERE IS A THRESHOLD OF NOT MORE THAN 1/2
 INCH IN HEIGHT.
 2014 FBC-ACCESS. CODE 404.3.3 THRESHOLDS. THRESHOLDS
 AND CHANGES IN LEVEL AT DOORWAYS SHALL COMPLY WITH
 404.2.5.
 2014 FBC-ACCESS. CODE 404.2.5 THRESHOLDS. THRESHOLDS,
 IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303. EXCEPTION:
 EXISTING OR ALTERED THRESHOLDS 3/4 INCH (19 MM) HIGH
 MAXIMUM THAT HAVE A BEVELED EDGE ON EACH SIDE WITH A
 SLOPE NOT STEEPER THAN 1:2 SHALL NOT BE REQUIRED TO
 COMPLY WITH 404.2.5.
  
 4) 2ND REQUEST. SHEET A-2 & A-4 BOTH INDICATES NEW
 WINDOWS AND DOORS, NO PRODUCT APPROVALS WERE SUBMITTED
 PLEASE SHOW COMPLIANCE WITH: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, IF INSTALLED, WALL
 LOUVERS,
 (D) IF INSTALLED, ROOFING PRODUCTS AND ASSEMBLIES,
 CURBS, INTAKE & EXHAUST ROOF TOP FANS, ROOF TOP RTUS
 (G) IF INSTALLED, PRE-ENGINEERED A/C STANDS
  
  
 5)2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6)2ND REQUEST. NOTICE COIL ROOF NAILS: ROOFING: NOTICE:
 EFFECTIVE APRIL 1/2016 THE REFERENCED MIAMI-DADE COUNTY
 ELECTROGALVANIZED FASTENERS LISTINGS ARE SUSPENDED:
 11--1019.02 & 11-1019.03 BLUELINX CORP.
 12-0423.06 CONTINENAL MATERIALS, INC.
 15-1123.04 PRIME SOURCE BUILDING PRODUCTS, INC.
 13-0530.01 SPECIALTY FASTENING SYSTEM
 12-0423.03 & 12-0423.04 SUMMIT CONGLOMERATE, LLC
 12-1205.11, 12-1205.13 & 13-05 & 13-0514.05 WEATHERPRO,
 LLC
  
 7) 2ND REQUEST. FOR ALL ROOF TOP EQUIPMENT, CURBS OR
 A/C STANDS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE. 2014 FBC-B 1604.4 ANALYSIS. LOAD
 EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS
 SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS
 THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY,
 GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?
  
 8A)2ND REQUEST DEPENDING ON THE PRODUCT APPROVALS FOR
 THE WINDOWS PRESSURES (MULLION) GIVEN MAYBE OR MAYBE
 NOT BE COMPLIANT FOR THE PRESSURES GIVEN ON 2 OF 6.
  
 8B) PLEASE NOTE SHEET 2 OF 6 LIST THIS IN A EXPOSURE D
 JOBSITE LOCATION. THE DESIGNER CAN DESIGN TO A MORE
 STRINGENT REQUIREMENT BUT THE PRESSURES WILL ALSO
 INCREASE AS WELL. THE PRESSURES GIVEN DO NOT STATE FOR
 WHAT SIZE OPENING THEY ARE FOR. SEE COMPONENTS &
 CLADDING PRESSURES POSITIVE & NEGATIVE FBC-B TABLE
 1609.2(2) .
  
 8C) NEW COMMENT. SHEET 2 OF 6 ON BOTH THE 1ST AND 2ND
 SET OF PLANS THE WIND DESIGN FOR BOTH THE ULTIMATE AND
 DESIGN WIND SPEED ARE BOTH 170 MPH, 3 SECOND GUST. 2014
 FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 9) 2ND REQUEST. 2014 FBC-B 1013.6 MECHANICAL EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 10) 2ND REQUEST. 2014FBC-B 1509.6.4 EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES. WHERE
 EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE INSTALLED
 ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT EXCEEDING
 16 FEET (4877 MM), SUCH ACCESS SHALL BE PROVIDED BY A
 PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH
 SHALL BE FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE
 GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE).
  
