Review Stop G GAS REVIEW
Rev No 5 Status P Date 2016-07-26 Cont ID  
Sent By tklarge Date 2016-07-26 Time 14:45 Rev Time 0.00
Received By tklarge Date 2016-07-26 Time 14:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2016-06-22 Cont ID  
Sent By tklarge Date 2016-06-22 Time 08:36 Rev Time 0.00
Received By tklarge Date 2016-06-22 Time 06:24 Sent To  
Notes
2016-06-22 06:20:181) NOTHING HAS BEEN DONE TO ADDRESS THE PLAN REVIEW
 COMMENTS FROM THE PREVIOUS REVIEW. YOU HAVE SUBMITTED
 THE SAME INCORRECT DRAWING WITH NO CORRECTIONS MADE.
 2) THE CSST LINE TO FP #1 & # 2 IS UNDERSIZED.THIS LINE
 SUPPLYING THE TWO FIREPLACES SHALL BE A MINIMUM OF 1
 1/4" WITH AN EHD OF 37 PER TABLE 402.4 (15) OF 2014
 FUEL GAS CODE.
 3) AN EHD OF 30 IS FOR A 1" CSST LINE, NOT 3/4" PER
 TABLE 402.4 (15) OF THE 2014 FBC-FUEL GAS CODE.
 4) THE MAXIMUM BTU LOAD ON A 1/2" CSST LINE AT 80 FT.
 IS 33,000 BTU'S. THE GAS DRAWING SHOWS A 1/2" CSST LINE
 SUPPLYING FP #1 WHICH IS 70,000 BTU'S. THIS LINE IS
 UNDERSIZED. THIS SHALL BE A MINIMUM OF 1" CSST WITH AN
 EHD OF 30.
 5) I AM TOTALLY CONFUSED WITH YOUR SUBMITTAL FOR THE
 COMBUSTION AIR CALCULATIONS. YOU ARE COMBINING TWO
 SEPARATE CODE SECTIONS TO COMPLY WITH COMBUSTION AIR
 REQUIREMENTS AND IT DOES NOT APPEAR THERE IS COMPLIANCE
 WITH EITHER METHOD.YOUR CALCULATIONS DO NOT MAKE ANY
 SENSE TO ME.CLARIFY.
 NOTE: THIS REVIEW IS SUBJECT TO PAYMENT OF 3 TIMES THE
 PLAN REVIEW FEE DUE TO THE PLANS BEING REJECTED FOR THE
 SAME COMMENTS IN ACCORDANCE WITH FL. STATUTE 553.80
 I SUGGEST THAT THE GAS CONTRACTOR CONTACT ME TO DISCUSS
 THIS ISSUE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2016-05-11 Cont ID  
Sent By tklarge Date 2016-05-11 Time 08:51 Rev Time 0.00
Received By tklarge Date 2016-05-11 Time 06:26 Sent To  
Notes
2016-05-11 06:44:351) THE CSST LINE TO FP #1 & # 2 IS UNDERSIZED.THIS LINE
 SUPPLYING THE TWO FIREPLACES SHALL BE A MINIMUM OF 1
 1/4" WITH AN EHD OF 37 PER TABLE 402.4 (15) OF 2014
 FUEL GAS CODE.
 2) AN EHD OF 30 IS FOR A 1" CSST LINE, NOT 3/4" PER
 TABLE 402.4 (15) OF THE 2014 FBC-FUEL GAS CODE.
 3) THE MAXIMUM BTU LOAD ON A 1/2" CSST LINE AT 80 FT.
 IS 33,000 BTU'S. THE GAS DRAWING SHOWS A 1/2" CSST LINE
 SUPPLYING FP #1 WHICH IS 70,000 BTU'S. THIS LINE IS
 UNDERSIZED. THIS SHALL BE A MINIMUM OF 1" CSST WITH AN
 EHD OF 30.
 4) I AM TOTALLY CONFUSED WITH YOUR SUBMITTAL FOR THE
 COMBUSTION AIR CALCULATIONS. YOU ARE COMBINING TWO
 SEPARATE CODE SECTIONS TO COMPLY WITH COMBUSTION AIR
 REQUIREMENTS AND IT DOES NOT APPEAR THERE IS COMPLIANCE
 WITH EITHER METHOD.YOUR CALCULATIONS DO NOT MAKE ANY
 SENSE TO ME.CLARIFY.
  
 I SUGGEST THAT THE GAS CONTRACTOR CONTACT ME TO DISCUSS
 THIS ISSUE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-04-25 Cont ID  
Sent By tklarge Date 2016-04-25 Time 05:37 Rev Time 0.00
Received By tklarge Date 2016-04-25 Time 05:22 Sent To  
Notes
2016-04-25 05:37:521) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407. 2ND REQUEST.
 2) THE PLANS SHOW PE PIPING BEING INSTALLED INSIDE THE
 STRUCTURE. PE PIPING SHALL ONLY BE INSTALLED OUTSIDE
 UNDERGROUND PER 2014 FBCR SEC.G2415.17.1
 3) THE MAXIMUM BTU LOAD ON A 3/4" SCH.40 METALLIC PIPE
 AT 80 FEET IS 117,000 BTU'S. THE PLANS SHOW A MAXIMUM
 BTU LOAD OF 157,000 BTU'S. THE SYSTEM IS UNDERSIZED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-04-06 Cont ID  
Sent By tklarge Date 2016-04-06 Time 04:41 Rev Time 0.00
Received By tklarge Date 2016-04-06 Time 04:31 Sent To  
Notes
2016-04-06 04:36:441. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-07-26 Cont ID  
Sent By tklarge Date 2016-07-26 Time 14:46 Rev Time 0.00
Received By tklarge Date 2016-07-26 Time 14:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-06-22 Cont ID  
Sent By tklarge Date 2016-06-22 Time 08:36 Rev Time 0.00
Received By tklarge Date 2016-06-21 Time 15:04 Sent To  
Notes
2016-06-21 15:04:39RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-11 Cont ID  
Sent By tklarge Date 2016-05-11 Time 08:51 Rev Time 0.00
Received By tklarge Date 2016-05-10 Time 13:49 Sent To  
Notes
2016-05-10 13:50:02RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-25 Cont ID  
Sent By tklarge Date 2016-04-25 Time 05:38 Rev Time 0.00
Received By tklarge Date 2016-04-22 Time 14:53 Sent To  
Notes
2016-04-22 14:53:17RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-04-06 Cont ID  
Sent By tklarge Date 2016-04-06 Time 04:41 Rev Time 0.00
Received By tklarge Date 2016-03-31 Time 12:37 Sent To  
Notes
2016-03-31 12:38:02PLUMB <5K