Plan Review Details - Permit 16031436
Plan Review Stops For Permit 16031436
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-14 Cont ID  
Sent By rmcdouga Date 2016-07-14 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2016-07-14 Time 07:08 Sent To  
Notes
2016-07-14 11:27:05APPROVED WITH EXCEPTIONS
 1) THE ENTRY DOOR IS SHOWN ON THE PLANS AS 3'-6" X
 8'-0". THE PRODUCT APPROVAL FOR THE ENTRY DOOR HAS A
 MAXIMUM PANEL WIDTH OF 3 FEET. A REVISION TO THE PLAN
 OR ANOTHER PRODUCT APPROVAL IS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-05-02 Cont ID  
Sent By rmcdouga Date 2016-05-02 Time 18:20 Rev Time 0.00
Received By rmcdouga Date 2016-05-02 Time 15:25 Sent To  
Notes
2016-05-02 17:11:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) WOOD CONSTRUCTION NOTE #2 ON SHEET A-1 REFERENCES
 CHAPTER 23 OF THE 2010 FBC. THE CORRECT REFERENCE IS
 CHAPTER 6 OF THE 2014 FBC RESIDENTIAL.
  
 2) THE DOOR FROM THE GARAGE TO THE RESIDENCE IS
 REQUIRED TO HAVE A SELF-CLOSING DEVICE. FBC R302.5.1
  
 3) THERE IS A DISCREPANCY BETWEEN THE PLANS AND THE
 ENERGY COMPLIANCE FORMS. THE TYPICAL WALL SECTION ON
 SHEET A-3 SPECIFIES R-30 INSULATION AND SCREEN VENTS IN
 THE SOFFIT. THE ENERGY FORMS HAVE R-20 INSULATION AND
 AN UN-VENTED ATTIC. CLARIFY. FBC 107.2.1
  
 4) SPECIFY THE REQUIRED DESIGN PRESSURES FOR ROOF ZONES
 1, 2 & 3 FOR THE 5/12 SLOPE ROOF ON THE PLANS. FBC
 R301.2.1
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND "APPROVED IN WRITING BY THE
 DESIGNER OF RECORD". PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE SINGLE HUNG WINDOWS, STRUCTURAL MULLIONS, SLIDING
 GLASS DOORS, ENTRY DOOR AND EXTERIOR OUTSWING DOOR AT
 THE GARAGE.
  
 THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT
 APPROVAL WEBSITE.
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
  
 THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT APPROVAL
 WEBSITE.
 HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 6) THE PRODUCT APPROVAL FOR THE SECTIONAL GARAGE DOOR
 HAS MAXIMUM DESIGN PRESSURES OF +36.0, -44.0 PSF AND
 THE PLAN (SHEET A-2) REQUIRES
 +49.1, -54.0 PSF.
  
 7) SPECIFY WHICH ONE OF THE ROOFING UNDERLAYMENTS
 LISTED IN THE TARCO PRODUCT APPROVAL (FL10450) WILL BE
 USED.
  