 11) 2ND REQUEST. PLEASE PROVIDE RESTROOM ELEVATIONS TO
 SHOW CODE COMPLIANCE FOR ACCESSIBLE RESTROOM ELEMENTS,
 PROVIDE WIDTH AND HEIGHT ELEVATION INCOMPLIANCE WITH
 2014 FBC-ACCESS. CHAPTER 6.
  
 12) 2ND REQUEST. SHOW COMPLIANCE WITH: 2014 FBC-ACCESS.
 CODE 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 13)2ND REQUEST. 2014 FBC-ACCESS. CODE 902.2 CLEAR FLOOR
 OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH SHALL BE PROVIDED.
 KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 14) 2ND REQUEST. 2014 FBC-ACCESS. CODE 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 15) 2ND REQUEST. 2014 FBC-ACCESS. CODE 703.1SIGNS SHALL
 COMPLY WITH 703. RESTROOM SIGNAGE. WHERE BOTH VISUAL
 AND TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN
 WITH BOTH VISUAL AND TACTILE CHARACTERS, OR TWO
 SEPARATE SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED
  
 16) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-04-20 Cont ID  
Sent By jwitmer Date 2016-04-20 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2016-04-20 Time 06:46 Sent To  
Notes
2016-04-20 07:34:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040042
 ADD: 1865 N. TAMARIND AVE.
 CONT: T. H. MOTTLEY
 TEL: 561-644-4081
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 20/2016
 ACTION: DENIED
  
 1) SHEET S-1THE CODE DATA INDICATES THE OCCUANCY AS A
 A-2 OCCUPANCY BUT THE OCCUPANCY LOAD IS STATED AT 15.
 WITH THE OCCUPANT LOAD LESS THAN 50 OCCUPANTS THIS
 OCCUPANCY IS CLASSIFIED AS A BUSINESS OCCUPANCY. SEE
 2014 FBC-B 303.1.1 SMALL BUILDINGS AND TENANT SPACES. A
 BUILDING OR TENANT SPACE USED FOR ASSEMBLY PURPOSES
 WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS SHALL BE
 CLASSIFIED AS A GROUP B OCCUPANCY.
  
 2) SHEET S-1 INDICATES THIS BUILDING TYPE AS A BUILDING
 TYPE III-B. PLEASE PROVIDE A SURVEY FOR THE DISTANCE
 FROM THE PROPERTY LINES CAN BE ESTABLISHED AND CODE
 COMPLIANCE WITH:
 2014 FBC-B TABLE 602 & TABLE 705.8.
  
 3) SHEET S-2 DOES NOT SHOW IF THE FRONT ENTRY IS AN
 ACCESSIBLE ENTRY, THAT THE ENTRY IS FLUSH WITH THE
 EXTERIOR AND THERE IS A THRESHOLD OF NOT MORE THAN 1/2
 INCH IN HEIGHT.
 2014 FBC-ACCESS. CODE 404.3.3 THRESHOLDS. THRESHOLDS
 AND CHANGES IN LEVEL AT DOORWAYS SHALL COMPLY WITH
 404.2.5.
 2014 FBC-ACCESS. CODE 404.2.5 THRESHOLDS. THRESHOLDS,
 IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303. EXCEPTION:
 EXISTING OR ALTERED THRESHOLDS 3/4 INCH (19 MM) HIGH
 MAXIMUM THAT HAVE A BEVELED EDGE ON EACH SIDE WITH A
 SLOPE NOT STEEPER THAN 1:2 SHALL NOT BE REQUIRED TO
 COMPLY WITH 404.2.5.
  
 4) SHEET S-2 INDICATES NEW WINDOWS AND DOORS, NO
 PRODUCT APPROVALS WERE SUBMITTED PLAESE SHOW COMPLIANCE
 WITH: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, IF INSTALLED, WALL
 LOUVERS,
 (D) IF INSTALLED, ROOFING PRODUCTS AND ASSEMBLIES,
 RURBS, INATAKE & EXHAUST ROOF TOP FANS, ROOF TOP RTUS
 (G) IF INSTALLED, PRE-ENGINEERED A/C STANDS
  
  
 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6) NOTICE COIL ROOF NAILS: ROOFING: NOTICE: EFFECTIVE
 APRIL 1/2016 THE REFERENCED MIAMI-DADE COUNTY
 ELECTROGALVANIZED FASTENERS LISTINGS ARE SUSPENDED:
 11--1019.02 & 11-1019.03 BLUELINX CORP.
 12-0423.06 CONTINENAL MATERIALS, INC.
 15-1123.04 PRIME SOURCE BUILDING PRODUCTS, INC.
 13-0530.01 SPECIALTY FASTENING SYSTEM
 12-0423.03 & 12-0423.04 SUMMIT CONGLOMERATE, LLC
 12-1205.11, 12-1205.13 & 13-05 & 13-0514.05 WEATHERPRO,
 LLC
  
 7) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?
  
 8) DEPENDING ON THE PRODUCT APPROVALS FOR THE WINDOWS
 PRESSURES (MULLION) GIVEN MAYBE OR MAYBE NOT BE
 COMPLIANT FOR THE PRESSURES GIVEN ON SHEET S3.
  
 9) 2014 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL
 BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF
 HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE
 ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL EXTEND NOT
 LESS THAN 30 INCHES (762 MM) BEYOND EACH END OF SUCH
 APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 10) 2014FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877
 MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT
 APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE
 FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE
 GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE).
  
 11) PLEASE PROVIDE RESTROOM ELEVATIONS TO SHOW CODE
 COMPLIANCE FOR ACCESSIBLE RESTROOM ELEMENTS, PROVIDE
 WIDTH AND HEIGHT ELEVATION INCOMPLIANCE WITH 2014
 FBC-ACCESS. CHAPTER 6.
  
 12) SHOW COMPLIANCE WITH: 2014 FBC-ACCESS. CODE 226.1
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
  
 13) 2014 FBC-ACCESS. CODE 902.2 CLEAR FLOOR OR GROUND
 SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH SHALL BE PROVIDED.
 KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 14) 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 15) 2014 FBC-ACCESS. CODE 703.1SIGNS SHALL COMPLY WITH
 703. RESTROOM SIGNAGE. WHERE BOTH VISUAL AND TACTILE
 CHARACTERS ARE REQUIRED, EITHER ONE SIGN WITH BOTH
 VISUAL AND TACTILE CHARACTERS, OR TWO SEPARATE SIGNS,
 ONE WITH VISUAL, AND ONE WITH TACTILE CHARACTERS, SHALL
 BE PROVIDED
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-13 Cont ID  
Sent By vperez Date 2016-08-13 Time 13:50 Rev Time 0.00
Received By vperez Date 2016-08-13 Time 13:50 Sent To  
Notes
2016-08-13 13:53:022ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS NOT ADDRESSED, PROVIDE A NARATIVE:
  