 8) VALUATION OF WORK WAS INCREASED TO $336,528.00. FBC
 109.31
  
 IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 RE-SUBMITTAL PROCEDURE
  
 YOU WILL BE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO
 BE SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER
 DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED
 APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE
 REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN
 CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK
 WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER.
 ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED
 SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH
 THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS
 SHALL BE SUBMITTED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-06-28 Cont ID  
Sent By vperez Date 2016-06-28 Time 09:24 Rev Time 0.00
Received By vperez Date 2016-06-28 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By vperez Date 2016-04-04 Time 07:30 Rev Time 0.00
Received By vperez Date 2016-04-04 Time 07:30 Sent To  
Notes
2016-04-04 07:49:21INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SHOW ON DRAWING THE RECEPTACLE OUTLETS
 REQUIRED FOR WALL SPACE SLIDING GLASS DOOR AREA OF THE
 FAMILY ROOM. CLARIFY LAYOUT TO COMPLY WITH FBC RES- SEC
 E3901 2.1 AND 2.2
 2. PROVIDE A NOTE TO COMPLY WITH TAMPER RESISTANT
 RECEPTACLE PER FBC RES-E4002.14
 3. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 4. LABEL GDO RECEPTACLE IN GARAGE TO BE GFCI PROTECTED.
 FBC RES E3902.2
 5. RECEPTACLE REQUIRED AT THE REAR OF DWELLING NO MORE
 THAN 6FT 6INCHES ABOVE GRADE PER FBC RES E3901.7
 6. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-14 Cont ID  
Sent By rmcdouga Date 2016-07-14 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2016-06-16 Time 12:32 Sent To  
Notes
2016-06-17 12:32:59R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-05-02 Cont ID  
Sent By rmcdouga Date 2016-05-02 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2016-03-30 Time 10:20 Sent To  
Notes
2016-03-31 10:20:55R25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-07-15 Cont ID  
Sent By rmcdouga Date 2016-07-15 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2016-07-15 Time 16:02 Sent To  
Notes
2016-07-15 16:04:46MU-2016-17888 PAID $417.24 FOR IMPACT FEES.
2016-07-15 13:55:08RMCDOUGAL'S DESK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-07-14 Cont ID  
Sent By rmcdouga Date 2016-07-14 Time 10:46 Rev Time 0.00
Received By rmcdouga Date 2016-07-14 Time 10:46 Sent To  
Notes
2016-07-14 10:46:38BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-05-02 Cont ID  
Sent By rmcdouga Date 2016-05-02 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2016-05-02 Time 15:25 Sent To  
Notes
2016-05-02 15:27:11BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-12 Cont ID  
Sent By jvalido Date 2016-07-12 Time 16:23 Rev Time 0.00
Received By jvalido Date 2016-07-12 Time 15:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-04-04 Cont ID  
Sent By jvalido Date 2016-04-04 Time 17:19 Rev Time 0.00
Received By jvalido Date 2016-04-04 Time 17:16 Sent To  
Notes
2016-04-04 17:19:33CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION
  
  
 107.1 - PROVIDE MECHANICAL PLANS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-06-23 Cont ID  
Sent By gearl Date 2016-06-23 Time   Rev Time 0.00
Received By gearl Date 2016-06-23 Time 11:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-04-11 Cont ID  
Sent By gjohnson Date 2016-04-11 Time 09:10 Rev Time 0.00
Received By gjohnson Date 2016-04-11 Time 09:10 Sent To  
Notes
2016-04-11 09:10:41PLUMBING COMMENTS:
  
 1.THE TUB AND THE SHOWER IN THE MASTER BATHROOM ARE NOT
 VENTED.
 SHALL COMPLY WITH FBC RES. SEC. P3101.2.1
  
 2.THE BACK TO BACK WATER CLOSETS IN THE MASTER BATHROOM
 AND POWDER ROOM BATH SHALL NOT BE INSTALLED ON A DOUBLE
 SANITARY TEE THE WAY YOU HAVE IT DRAWN ON RISER.
 PER FBC RES.SEC. P3005.1.1
  
 3. IT APPEARS THAT YOU HAVE THE BUILDING DRAIN RUNNING
 PARALLEL UNDER THE FOOTER THIS IS NOT PERMITTED, IT
 ALSO CREATES OTHER PROBLEMS WITH VENTING AND
 CONNECTIONS OF THE PLUMBING SYSTEM.
 PER FBC RES. SEC. R403.1
  
 4.WHAT IS THE 12"X11/2" RECESSED WATER STOP SHT.S1
 PLEASE CLARIFY.
 PER WPB AMEND.TO FBC 107.2.1
  
 5. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW FOR
 THE POOL.
 PER WPB UTILITIES DEPT CROSS CONNECTION MANUAL SEC I
 PG. 19
  