 1. PLEASE SHOW THE REQUIRED EM LIGHTING FOR THE SPACE
 UNDER SCOPE, EITHER BY WALL PACKS OR EM BALLAST. FBC
 107.3.5
 2. SHOW THE RECEPTACLES OUTLETS IN THE SPACE AND LABEL
 EXISTING IF NOT NEW. FBC 107.3.5
 3. LABEL CIRCUIT ID DESIGNATION FOR ALL LIGHTING AND
 RECEPTACLE OUTLETS TO CORRELATE WITH PANEL SCHEDULE
 SHOWN. FBC 107.3.5
 4. SHOW RTU ON ROOFTOP AND A RECEPTACLE OUTLET WITHIN
 25FT TO WP/WR GFCI PROTECTED. NEC 210.63
 5. CLARIFY IF THERE IS AN EXISTING SHOW WINDOW
 RECEPTACLES PER NEC 210.62
 7. PLANS TO BE SIGNED AND SEALED BY DESIGNER OF RECORD.
 FBC FLORIDA STATUE
 6. FEEL FREE TO CONTACT ME WITH ANY QUESTIONS OR
 CONCERNS.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-06 Cont ID  
Sent By vperez Date 2016-04-06 Time 10:23 Rev Time 0.00
Received By vperez Date 2016-04-06 Time 09:30 Sent To  
Notes
2016-04-06 10:24:42INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE SHOW THE REQUIRED EM LIGHTING FOR THE SPACE
 UNDER SCOPE, EITHER BY WALL PACKS OR EM BALLAST. FBC
 107.3.5
 2. SHOW THE RECEPTACLES OUTLETS IN THE SPACE AND LABEL
 EXISTING IF NOT NEW. FBC 107.3.5
 3. LABEL CIRCUIT ID DESIGNATION FOR ALL LIGHTING AND
 RECEPTACLE OUTLETS TO CORRELATE WITH PANEL SCHEDULE
 SHOWN. FBC 107.3.5
 4. SHOW RTU ON ROOFTOP AND A RECEPTACLE OUTLET WITHIN
 25FT TO WP/WR GFCI PROTECTED. NEC 210.63
 5. CLARIFY IF THERE IS AN EXISTING SHOW WINDOW
 RECEPTACLES PER NEC 210.62
 6. FEEL FREE TO CONTACT ME WITH ANY QUESTIONS OR
 CONCERNS.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-08 Cont ID  
Sent By pleduc Date 2016-08-08 Time   Rev Time 0.00
Received By pleduc Date 2016-08-08 Time 16:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-04-06 Cont ID  
Sent By pleduc Date 2016-04-06 Time   Rev Time 0.00
Received By pleduc Date 2016-04-06 Time 14:53 Sent To  
Notes
2016-04-06 15:56:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET S 1 - PER NFPA 1 AND 101, THE INDICATED
 ASSEMBLY OCCUPANCY ISINCORRECT.
  
 PER NFPA 101, 6.1.2.1* DEFINITION ? ASSEMBLY OCCUPANCY.
 AN OCCUPANCY (1) USED FOR A GATHERING OF 50 OR MORE
 PERSONS FOR DELIBERATION, WORSHIP, ENTERTAINMENT,
 EATING, DRINKING, AMUSEMENT, AWAITING TRANSPORTATION,
 OR SIMILAR USES; OR (2) USED AS A SPECIAL
 AMUSEMENTBUILDING, REGARDLESS OF OCCUPANT LOAD.
  
 YOUR OCCUPANCY DOES NOT MEET THIS DEFINITION AND IS
 THEREFORE CLASSIFIED AS A MERCANTILE OCCUPANY. PER NFPA
 101 * "RESTAURANTS AND DRINKING ESTABLISHMENTS WITH AN
 OCCUPANT LOAD OF FEWER THAN 50 PERSONS SHOULD BE
 CLASSIFIED AS MERCANTILE
 OCCUPANCIES."
  
 THE OCCUPANCY SHALL COMPLY WITH NFPA 101, CHAPTER 36,
 NEW MERCANTILE OCCUPANCIES
  
 2. SHEET S 2 - AN EXISTING HOOD SYSTEM IS INDICATED.
 PER CHAPTER 36, 36.3.2.3 COOKING EQUIPMENT. COOKING
 EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE WITH 9.2.3,
 UNLESS THE COOKING EQUIPMENT IS ONE OF THE FOLLOWING
 TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 PLEASE INDICATE WITH A NOTE THAT THE SYSTEM IS
 CURRENTLY COMPLIANT WITH A SYSTEM CERTIFICATION TAG OR
 THE SYSTEM WILL HAVE A CURRENT CERTIFICATION TAG ON
 FINAL FIRE INSPECTION.
  
 3. SHEET S 2 - THE DOOR SCHEDULE DOES NOT INDICATE THE
 TYPE OF LOCKS OR HARDWARE. PER CHAPTER 36, 36.2.2.2
 DOORS.
  
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 PER CHAPTER 7, MEANS OF EGRESS, 7.2.1.5.3 LOCKS, IF
 PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, A TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THESPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE LOCATED
 AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN
 THE DOOR LEAF WITH NOT MORE THAN ONE RELEASING
 OPERATION, UNLESS OTHERWISE SPECIFIED IN 7.2.1.5.10.3,
 7.2.1.5.10.4, OR 7.2.1.5.10.6.
  
  
  
 4. SHEET S 3 - THERE IS NO ROOF HOOD VENTILATION
 EQUIPEMNT SHOWN ON THE BUILDING ELEVATIONS. PLEASE
 PROVIDE APPROPRIATE DRAWINGS.
  
 5. SHEET S 3 - PROVIDE INDICATION OF THE ROOF STRUCTURE
 MATERIAL. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS
 REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 6. SHEET E 1 - AN EXIT SIGN IS INDICATED IN THE PREP
 ROOM LEADING INTO THE KITCHEN AREA. IT IS NONCOMPLIANT,
 PER CHAPTER 36, 36.2 MEANS OF EGRESS REQUIREMENTS.
  
 36.2.1 GENERAL.
 36.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER 7 AND THIS CHAPTER.
  
 36.2.5 ARRANGEMENT OF MEANS OF EGRESS.
  
 36.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH SECTION 7.5.
  
 PER CHAPTER 7, 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO
 7.1.9 AND 7.2.1.5.
  
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS
 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR
 SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO
 LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS
 PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, 19, 22, OR
 23.
  
  
 THE EXIT SIGN CAN BE PLACED INSIDE THE KITCHEN LEADING
 TO THE PREP ROOM ONLY. PLEASE CORRECT.
  
  
 7. ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE NOTED COMMENTS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-08-22 Cont ID  
Sent By gjohnson Date 2016-08-22 Time 11:03 Rev Time 0.00
Received By gjohnson Date 2016-08-22 Time 11:03 Sent To  
Notes
2016-08-22 11:04:55GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-22 Cont ID  
Sent By gjohnson Date 2016-08-22 Time 11:01 Rev Time 0.00
Received By gjohnson Date 2016-08-04 Time 15:58 Sent To  
Notes
2016-08-05 11:04:19B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-25 Cont ID  
Sent By gjohnson Date 2016-04-25 Time 10:31 Rev Time 0.00
Received By gjohnson Date 2016-04-01 Time 10:24 Sent To  
Notes
2016-04-04 10:24:38B10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-04-20 Cont ID  
Sent By jwitmer Date 2016-04-20 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2016-04-20 Time 06:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-17 Cont ID  
Sent By hmoser Date 2016-08-17 Time 08:52 Rev Time 0.00
Received By hmoser Date 2016-08-17 Time 08:52 Sent To P
Notes
2016-08-17 09:10:32PLAN DENIED
 PAGE 4 OF 6 SHOW NEW AHU NO PLAN OR INFORMATION
 SUBMITTED WITH PLANS. SECTION 107 FBC 2014.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-05 Cont ID  
Sent By hmoser Date 2016-04-05 Time 09:28 Rev Time 0.00
Received By hmoser Date 2016-04-05 Time 09:28 Sent To  
Notes
2016-04-05 09:32:18PLAN DENIED
 PAGE S-3 SHOWS NEW AIR CONDITIONING UNIT. KNOW PLAN
 SUBMITTED
 FOR AIR CONDITIONING . PER SECTION 107 FBC 2014
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-08-22 Cont ID  
Sent By gjohnson Date 2016-08-22 Time 10:07 Rev Time 0.00
Received By gjohnson Date 2016-08-22 Time 10:07 Sent To  
Notes
2016-08-22 10:48:342ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
  
  
  
 1. THE MIRROR SHALL COMPLY WITH FBC ACC. 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. /YOU SHOW THE BOTTOM
 OF THE MIRROR AT 24IN ABOVE THE FINISHED FLOOR IF THE
 LAVATORY IS SET AT 34IN TO THE RIM TO ACCOMMODATE KNEE
 A TOE CLEARANCE HOW CAN THE MIRROR BE SET AT 24IN
 PLEASE CLARIFY. PER WPB AMEND TP FBC 107.2.1
  
 2. DOOR TO BATHROOM SHALL COMPLY WITH FBC ACC 603.2.3
 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
  
 (3.) THE WATER CLOSET SHALL COMPLY
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 PLEASE SHOW OVERALL DIMENSIONS OF BATHROOM TO SHOW
 COMPLIANCE
  