  
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-06-21 Cont ID  
Sent By awooten Date 2016-06-21 Time 13:38 Rev Time 0.00
Received By awooten Date 2016-06-21 Time 16:35 Sent To  
Notes
2016-06-21 16:38:54***SPECIFIC CONDITIONS APPLY SEE ZONING PROVISO***
  
 DO NOT APPROVE FINAL WITHOUT CONFIRMING THAT LANDSCAPE
 PERMIT HAS BEEN ISSUED AND INSPECTION OF LANDSCAPE
 INSTALLATION HAS BEEN APPROVED.
2016-06-21 13:39:29PLANNING AND ZONING COMMENTS:
 6/21/16
 1. IF LANDSCAPE PLAN IS NOT SUBMITTED CONCURRENTLY WITH
 BUILDING PERMIT FOR THE NEW HOUSE CONSTRUCTION, A
 CONDITIONAL APPROVAL FORM WILL NEED TO BE COMPLETED AND
 SUBMITTED TO THE PLANNING DIVISION FOR PROCESSING.
 PLEASE CONTACT THE PLANNING DEPARTMENT FOR A COPY OF
 THIS FORM IF YOU WISH TO PROCEED WITH THIS DIRECTION
 RATHER THAN SUBMIT A LANDSCAPE PERMIT CONCURRENTLY.
  
 A. SEPARATE PERMITS REQUIRED FOR LANDSCAPING, DRIVEWAY,
 AND FENCING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561) 822-1449
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-04-14 Cont ID  
Sent By dkittred Date 2016-04-14 Time 15:46 Rev Time 0.00
Received By dkittred Date 2016-04-14 Time 14:12 Sent To  
Notes
2016-04-14 15:46:17PLANNING AND ZONING COMMENTS: ***FAILED***
  
 4/14/16
  
 1. APPLICATION INDICATES LANDSCAPE PLAN WILL BE
 SUBMITTED AT A LATER DATE. IF LANDSCAPE PLAN IS NOT
 SUBMITTED CONCURRENTLY WITH BUILDING PERMIT FOR THE NEW
 HOUSE CONSTRUCTION, A CONDITIONAL APPROVAL FORM WILL
 NEED TO BE COMPLETED AND SUBMITTED TO THE PLANNING
 DIVISION FOR PROCESSING. PLEASE CONTACT ME FOR A COPY
 OF THIS FORM IF YOU WISH TO PROCEED THIS DIRECTION
 RATHER THAN SUBMIT A LANDSCAPE PERMIT CONCURRENTLY.
  
 2. INCLUDE MECHANICAL EQUIPMENT ON THE SITE PLAN AND
 INDICATE SETBACKS. MECHANICAL EQUIPMENT MAY NOT
 ENCROACH MORE THAN 4 FEET INTO A REQUIRED SETBACK [ZLDR
 SEC. 94-305(B)(4)].
  
 3. INDICATE HOW MECHANICAL EQUIPMENT WILL BE SCREENED
 FROM STREET VIEW IN ACCORDANCE WITH ZLDR SEC.
 94-444(B).
  
 4. INDICATE HEIGHT OF BUILDING FROM FINISHED GRADE
 [ZLDR SEC. 94-72(A)(3)].
  
 GENERAL COMMENTS:
  
 A. SEPARATE PERMITS REQUIRED FOR LANDSCAPING, DRIVEWAY,
 FENCING.
  
 B. FOR REMOVAL OR RELOCATION OF ANY TREES ON THE
 SUBJECT PROPERTY, A TREE ALTERATION MUST FIRST BE
 APPLIED FOR AND OBTAINED FROM THE PLANNING DIVISION.
 HTTP://WWW.WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FOR
 MS/PLANNING-ZONING-FORMS
  
 C. ALL REFERENCED CODE SECTIONS CAN BE FOUND ON
 WWW.MUNICODE.COM BY NAVIGATING TO WEST PALM BEACH.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
  