 (4) GRAB BARS SHALL COMPLY WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER
  
 (5) TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 (6) LAVATORY SHALL COMPLY WITH FBC ACC 606.2 CLEAR
 FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 (8) PLEASE PROVIDE A WATER RISER DIAGRAM PER WPB AMEND.
 TO FBC SEC. 107.3.5.1.3(3)
  
 (9) A GREASE INTERCEPTOR IS REQUIRED FOR 3 COMP SINK
 AND SERVICE SINK. PER FBC PL SEC. 1003.1 WHERE
 REQUIRED.
 INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO
 PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER
 SUBSTANCES HARMFUL OR HAZARDOUS TO THE PUBLIC SEWER,
 THE PRIVATE SEWAGE SYSTEM OR THE SEWAGE TREATMENT PLANT
 OR PROCESSES.
 PROVIDE MANUFACTURE CALCULATIONS FOR GREASE INTERCEPTOR
  
 (10) IDENTIFY THE FIXTURE UPSTEAM OF THE WATER CLOSET.
 NO OTHER FIXTURES CAN TIE INTO THE WET VENT. THE 3 COMP
 SINK HAND SINK SHALL TIE IN DOWN STREAM OF BATHROOM
 GROUP. PER FBC PL SEC. 912.1
  
 (11) THE 3 COMP. SINK SHALL BE INDIRECT WASTE. PER FBC
 PL SEC. 802.1 OR 802.1.8
  
 (12) SHT. E-1 SHALL BE SIGNED AND SEALED PER FAC
 61G15-23.001
  
 13. A SERVICE SINK IS REQUIRED .PER FBC PL TABLE 403.1
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-22 Cont ID  
Sent By gjohnson Date 2016-04-22 Time 17:26 Rev Time 0.00
Received By gjohnson Date 2016-04-22 Time 17:26 Sent To  
Notes
2016-04-22 17:53:331ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 (1) DRINKING FOUNTAINS SHALL COMPLY WITH FBC ACC.
 SEC.602.1 GENERAL.
 DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602.
  
 (2) THE MIRROR SHALL COMPLY WITH FBC ACC. 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 (3.) THE WATER CLOSET SHALL COMPLY WITH FBC ACC 604.2
 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
 604.3 CLEARANCE.
 CLEARANCES AROUND WATER CLOSETS AND IN TOILET
 COMPARTMENTS SHALL COMPLY WITH 604.3.
  
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 304.3.1 CIRCULAR SPACE.
 THE TURNING SPACE SHALL BE A SPACE OF 60 INCHES (1525
 MM) DIAMETER MINIMUM. THE SPACE SHALL BE PERMITTED TO
 INCLUDE KNEE AND TOE CLEARANCE COMPLYING WITH 306.
  
 304.3.2 T-SHAPED SPACE.
 THE TURNING SPACE SHALL BE A T-SHAPED SPACE WITHIN A 60
 INCH (1525 MM) SQUARE MINIMUM WITH ARMS AND BASE 36
 INCHES (915 MM) WIDE MINIMUM. EACH ARM OF THE T SHALL
 BE CLEAR OF OBSTRUCTIONS 12 INCHES (305 MM) MINIMUM IN
 EACH DIRECTION AND THE BASE SHALL BE CLEAR OF
 OBSTRUCTIONS 24 INCHES (610 MM) MINIMUM. THE SPACE
 SHALL BE PERMITTED TO INCLUDE KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 ONLY AT THE END OF EITHER THE BASE
 OR ONE ARM.
  
 (4) GRAB BARS SHALL COMPLY WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER
  
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 609.3 SPACING.
 THE SPACE BETWEEN THE WALL AND THE GRAB BAR SHALL BE 1
 1/2 INCHES (38 MM). THE SPACE BETWEEN THE GRAB BAR AND
 PROJECTING OBJECTS BELOW AND AT THE ENDS SHALL BE 1 1/2
 INCHES (38 MM) MINIMUM. THE SPACE BETWEEN THE GRAB BAR
 AND PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305
 MM) MINIMUM.
  
 (5) TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 (6) LAVATORY SHALL COMPLY WITH FBC ACC 606.2 CLEAR
 FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 (7) THIS OCCUPANCY CAN NOT BE CLASSIFIED A A-2 PER FBC
 303.1.1 IT IS CLASSIFIED AS B WITH A OCCUPANT LOAD OF 9
  
 (8) PLEASE PROVIDE A WATER RISER DIAGRAM PER WPB AMEND.
 TO FBC SEC. 107.3.5.1.3(3)
  
 (9) A GREASE INTERCEPTOR IS REQUIRED FOR 3 COMP. SINK
 AND SERVICE SINK. PER FBC PL SEC. 1003.1 WHERE
 REQUIRED.
 INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO
 PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER
 SUBSTANCES HARMFUL OR HAZARDOUS TO THE PUBLIC SEWER,
 THE PRIVATE SEWAGE SYSTEM OR THE SEWAGE TREATMENT PLANT
 OR PROCESSES.
  
 (10) IDENTIFY THE FIXTURE UPSTEAM OF THE WATER CLOSET.
 NO OTHER FIXTURES CAN TIE INTO THE WET VENT. THE 3 COMP
 SINK HAND SINK SHALL TIE IN DOWN STREAM OF BATHROOM
 GROUP. PER FBC PL SEC. 912.1
  
 (11) THE 3 COMP. SINK SHALL BE INDIRECT WASTE. PER FBC
 PL SEC. 802.1 OR 802.1.8
  
 (12) SHT. E-1 SHALL BE SIGNED AND SEALED PER FAC
 61G15-23.001
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-08-04 Cont ID  
Sent By ajones Date 2016-08-04 Time 14:53 Rev Time 0.00
Received By ajones Date 2016-08-03 Time 13:23 Sent To  
Notes
2016-08-04 15:45:588/4/16- PASSED WITH THE FOLLOWING PROVISOS:
  
 1. NEED A LETTER FROM THE PUBLIC WORKS/ ENGINEERING
 APPROVING THE METHOD FOR GARAGE PICKUP.
 2. A SEPARATE LANDSCAPE PERMIT IS REQUIRED PRIOR TO CO
 3. BEFORE THE ISSUANCE OF A CO THE TWO PARCELS WILL
 NEED TO HAVE A UNITY OF TITLE. CONTACT VINCE NOEL AT
 (561) 494-1096.
 4. TTHE NEW WINDOWS SHALL BE OPERABLE. VERIFICATION
 SHALL BE PROVIDED THAT WINDOW TYPE D HAS AT LEAST FOUR
 (4) INCHES BETWEEN THE PANES.
 ANGELLA VANN, AICP
 561-317-8177
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-04-14 Cont ID  
Sent By avann Date 2016-04-14 Time 17:23 Rev Time 0.00
Received By ajones Date 2016-04-14 Time 17:23 Sent To  
Notes
2016-04-14 17:24:414/14/16- FAILED- THE TWO PARCELS WILL NEED TOHAVE A
 UNITY OF TITLE. CONTACT VINCE NOEL AT (561) 494-1096.
 2. THE AMOUNT OF WORK WILL EXCEED 50% OF THE VALUE OF
 THE BUILDING; THEREFORE, A LANDSCAPE PLAN, SIGNED AND
 SEALED BY A LANDSCAPE ARCHITECT, IS REQUIRED PRIOR TO
 THE ISSUANCE OF THE BUILDING PERMIT.
 YOU CAN CONTACT RAY CARANCI, THE CITY LANDSCAPE PLANNER
 AT 561-822-1462 TO DISCUSS LANDSCAPE IMPROVEMENTS.
 3. THE NEW WINDOWS SHALL BE OPERABLE. VERIFICATION
 SHALL BE PROVIDED THAT WINDOW TYPE D HAS AT LEAST FOUR
 (4) INCHES BETWEEN THE PANES.
  
 ANGELLA VANN, AICP
 561-317-8177
 [email protected]